Chiller Sizing Formulas: Injection Molding Extrusion
Chiller Sizing Formulas: Injection Molding Extrusion
Chiller Sizing Formulas: Injection Molding Extrusion
INJECTION MOLDING
EXTRUSION
SHEET CALENDERING
HDPE
LDPE
PP
ACRYLIC
PPO
NYLON
DERLIN
UREATHANE
PET
PS
ABS
PC
ACETAL
CELCON
PVC
30 lbs/hour
35 lbs/hour
35 lbs/hour
35 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
40 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
50 lbs/hour
60 lbs/hour
PE 35 lbs/hour/ton
ABS 60 lbs/hour/ton
PS 60 lbs/hour/ton
PROFILE & PIPE
HDPE 50 - 60 lbs/hour/ton
LDPE 50 - 60 lbs/hour/ton
PP 50 - 60 lbs/hour/ton
PET 50 - 60 lbs/hour/ton
ABS 60 - 75 lbs/hour/ton
PVC 60 - 75 lbs/hour/ton
EXTRUDER COOLING
Barrel 1 ton/" screw dia.
Screw 2 tons
Throat 1/2 ton up to 3"
Throat 1 ton 4" to 6"
Gear Box (oil) 100 hp / ton
BLOW HOLDING
VACUUM FORMING
POLYOLFINS 35 lbs/hour/ton
PET 40 lbs/hour/ton
PVC 70 lbs/hour/ton
HDPE 70 lbs/hour/ton
LDPE 70 lbs/hour/ton
PP 70 lbs/hour/ton
PS 200 lbs/hour/ton
PVC 250 lbs/hour/ton
MIXER:
lbs/hour x .5 x temp. difference + 0.2 hp. = tons
12,000 Btu/ton
VACUUM FORMING:
(temp. sheet on - temp. sheet off) x S.H> x lbs/hour = tons
12,000 Btu/ton
* S.H. is specific heat of plastic.
* Approx. temp. in 220 F. and temp. out 100 F.
* Sheet is cooled by the surrounding air, lbs/hour may be increased by 10%
PLATING BATHS:
DC amps x DC volts x 3.414 x 75% eff. = Tons
12,000 Btu/ton
GENERAL FORMULAE
.11 hp / ton
.1 hp / ton
.1 hp / ton
.1 hp / ton
.2 hp / ton
.16 hp / ton
.2 hp / ton
100 kw / ton
1 ton = 1 ton
DIE CASTING:
Zinc - lbs/hour x 35 btu/lb. = Tower Tons
15,000 Btu/ton
Aluminum - lbs/hour x 325 btu/lb. = Tower Tons
15,000 Btu/ton
STEEL QUENCHING:
Continuous - lbs/hour x 0.166 x (temp. in - temp. out) = Tower Tons
15,000 Btu/ton
Batch - lbs/load x 0.166 x (temp. in - temp. out) = Tower Tons
Quench time (hrs) x 15,000 Btu/ton
FAN BEARINGS:
TRANSFORMER COOLING:
MOLD ROOM COOLING:
TRANSFORMER COOLING:
1 KVA = 1 ton
* To use any of the above on a chilling system use 12,000 Btu instead of 15,000