2. TRANSMISSION LINES
The electric parameters of transmission lines (i.e. resistance, inductance, and capacitance) can be
determined from the specifications for the conductors, and from the geometric arrangements of
the conductors.
2.1 Transmission Line Resistance
Resistance to d.c. current is given by
R dc
where
Because of skin effect, the d.c. resistance is different from ac resistance. The ac resistance is
referred to as effective resistance, and is found from power loss in the conductor
R
power loss
I2
The variation of resistance with temperature is linear over the normal temperature range
resistance
( )
R2
R1
T1
T2
temperature (oC)
( R 1 0)
(T1 T)
( R 2 0)
(T2 T)
www.jntuworld.com || www.jwjobs.net
Page 3
T2
T1
R2
T
R1
T
2 10 7 ln
GMD
GMR
[H/m]
where GMR is the geometric mean radius (available from manufacturers tables)
GMD is the geometric mean distance (must be calculated for each line
configuration)
Geometric Mean Radius: There are magnetic flux lines not only outside of the conductor, but
also inside. GMR is a hypothetical radius that replaces the actual conductor with a hollow
conductor of radius equal to GMR such that the self inductance of the inductor remains the same.
If each phase consists of several conductors, the GMR is given by
3
n
GMR
n2
where d11=GMR1
d22=GMR2
.
.
.
dnn=GMRn
Note: for a solid conductor, GMR = r.e-1/4 , where r is the radius of the conductor.
www.jntuworld.com || www.jwjobs.net
Page 4
a
m
GMD
mn '
(Daa ' Dab' ... Dan' ).(Dba ' D bb' ... D bn' ).....(D ma ' Dmb' ..... Dmn' )
r1
r2
D
L1
2 10
ln
D
r1 '
L2
2 10
ln
D
r2 '
L1
L2
4 10
2 10
D2
ln
r1 ' r2 '
ln
D
r1 '
ln
D
r2 '
2 10
1/ 2
4 10
ln
ln
D2
r1 ' r2 '
2 10
1
2
ln
D2
r1 ' r2 '
D
r1 ' r2 '
If r1 = r2 , then
LT
4 10
ln
D
r1 '
www.jntuworld.com || www.jwjobs.net
Page 5
Example: Find GMD, GMR for each circuit, inductance for each circuit, and total inductance
per meter for two circuits that run parallel to each other. One circuit consists of three 0.25 cm
radius conductors. The second circuit consists of two 0.5 cm radius conductor
9m
a
a
6m
6m
b
6m
circuit B
c
circuit A
Solution:
m = 3, n = 2,
GMD
m n = 6
where
D aa ' D bb '
9m
D ab '
D cb '
D ba '
D ca '
12 2
92
62
92
117 m
15 m
GMD = 10.743 m
Geometric Mean Radius for Circuit A:
GMR A
32
D aa D ab D ac D ba D bb D bc D ca D cb D cc
0.25 10
3
4
6 4 12 2
0.481m
GMR B
22
0.5 10
2
4
62
0.153m
Inductance of circuit A
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 6
LA
2 10 7 ln
GMD
GMR A
2 10 7 ln
10.743
0.481
6.212 10
2 10 7 ln
10.743
0153
.
8.503 10
H/m
Inductance of circuit B
LB
2 10 7 ln
GMD
GMR B
H/m
LA
LB
14.715 10
H/m
XL
2 fL
2 f
XL
4 f
10 7 ln
XL
4 f
10
XL
2.022 10
XL
2.022 10
GMD
GMR
GMD
GMR
/m
/m
GMD
/ mile
GMR
GMD
ln
/ mile
GMR
1
ln
2.022 10 3
GMR
1609 ln
ln GMD
/ mile
Xa
Xd
If both, GMR and GMD are in feet, then Xa represents the inductive reactance at 1 ft spacing,
and Xd is called the inductive reactance spacing factor.
Example: Find the inductive reactance per mile of a single phase line operating at 60 Hz. The
conductor used is Partridge, with 20 ft spacings between the conductor centers.
