PROTOCOL FOR BOILER COLUMN ALIGNMENT
Client - Raichur Bio Energies Pvt. Ltd.
Location- Yedlapur, Raichur, Karnataka.
Project No. -PD0581
Protocol No.-03
Date-05.06.2013
+Z
-X
BK1
+X
BK2
-Z
BC1
BC3
BC2
BC4
ST1
ST2
BC5
BOILER
FRONT
BC6
BOILER COLUMNS VERTICALITY ALIGNMENT
Sr.No.
Column
Mark No.
BK1
BK2
BC1
BC2
BC3
BC4
BC5
BC6
ST1
10
ST2
BY KAMAL CONST.
Along Axis
-X
+Z
+X
+Z
-X
+Z
-X
-Z
+X
+Z
+X
-Z
+X
+Z
+X
-Z
-X
-Z
+X
-Z
Top
Plumb readings
Middle
Bottom
400
398
397
400
402
404
400
404
408
400
403
405
400
401
402
400
402
403
400
402
404
400
398
396
400
401
403
400
402
405
400
401
403
400
399
398
400
403
405
400
397
394
400
403
405
400
398
394
400
398
396
400
399
396
400
402
405
400
396
393
BY TIL
Max.
Deviation
-3
+4
+8
+5
+2
+3
+4
-4
+3
+5
+3
-2
+5
-6
+5
-6
-4
-4
+5
-7
Remark
BY RBEPL
BY RBEPL
PROTOCOL FOR BOILER COLUMN ALIGNMENT
Client - Raichur Bio Energies Pvt. Ltd.
Location- Yedlapur, Raichur, Karnataka.
Project No. - PD0581
Protocol No.-03
Date-05.06.2014
BOILER COLUMNS ELEVATION ALIGNMENT
Column Assembly
SR. NO.
EL+5300
BY KAMAL CONST.
1
2
3
4
5
6
7
8
9
10
COLUMN ELEVATION AS PER
ACTUAL
MARK NO.
DRAWING
ELEVATION
BK1
+5300
+5300
BK2
+5300
+5301
BC1
+5300
+5301
BC2
+5300
+5299
BC3
+5300
+5300
BC4
+5300
+5300
BC5
+5300
+5300
BC6
+5300
+5302
ST1
+5300
+5300
ST2
+5300
+5301
BY TIL
NT
Protocol No.-03
Date-05.06.2014
VATION ALIGNMENT
DEVIATION REMARK
0
+1
+1
-1
0
0
0
+2
0
+1
BY RBEPL