Chiller Sizing Formulas: Injection Molding Extrusion

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

CHILLER SIZING FORMULAS

INJECTION MOLDING

EXTRUSION
SHEET CALENDERING

HDPE
LDPE
PP
ACRYLIC
PPO
NYLON
DERLIN
UREATHANE
PET
PS
ABS
PC
ACETAL
CELCON
PVC

30 lbs/hour
35 lbs/hour
35 lbs/hour
35 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
60 lbs/hour

PE 35 lbs/hour/ton
ABS 60 lbs/hour/ton
PS 60 lbs/hour/ton
PROFILE & PIPE
HDPE 50 - 60 lbs/hour/ton
LDPE 50 - 60 lbs/hour/ton
PP 50 - 60 lbs/hour/ton
PET 50 - 60 lbs/hour/ton
ABS 60 - 75 lbs/hour/ton
PVC 60 - 75 lbs/hour/ton
EXTRUDER COOLING
Barrel 1 ton/" screw dia.
Screw 2 tons
Throat 1/2 ton up to 3"
Throat 1 ton 4" to 6"
Gear Box (oil) 100 hp / ton

FEED THROAT INJECTION MOLDING:

1/2 ton up to 400 ton machine.


1 ton over 400 ton machine.

BLOW HOLDING

VACUUM FORMING

POLYOLFINS 35 lbs/hour/ton
PET 40 lbs/hour/ton
PVC 70 lbs/hour/ton

HDPE 70 lbs/hour/ton
LDPE 70 lbs/hour/ton
PP 70 lbs/hour/ton
PS 200 lbs/hour/ton
PVC 250 lbs/hour/ton

BLOWN FILM LOAD SIZING


100 CFM
100 CFM
100 CFM

40 F (4.4 C) Air Off 1.14 tons Ent. Glycol 33 F


45 F (7.2 C) Air Off 1.05 tons Ent. Glycol 35 F
50 F (10 C) Air Off 0.85 tons Ent. Water 40 F

Entering Air Conditions


A Guide to calculate the DIE CFM:
1 3 cfm / lb.
2 150 to 170 cfm / inch

90 F dry bulb / 78 F wet bulb


Includes blower motor heat

HOT RUNNER MOLDS:


convert heater watts to btu's and divide by 2. (watts x 3.414 divide by 24,000 Btu

MIXER:
lbs/hour x .5 x temp. difference + 0.2 hp. = tons
12,000 Btu/ton

VACUUM FORMING:
(temp. sheet on - temp. sheet off) x S.H> x lbs/hour = tons
12,000 Btu/ton
* S.H. is specific heat of plastic.
* Approx. temp. in 220 F. and temp. out 100 F.
* Sheet is cooled by the surrounding air, lbs/hour may be increased by 10%

COOLING & HEATING LOAD:


lbs/hour x (temp. start - temp. end) x S.H. = BTUs
* S.H. is specific heat of material.

MOLD HEAT UP TIME:


weight (lbs) x (temp. start - temp. end) x S.H. = Time in Hrs.
heater capacity (Btu's)
* S.H. is specific heat of mold material.

PLATING BATHS:
DC amps x DC volts x 3.414 x 75% eff. = Tons
12,000 Btu/ton

FOR TOWER WATER


COOLING TOWER SIZING
Hydraulic Cooling
Vacuum Pump
Rubber Mills
Gear Drives
Water Pumps
Air Compressor oil
Air Comp. after cooler
Spot Welders
Chiller Condenser

GENERAL FORMULAE

.11 hp / ton
.1 hp / ton
.1 hp / ton
.1 hp / ton
.2 hp / ton
.16 hp / ton
.2 hp / ton
100 kw / ton
1 ton = 1 ton

To run any of the above equipment on a chiller multiply the


tower cooling load by 1.25.

Chiller Ton 12,000 btu


Chiller Flow 2.4 gpm / ton
Chiller Tons gpm x TD div. 24
Chiller With Water Range 42 F to 70 F
Chiller With Glycol Range 15 F to 42 F
Tower Ton 15,000 btu
Tower Flow 3 gpm / /ton
Tower Tons gpm x TD div. 30
Tower Water Range summer 70 F to 85 F, winter a low of 50 F to
85 F
TD - Temperature Difference (between in & out

DIE CASTING:
Zinc - lbs/hour x 35 btu/lb. = Tower Tons
15,000 Btu/ton
Aluminum - lbs/hour x 325 btu/lb. = Tower Tons
15,000 Btu/ton

*(pour at 800 F. Remove at 600 F.)

* (pour at 1200 F. Remove at 600 F.)

STEEL QUENCHING:
Continuous - lbs/hour x 0.166 x (temp. in - temp. out) = Tower Tons
15,000 Btu/ton
Batch - lbs/load x 0.166 x (temp. in - temp. out) = Tower Tons
Quench time (hrs) x 15,000 Btu/ton

FAN BEARINGS:
TRANSFORMER COOLING:
MOLD ROOM COOLING:
TRANSFORMER COOLING:

0.2 ton/fan motor (2 gpm/fan motor)


1 KVA = 1 ton
80 sq. ft./ton (16' ceiling)

1 KVA = 1 ton
* To use any of the above on a chilling system use 12,000 Btu instead of 15,000