D = 20 ft
www.jntuworld.com || www.jwjobs.net
Page 7
Solution: From the Tables, for Partridge conductor, GMR = 0.0217 ft and inductive reactance at
1 ft spacing Xa= 0.465 /mile. The spacing factor for 20 ft spacing is Xd = 0.3635 /mile. The
inductance of the line is then
X L X a X d 0.465 0.3635 0.8285
/ mile
2 10 7 ln
D eq
GMR
where Deq is the geometric mean of the three spacings of the three phase line.
Deq
Dab Dac D bc
Example: A three phase line operated at 60 Hz is arranged as shown. The conductors are ACSR
Drake. Find the inductive reactance per mile.
20ft
20 ft
38 ft
Solution:
For ACSR Drake conductor, GMR = 0.0373 ft
D eq
L
XL
20 20 38
24.8 ft
24.8
13 10 7
H/m
0.0373
60 1609 13 10 7 0.788
2 10 7 ln
2
/ mile
OR
from the tables X a 0.399
/ mile
The spacing factor is calculated for spacing equal the geometric mean distance between the
/ mile
conductors, that is, X d 2.022 10 3 60 ln 24.8 0.389
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 8
Xa
Xd
0.788
Example: Each conductor of the bundled conductor line shown in the figure is 1272 MCM
Pheasant. Find:
a) the inductive reactance in /km and /mile per phase for d = 45 cm
b) the p.u. series reactance if the length of the line is 160 km and the base is 100 MVA, 345 kV.
8m
8m
Solution:
a) The distances in ft are
0.45
d
1476
.
ft
0.3048
8
D
26.25 ft
0.3048
For Pheasant conductors, GMR = 0.0466 ft.
GMRb for a bundle of conductors is
GMR b
GMR d
0.0466 1476
.
0.2623 ft
2 10 7 ln
D eq
GMR b
2 10 7 ln
33.07
0.2623
9.674 10
H/m
2 fL
60 9.674 10
b) Base impedance Z b
Vb2
Sb
3452
100
3.647 10
/m
0.3647
/ km
0.5868
/ mile
1190
www.jntuworld.com || www.jwjobs.net
Page 9
XL
160 0.3647
X Lp.u.
XL
Zb
58.35
1190
58.35
0.049 p. u.
r1
r2
D
For a two conductor line, the capacitance between the conductors is given by
D2
ln
r1 r2
where
F/ m
www.jntuworld.com || www.jwjobs.net
Page 10
Formally, this equation corresponds to the equation for inductance of a two conductor line. The
equation was derived for a solid round conductor and assuming a uniform distribution of charge
along the conductors. The electric field, and therefore the capacitance of stranded conductors is
not the same as for solid conductors, but if the radii of the conductors are much smaller than the
distance between the conductors, the error is very small and an outside radii of the stranded
conductors can be used in the equation.
For most single phase lines, r1 = r2 . In this case, half way between the conductors there is a point
where E = 0. This is the neutral point n
Can
Cbn
The capacitance from conductor a to point n is Can and is the same as the capacitance from
conductor b to n, Cbn. Can and Cbn are connected in series, therefore C an C bn 2C ab .1
It follows that
C an
[F/m]
D
ln
r
1
2 fC
Since X c
Xc
2 f
1
2
ln
2.862 10 9 D
ln
f
r
D
r
Xc
mile is
1
1609
1779
.
10 6 D
ln
f
r
mile
Similarly as for inductive reactance, this expression can be split into two terms that are called
capacitive reactance at 1 ft spacing (Xa) and the capacitive reactance spacing factor (Xd).
C ab
1
1
C an
Therefore, C an
1
C bn
C an C bn
C an C bn
If Can
C bn , then C ab
C 2an
2C an
C an
2
2Cab
www.jntuworld.com || www.jwjobs.net
Page 11
Xc
1779
.
10 6 1
ln
f
r
1779
.
10 6
ln D
f
Xa
Xd
mile
Xa is given in the tables for the standard conductors, Xd is given in the tables for the capacitive
reactance spacing factor.
Example: Find the capacitive reactance in M miles for a single phase line operating at 60 Hz.
The conductor used for the line is Partridge, and the spacing is 20 ft.
0.642
2
in
0.0268 ft
XC
1779
.
10 6
20
ln
f
0.0268
01961
.
M . mile
OR
.
