Cable Codification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Code Corner

AWG,
RHW,
CNN, USE-2,
THHN, THW,
XLPE, #@%*&!
John Wiles
Sponsored by the Photovoltaic Systems Assistance Center, Sandia National
Laboratories

ont understand the designations,


types, and sizes of conductors
used in PV systems? Read on. In
the next several issues of Code Corner,
we will deal with the wires, cables, and
conductors used in a PV system. Wind
power installers should also take note:
the conductor requirements for wind
systems are very much like those for PV
systems and any other electrical
systems.

Conductors, Wires, CablesWhats the Difference?


Many people use the terms conductor, wire, and
cable interchangeably. I do too. The NEC uses the
terms in specific ways, but it also uses the terms
interchangeably. Here are some definitions found in
Article 100 of the National Electrical Code (NEC).
Conductor
Bare A conductor having no covering or electrical
insulation whatsoever.
Covered A conductor encased within material of
composition and thickness that is not recognized by this
Code as electrical insulation.
Insulated A conductor encased within material of
composition and thickness that is recognized by this
Code as electrical insulation.
Premises Wiring (System) That interior and exterior
wiring including power, lighting, control, and signal

128

Home Power #76 April / May 2000

circuit wiring together with all of their associated


hardware, fittings, and other devices, both permanently
and temporarily installed, that extends from the service
point of utility conductors or source of power such as a
battery, a solar photovoltaic system, or a generator,
transformer, or converter windings to outlet(s). Such
wiring does not include wiring internal to appliances,
fixtures, motors, controllers, motor control centers, and
similar equipment.
Service Conductors The conductors from the service
point to the service disconnecting means.
Service Cable Service conductors made up in the form
of a cable.
Section 800-2 (Communications Circuits) has the
following definition:
Cable A factory assembly of two or more conductors
having an overall covering.
Other sections of the Code mention single conductor
cablesthe Code does not always define a cable as
two or more conductors grouped together. Multipleconductor cables may or may not have an outer jacket
depending on their use and the applicable code
requirements. For example, the power cable on an
electric drill may have three conductors and be required
to have an outer jacket, such as conductor type SOW.
On the other hand, a type USE underground service
entrance cable may also have three conductors; two
are insulated, one is bare, and there may not be a
requirement for an outer jacket in some installations.
Section 300-3(a) of the NEC says that single
conductors specified in this code must be installed as
part of a code-recognized wiring system. The process
of obtaining listing by Underwriters Laboratories or
other testing laboratories poses similar constraints on
the use of these cables.
Conductor Properties
The Properties of Common Conductors table lists some
commonly used conductors and a few of their
characteristics. These have been extracted from NEC
Table 310-13.
The first column (Type) shows the conductor type
designation. The second column (Temp. C/F) shows
temperature rating of the insulation in degrees
Celsius/degrees Fahrenheit. The third column (Moist.)
shows the highest moisture condition allowed at this
temperature. The fourth column (Conduit) indicates
whether or not the conductor must be installed in some
sort of conduit or raceway. The last column (Sunlight
Res.) shows whether the conductor is inherently
sunlight resistant (with no marking) or not, or whether it
must be marked sunlight resistant if applicable. In some

Code Corner

Properties of Common Conductors


Type

THHN
THWN
THWN
THWN-2
THW
THW-2
RHW
RHW-2
RHH
USE
USE-2
UF
SE

Temp. C/F Moist. Conduit Req. Sunlight Res.

90/194
75/167
90/194
90/194
75/167
90/194
75/167
90/194
90/194
75/167
90/194
60/140
75/167