M . mile
From tables X 'a 01074
'
X d 0.0889 M . mile
X 'a
XC
X 'd
for 20 spacing
01963
.
M . mile
This is the capacitive reactance between the conductor and the neutral. Line-to-line capacitive
reactance is
X CL
XC
2
0.0981 M . mile
Capacitance of Balanced Three Phase Line between a phase conductor and neutral is given by
Cn
2
ln
D eq
F/ m
Db
www.jntuworld.com || www.jwjobs.net
Page 12
1779
.
106 D eq
ln
f
Db
X cn
. mile
Example:
a) A three phase 60 Hz line is arranged as shown. The conductors are ACSR Drake. Find the
capacitive reactance for 1 mile of the line.
b) If the length of the line is 175 miles and the normal operating voltage is 220 kV, find the
capacitive reactance to neutral for the entire length of the line, the charging current for the line,
and the charging reactive power.
20ft
20 ft
38 ft
Solution:
The outside radius for Drake conductors is r
1108
.
in
2
0.0462 ft
Deq
20 20 38
24.8 ft
0.0912 M . mile
1779
.
10 6
1779
.
10 6
ln D eq
ln 24.8
f
60
X cn X 'a X 'd 01864
.
M . mile
X 'd
0.0952 M . mile
X Ctotal
X cn
175
1065
Charging current is
IC
VLN
X Ctotal
220k
3
1065
119 A
www.jntuworld.com || www.jwjobs.net
Page 13
3VLL I C
3 220k 119
45.45 MVAr
E R I equiv cos
I equiv
PR
E R cos
From that,
Ploss
2
equiv
PR
E R cos
R
R
Power utilities usually strive to maintain the receiving end voltage constant. The power delivered
by the transmission line is determined by the load connected to the line and cannot be changed
without changing the load. The only term in the above equation that can be regulated is the
power factor. If the power factor can be adjusted to be equal to 1, the power losses will be
minimum.
Efficiency of the transmission line is given by
PR
100%
PS
Thermal Limits on equipment and conductors depend on the material of the insulation of
conductors. The I2R losses are converted into heat. The heat increases the temperature of the
conductors and the insulation surrounding it. Some equipment can be cooled by introducing
circulation of cooling media, other must depend on natural cooling. If the temperature exceeds
the rated value, the insulation will deteriorate faster and at higher temperatures more immediate
damage will occur.
The power losses increase with the load. It follows that the rated load is given by the temperature
limits. The consequence of exceeding the rated load for short periods of time or by small
amounts is a raised temperature that does not destroy the equipment but shortens its service life.
Many utilities routinely allow short time overloads on their equipment - for example transformers
are often overloaded by up to 15% during peak periods that may last only 15 or 30 minutes.
www.jntuworld.com || www.jwjobs.net
Page 14
UNIT-II
Performance of Short and Medium
Length Transmission Lines
www.jntuworld.com || www.jwjobs.net
Page 15
Whatever may be the category of transmission line, the main aim is to transmit power from one
end to another. Like other electrical system, the transmission network also will have some power
loss and voltage drop during transmitting power from sending end to receiving end. Hence,
performance of transmission line can be determined by its efficiency and voltage regulation.
power sent from sending end line losses = power delivered at receiving end
Voltage regulation of transmission line is measure of change of receiving end voltage from noload to full load condition.
Every transmission line will have three basic electrical parameters. The conductors of the line
will have resistance, inductance, and capacitance. As the transmission line is a set of conductors
being run from one place to another supported by transmission towers, the parameters are
distributed uniformly along the line.
The electrical power is transmitted over a transmission line with a speed of light that is 3X108 m
sec. Frequency of the power is 50Hz. The wave length of the voltage and current of the power
can be determined by the equation given below,
f. = v where f is power frequency, &labda is wave length and v is the speed of light.
www.jntuworld.com || www.jwjobs.net
Page 16
Hence the wave length of the transmitting power is quite long compared to the generally used
line length of transmission line.
For this reason, the transmission line, with length less than 160 km, the parameters are assumed
to be lumped and not distributed. Such lines are known as electrically short transmission line.
This electrically short transmission lines are again categorized as short transmission line (length
up to 80 km) and medium transmission line(length between 80 and 160 km). The capacitive
parameter of short transmission line is ignored whereas in case of medium length line the
capacitance is assumed to be lumped at the middle of the line or half of the capacitance may be
considered to be lumped at each ends of the transmission line. Lines with length more than 160
km, the parameters are considered to be distributed over the line. This is called long transmission
line.
ABCD PARAMETERS
A major section of power system engineering deals in the transmission of electrical power from
one particular place (eg. Generating station) to another like substations or distribution units with
maximum efficiency. So its of substantial importance for power system engineers to be thorough
with its mathematical modeling. Thus the entire transmission system can be simplified to a two
port network for the sake of easier calculations.
The circuit of a 2 port network is shown in the diagram below. As the name suggests, a 2 port
network consists of an input port PQ and an output port RS. Each port has 2 terminals to connect
itself to the external circuit. Thus it is essentially a 2 port or a 4 terminal circuit, having
www.jntuworld.com || www.jwjobs.net
Page 17
www.jntuworld.com || www.jwjobs.net
Page 18
Thus its implies that on applying open circuit condition to ABCD parameters, we get parameter
A as the ratio of sending end voltage to the open circuit receiving end voltage. Since dimension
wise A is a ratio of voltage to voltage, A is a dimension less parameter.
Applying the same open circuit condition i.e IR = 0 to equation (2)
Thus its implies that on applying open circuit condition to ABCD parameters of transmission
line, we get parameter C as the ratio of sending end current to the open circuit receiving end
voltage. Since dimension wise C is a ratio of current to voltage, its unit is mho.
Thus C is the open circuit conductance and is given by
C = IS VR mho.
ABCD parameters when receiving end is short circuited
Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter
B as the ratio of sending end voltage to the short circuit receiving end current. Since dimension
wise B is a ratio of voltage to current, its unit is . Thus B is the short circuit resistance and is
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 19
given by
B = VS IR .
Applying the same short circuit condition i.e VR = 0 to equation (2) we get
Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter
D as the ratio of sending end current to the short circuit receiving end current. Since dimension
wise D is a ratio of current to current, its a dimension less parameter. the ABCD parameters of
transmission line can be tabulated as:Parameter
Specification
Unit
A = VS / VR Voltage ratio
Unit less
B = VS / IR Short circuit resistance
C = IS / VR Open circuit conductance mho
D = IS / IR Current ratio
Unit less
SHORT TRANSMISSION LINE
The transmission lines which have length less than 80 km are generally referred as short
transmission lines.
For short length, the shunt capacitance of this type of line is neglected and other parameters like
resistance and inductance of these short lines are lumped, hence the equivalent circuit is
represented as given below,
Lets draw the vector diagram for this equivalent circuit, taking receiving end current Ir as
reference. The sending end and receiving end voltages make angle with that reference receiving
end current, of s and r, respectively.
www.jntuworld.com || www.jwjobs.net
Page 20
As the shunt capacitance of the line is neglected, hence sending end current and receiving end
current is same, i.e.
Is = Ir.
Now if we observe the vector diagram carefully, we will get,
Vs is approximately equal to
Vr + Ir.R.cosr + Ir.X.sinr
That means,
Vs Vr + Ir.R.cosr + Ir.X.sinr as the it is assumed that s r
As there is no capacitance, during no load condition the current through the line is considered as
zero, hence at no load condition, receiving end voltage is the same as sending end voltage
Here, vr and vx are the per unit resistance and reactance of the short transmission line.
Any electrical network generally has two input terminals and two output terminals. If we
consider any complex electrical network in a black box, it will have two input terminals and
output terminals. This network is called two port network. Two port model of a network
simplifies the network solving technique. Mathematically a two port network can be solved by 2
by 2 matrixes.
A transmission as it is also an electrical network; line can be represented as two port network.
Hence two port network of transmission line can be represented as 2 by 2 matrixes. Here the
concept of ABCD parameters comes. Voltage and currents of the network can represented as ,
Vs= AVr + BIr(1)
Is= CVr + DIr(2)
Where A, B, C and D are different constant of the network.
www.jntuworld.com || www.jwjobs.net
Page 21
Hence, A is the voltage impressed at the sending end per volt at the receiving end when receiving
end is open. It is dimension less.