Damp
Wet
Dry
Wet
Wet
Wet
Wet
Wet
Damp
Wet
Wet
Wet
Wet

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No

No
No
No
No
No
No
No
No
No
Yes
Yes
Marked
Yes

cases, the conductor has insulation rated at more than


one temperature. A second entry for the same cable
type shows the secondary temperature/moisture data
(see THWN).
By this time, your eyes are crossed, you have a
headache, and Ill bet at least some of you are
wondering about the alphabet soup. The Wire & Cable
Types table has the insiders info on what all those
letters stand for in the Proper ties of Common
Conductors Type column.
Many conductors will be marked as two or more types,
indicating that they meet the listing requirements for
each type. An example is a conductor marked THHN
or THWN-2. This dual or triple marking indicates that
the conductor has the properties of both types and can
be used in the worst-case environment specified for
either (for example, 90C (194F) and wet). Another
example is a conductor marked USE-2 or RHW-2.
Because they have no flame retardant, conductor types
marked with just USE-2 cannot be used in conduit
inside buildings. However, conductor type RHW-2 does
have the flame retardant, so the dual-marked cable can
be used outside in sunlight, underground, and in
conduit inside buildings.
Section 690-31 of the NEC allows single conductors in
types UF, USE, USE-2 (will be in the 2002 NEC), and
SE to be used for connecting PV modules where the
conductors are exposed in free air and subject to those
outdoor sunlit and wet conditions. PV module junction
boxes may operate as hot as 75C (167F). From the
above chart, types SE, USE, and UF should be ruled
out for most installations, and only used in very cold
climates. A dual-marked conductor such as USE-2 or
RHW-2 is one of the best conductors to use for
connecting PV modules since it can also be run through
conduit to interior locations.

Multiconductor Cables
There are several multiconductor, sheathed cables that
do not have to be installed in conduit for protection if
they are afforded physical protection by the location of
the installation. The first cable is the very common
nonmetallic sheathed cable, type NM, commonly sold
as standard Romex . It has two or three insulated
conductors and a bare equipment-grounding conductor
enclosed in an outer jacket or sheath. This cable is
approved for use in residential, dry locations (as in the
walls of a house), and has a final temperature rating of
60C (140F). It is not sunlight resistant and cannot be
used in damp or wet locations.
A second multiconductor sheathed cable is type UF that
also must be installed with physical protection in mind.
It is frequently marked sunlight resistant and usually
has a temperature rating of 60C (140F). This cable
can be installed outdoors as long as it is out of the
sunlight and solar heating areas. It might be used for
wiring from a PV combiner box mounted in the shade
on the roof to a PV power center located in the house.
Summary
So, where do we use which? Conductors in conduits or
raceways can be used for nearly any wiring in a PV
system. Local codes may require that conduit be used
in commercial installations. As mentioned above,
modules may be connected to each other and to nearby
combiner boxes by using certain types of exposed
single-conductors (USE-2). Wiring inside buildings may
be made with the sheathed cables (NM and UF).
Battery and inverter conductors tend to be rather large
in size and relatively stiff. Conductor types RHW and
THW are available in fine-stranded varieties that are
considerably more flexible than the normal conductors
available at the local building or electrical supply store.
Dealers and distributors in the PV industry stock or can
get these flexible conductors.
Wire & Cable Types
Type

T
H
HH
N
W
R
U
USE
UF
SE
-2

Description

Thermoplastic insulation
75C (Note: lack of "H" indicates 60C)
90C
Nylon jacket
Moisture resistant
Rubber insulation
Underground use
Underground Service Entrance *
Underground Feeder *
Service Entrance *
90C and wet

* May be either single conductor or multiple conductor cable

Home Power #76 April / May 2000

129

Code Corner

In the next Code Corner, I will address the ampacity


and sizing of the conductors used in renewable energy
systems.
Questions or Comments?
If you have questions about the NEC or the
implementation of PV systems following the
requirements of the NEC, feel free to call, fax, email, or
write me. Sandia National Laboratories sponsors my
activities in this area as a support function to the PV
Industry. This work was supported by the United States
Department of Energy under Contract DE-AC0494AL8500. Sandia is a multi-program laboratory
operated by Sandia Corporation, a Lockheed Martin
Company, for the United States Department of Energy.
Access
Author: John C. Wiles, Southwest Technology
Development Institute, New Mexico State University,
Box 30,001/ MSC 3 SOLAR, Las Cruces, NM 88003
505-646-6105 Fax: 505-646-3841 [email protected]
www.nmsu.edu/~tdi
Sponsor: Sandia National Laboratories, Ward Bower,
Department 6218, PO Box 5800 MS 0753,
Albuquerque, NM 87185-0753 505-844-5206
Fax: 505-844-6541 [email protected]
www.sandia.gov/pv
National Electrical Code and NEC are registered
trademarks of the National Fire Protection Association.
The 1999 NEC and the NEC Handbook are available
from the NFPA, 11 Tracy Dr., Avon, MA 02322
800-344-3555 or 508-895-8300 Fax: 800-593-6372 or
508-895-8301 [email protected] www.nfpa.org

130

Home Power #76 April / May 2000

You might also like