If we put Vr = 0 at equation (1), we get
That indicates it is impedance of the transmission line when the receiving terminals are short
circuited. This parameter is referred as transfer impedance.
C is the current in amperes into the sending end per volt on open circuited receiving end. It has
the dimension of admittance.
D is the current in amperes into the sending end per amp on short circuited receiving end. It is
dimensionless.
Now from equivalent circuit, it is found that,
Vs = Vr + IrZ and Is = Ir
Comparing these equations with equation 1 and 2 we get,
www.jntuworld.com || www.jwjobs.net
Page 22
The transmission line having its effective length more than 80 km but less than 250 km, is
generally referred to as a medium transmission line. Due to the line length being considerably
high, admittance Y of the network does play a role in calculating the effective circuit parameters,
unlike in the case of short transmission lines. For this reason the modelling of a medium length
transmission line is done using lumped shunt admittance along with the lumped impedance in
series to the circuit.
These lumped parameters of a medium length transmission line can be represented using two
different models, namely.
1) Nominal representation.
2) Nominal T representation.
Lets now go into the detailed discussion of these above mentioned models.
Nominal representation of a medium transmission line
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 23
In case of a nominal representation, the lumped series impedance is placed at the middle of the
circuit where as the shunt admittances are at the ends. As we can see from the diagram of the
network below, the total lumped shunt admittance is divided into 2 equal halves, and each half
with value Y 2 is placed at both the sending and the receiving end while the entire circuit
impedance is between the two. The shape of the circuit so formed resembles that of a symbol ,
and for this reason it is known as the nominal representation of a medium transmission line. It
is mainly used for determining the general circuit parameters and performing load flow analysis.
As we can see here, VS and VR is the supply and receiving end voltages respectively, and
Is is the current flowing through the supply end.
IR is the current flowing through the receiving end of the circuit.
I1 and I3 are the values of currents flowing through the admittances. And
I2 is the current through the impedance Z.
Now applying KCL, at node P, we get.
IS = I1 + I2 (1)
Similarly applying KCL, to node Q.
I2 = I3 + IR (2)
Now substituting equation (2) to equation (1)
IS = I1 + I3 + IR
www.jntuworld.com || www.jwjobs.net
Page 24
Comparing equation (4) and (5) with the standard ABCD parameter equations
VS = A VR + B IR
IS = C VR + D IR
We derive the parameters of a medium transmission line as:
Here also Vs and Vr is the supply and receiving end voltages respectively, and
Is is the current flowing through the supply end. Ir is the current flowing through the receiving
end of the circuit. Let M be a node at the midpoint of the circuit, and the drop at M, be given by
Vm. Applying KVL to the above network we get
www.jntuworld.com || www.jwjobs.net
Page 25
Again comparing Comparing equation (8) and (10) with the standard ABCD parameter equations
VS = A VR + B IR
IS = C VR + D IR
The parameters of the T network of a medium transmission line are
www.jntuworld.com || www.jwjobs.net
Page 26
UNIT-III
Performance of Long Transmission
Lines
www.jntuworld.com || www.jwjobs.net
Page 27
a) Ignoring the shunt admittance of the network, like in a small transmission line model.
b) Considering the circuit impedance and admittance to be lumped and concentrated at a point as
was the case for the medium line model.
Rather, for all practical reasons we should consider the circuit impedance and admittance to be
distributed over the entire circuit length as shown in the figure below.
The calculations of circuit parameters for this reason is going to be slightly more rigorous as we
will see here. For accurate modeling to determine circuit parameters let us consider the circuit of
the long transmission line as shown in the diagram below.
www.jntuworld.com || www.jwjobs.net
Page 28
Here a line of length l > 250km is supplied with a sending end voltage and current of VS and IS
respectively, where as the VR and IR are the values of voltage and current obtained from the
receiving end. Lets us now consider an element of infinitely small length x at a distance x from
the receiving end as shown in the figure where.
V = value of voltage just before entering the element x.
I = value of current just before entering the element x.
V+V = voltage leaving the element x.
I+I = current leaving the element x.
V = voltage drop across element x.
zx = series impedence of element x
yx = shunt admittance of element x
Where Z = z l and Y = y l are the values of total impedance and admittance of the long
transmission line.
the voltage drop across the infinitely small element x is given by
V = I z x
Or I z = V x
Or I z = dV dx (1)
Now to determine the current I, we apply KCL to node A.
I = (V+V)yx = V yx + V yx
Since the term V yx is the product of 2 infinitely small values, we can ignore it for the sake of
easier calculation.
we can write dI dx = V y (2)
Now derevating both sides of eq (1) w.r.t x,
d2 V d x2 = z dI dx
Now substituting dI dx = V y from equation (2)
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 29
d2 V d x2 = zyV
or d2 V d x2 zyV = 0 (3)
The solution of the above second order differential equation is given by.
V = A1 exyz + A2 exyz (4)
Derivating equation (4) w.r.to x.
dV/dx = (yz) A1 exyz (yz)A2 exyz (5)
Now comparing equation (1) with equation (5)
Now to go further let us define the characteristic impedance Zc and propagation constant of a
long transmission line as
Zc = (z/y)
= (yz)
Then the voltage and current equation can be expressed in terms of characteristic impedance and
propagation constant as
V = A1 ex + A2 ex (7)
I = A1/ Zc ex + A2 / Zc ex (8)
Now at x=0, V= VR and I= Ir. Substituting these conditions to equation (7) and (8) respectively.
VR = A1 + A2 (9)
IR = A1/ Zc + A2 / Zc (10)
Solving equation (9) and (10),
We get values of A1 and A2 as,
A1 = (VR + ZCIR) 2
And A1 = (VR ZCIR) 2
Now applying another extreme condition at x=l, we have V = VS and I = IS.
Now to determine VS and IS we substitute x by l and put the values of A1 and A2 in equation (7)
and (8) we get
DEPARTMENT OF EEE - SVECW
www.jntuworld.com || www.jwjobs.net
Page 30
A = cosh l
D = cosh l
www.jntuworld.com || www.jwjobs.net
B = ZC sinh l
Page 31
UNIT IV
Power System Transients
www.jntuworld.com || www.jwjobs.net
Page 32
. e- x = E . e - ( + j ) x = E e - x e - j x
where
represents the attenuation in the length of line x
represents the phase angle change in the length of line x
e-.[
e-j [
Therefore,
.
attenuation constant of the line in neper/km
phase angle constant of the line in rad/km.
It is also common for an attenuation factor k to be defined corresponding to the length of a particular
-.O
line. i.e. k = e for a line of length l.
The propagation constant of a line RI D OLQH RI VHULHV LPSHGDQFH z and shunt
admittance y per unit length is given by
= z.y = (r + j l) (g + j c)
Similarly the surge impedance of the line (or characteristic impedance) Zo
Z0
=
z = (r + j l)
(g + j c)
y
When a voltage surge of magnitude unity reaches a junction between two sections with surge
impedances Z1 and Z2, then a part . is transmitted and a part is reflected back. In traversing the
second line, if the attenuation factor is k, then on reaching the termination at the end of the second
line its amplitude would be reduced to N . . The lattice diagram may now be constructed as follows.
Set the ends of the lines at intervals equal to the time of transit of each line. If a suitable time scale is
chosen, then the diagonals on the diagram show the passage of the waves.
High Voltage Transient Analysis
www.jntuworld.com || www.jwjobs.net
Page 33
(2)
The position of any wave at any time can be deduced directly from the diagram.
(3)
The total potential at any point, at any instant of time is the superposition of all the
waves which have arrived at that point up until that instant of time, displaced in
position from each other by intervals equal to the difference in their time of arrival.
(4)
The history of the wave is easily traced. It is possible to find where it came from
and just what other waves went into its composition.
(5)
Attenuation is included, so that the wave arriving at the far end of a line
corresponds to the value entering multiplied by the attenuation factor of the line.
www.jntuworld.com || www.jwjobs.net
Page 34
UNIT-V
Various Factors Governing the
Performance of Transmission line
www.jntuworld.com || www.jwjobs.net
Page 35
SKIN EFFECT
The phenomena arising due to unequal distribution of current over the entire cross section of
the conductor being used for long distance power transmission is referred as the skin effect
in transmission lines. Such a phenomena does not have much role to play in case of a very
short line, but with increase in the effective length of the conductors, skin effect increases
considerably. So the modifications in line calculation needs to be done accordingly.
The distribution of current over the entire cross section of the conductor is quite uniform in
case of a dc system. But what we are using in the present era of power system engineering is
predominantly an alternating current system, where the current tends to flow with higher
density through the surface of the conductors (i.e skin of the conductor), leaving the core
deprived of necessary number of electrons. In fact there even arises a condition when
absolutely no current flows through the core, and concentrating the entire amount on the
surface region, thus resulting in an increase in the effective resistance of the conductor. This
particular trend of an ac transmission system to take the surface path for the flow of current
depriving the core is referred to as the skin effect in transmission lines
Why skin effect occurs in transmission lines ?
Having understood the phenomena of skin effect let us now see why this arises in case of an
a.c. system. To have a clear understanding of that look into the cross sectional view of the
conductor during the flow of alternating current given in the diagram below.
Let us initially consider the solid conductor to be split up into a number of annular filaments
spaced infinitely small distance apart, such that each filament carries an infinitely small
fraction
of
the
total
current.
Like
if
the
total
current
Lets consider the conductor to be split up into n filament carrying current i such that I = n i .
Now during the flow of an alternating current, the current carrying filaments lying on the core
has a flux linkage with the entire conductor cross section including the filaments of the
surface as well as those in the core. Whereas the flux set up by the outer filaments is
restricted only to the surfaceitself and is unable to link with the inner filaments.Thus the flux
linkage of the conductor increases as we move closer towards the core and at the same rate
increases the inductance as it has a direct proportionality relationship with flux linkage. This
results in a larger inductive reactance being induced into the core as compared to the outer
sections of the conductor. The high value of reactance in the inner section results in the
current being distributed in an un uniform manner and forcing the bulk of the current to flow
through the outer surface or skin giving rise to the phenomena called skin effect in
transmission lines.
www.jntuworld.com || www.jwjobs.net
Page 36
www.jntuworld.com || www.jwjobs.net
Page 37
receiving end voltage tends to get larger than applied voltage leading to the phenomena called
Ferranti effect in power system. It is illustrated with the help of a phasor diagram below.
Thus both the capacitance and inductance effect of transmission line are equally responsible
for this particular phenomena to occur, and hence Ferranti effect is negligible in case of a
short transmission lines as the inductance of such a line is practically considered to be
nearing zero. In general for a 300 Km line operating at a frequency of 50 Hz, the no load
receiving end voltage has been found to be 5% higher than the sending end voltage.
Now for analysis of Ferranti effect let us consider the phasor diagrame shown above.
Here Vr is considered to be the reference phasor, represented by OA.
Thus Vr = Vr (1 + j0)
Capacitance current, Ic = jCVr
Now sending end voltage Vs = Vr + resistive drop + reactive drop.
= Vr + IcR + jIcX
= Vr+ Ic (R + jX)
= Vr+jcVr (R + j L)
[since X = L]
www.jntuworld.com || www.jwjobs.net
Page 38
Now if we consider c0 and L0 are the values of capacitance and inductance per km of the
transmission line, where l is the length of the line.
Thus capacitive reactance Xc = 1/( l c0)
Since, in case of a long transmission line the capacitance is distributed throughout its length,
the average current flowing is,
Ic = 1/2 Vr/Xc = 1/2 Vr l c0
Now the inductive reactance of the line = L0 l
Thus the rise in voltage due to line inductance is given by,
IcX = 1/2Vr l c0 X L0 l
Voltage rise = 1/2 Vr2 l 2 c0L0
From the above equation it is absolutely evident, that the rise in voltage at the receiving end
is directly proportional to the square of the line length, and hence in case of a long
transmission line it keeps increasing with length and even goes beyond the applied sending
end voltage at times, leading to the phenomena called Ferranti effect in power system.
CORONA
Electric-power transmission practically deals in the bulk transfer of electrical energy, from
generating stations situated many kilometers away from the main consumption centers or the
cities. For this reason the long distance transmission cables are of utmost necessity for
effective power transfer, which in-evidently results in huge losses across the system.
Minimizing those has been a major challenge for power engineers of late and to do that one
should have a clear understanding of the type and nature of losses. One of them being the
corona effect in power system, which has a predominant role in reducing the efficiency of
EHV(extra high voltage lines) which we are going to concentrate on, in this article.
What is corona effect in power system and why it occurs?
For corona effect to occur effectively, two factors here are of prime importance as mentioned
below:1) Alternating potential difference must be supplied across the line.
2) The spacing of the conductors, must be large enough compared to the line diameter.
www.jntuworld.com || www.jwjobs.net
Page 39
www.jntuworld.com || www.jwjobs.net
Page 40
www.jntuworld.com || www.jwjobs.net
Page 41
UNIT-VI
OVERHEAD LINE INSULATORS
www.jntuworld.com || www.jwjobs.net
Page 42
There are mainly three types of insulator used as overhead insulator likewise
1. Pin Insulator
2. Suspension Insulator
3. Strain Insulator
In addition to that there are other two types of electrical insulator available mainly for low
voltage application, e.i. Stay Insulator and Shackle Insulator.
Pin Insulator
Pin Insulator is earliest developed overhead insulator, but still popularly used in power
network up to 33KV system. Pin type insulator can be one part, two parts or three parts type,
depending upon application voltage. In 11KV system we generally use one part type insulator
where whole pin insulator is one piece of properly shaped porcelain or glass. As the leakage
path of insulator is through its surface, it is desirable to increase the vertical length of the
insulator surface area for lengthening leakage path. In order to obtain lengthy leakage path,
one, tow or more rain sheds or petticoats are provided on the insulator body. In addition to
that rain shed or petticoats on an insulator serve another purpose. These rain sheds or
petticoats are so designed, that during raining the outer surface of the rain shed becomes wet
but the inner surface remains dry and non-conductive. So there will be discontinuations of
conducting path through the wet pin insulator surface.
In higher voltage like 33KV and 66KV manufacturing of one part porcelain pin insulator
becomes difficult. Because in higher voltage, the thickness of the insulator become more and
a quite thick single piece porcelain insulator can not manufactured practically. In this case we
use multiple part pin insulator, where a number of properly designed porcelain shells are
fixed together by Portland cement to form one complete insulator unit. For 33KV tow parts
and for 66KV three parts pin insulator are generally used.
Designing consideration of Electrical Insulator
The live conductor attached to the top of the pin insulator is at a potential and bottom of the
insulator fixed to supporting structure of earth potential. The insulator has to withstand the
potential stresses between conductor and earth. The shortest distance between conductor and
earth, surrounding the insulator body, along which electrical discharge may take place
through air, is known as flash over distance.
1. When insulator is wet, its outer surface becomes almost conducting. Hence the flash over
distance of insulator is decreased. The design of an electrical insulator should be such that the
decrease of flash over distance is minimum when the insulator is wet. That is why the upper
most petticoat of a pin insulator has umbrella type designed so that it can protect, the rest
lower part of the insulator from rain. The upper surface of top most petticoat is inclined as
less as possible to maintain maximum flash over voltage during raining.
2. To keep the inner side of the insulator dry, the rain sheds are made in order that these rain
sheds should not disturb the voltage distribution they are so designed that their subsurface at
right angle to the electromagnetic lines of force.
www.jntuworld.com || www.jwjobs.net
Page 43
Suspension Insulator
In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size,
weight of the insulator become more. Handling and replacing bigger size single unit insulator
are quite difficult task. For overcoming these difficulties, suspension insulator was
developed.
In suspension insulator numbers of insulators are connected in series to form a string and
the line conductor is carried by the bottom most insulator. Each insulator of a suspension
string is called disc insulator because of their disc like shape.
Advantages of Suspension Insulator
1. Each suspension disc is designed for normal voltage rating 11KV(Higher voltage rating
15KV), so by using different numbers of discs, a suspension string can be made suitable for
any voltage level.
2. If any one of the disc insulators in a suspension string is damaged, it can be replaced much
easily.
3. Mechanical stresses on the suspension insulator is less since the line hanged on a flexible
suspension string.
4. As the current carrying conductors are suspended from supporting structure by suspension
string, the height of the conductor position is always less than the total height of the
supporting structure. Therefore, the conductors may be safe from lightening.