DATA Water

The document summarizes the input parameters for a water supply system simulation. It includes: 1) The daily and peak water demand rates which are 2.94 L/sec and 7.35 L/sec respectively. Node information including hydraulic head, reduced level, and flow rates are provided. Pipes connecting the 6 nodes have diameters of 150mm and lengths ranging from 5 to 178 meters. 2) The hydrant pipe simulation with a fire flow rate of 25.77 L/sec which is the average flow plus a fire flow rate. The same 6 nodes are used with the hydrant pipe having diameters of 150-200mm and lengths matching the domestic pipe.

Uploaded by

MatAleng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views2 pages

DATA Water

The document summarizes the input parameters for a water supply system simulation. It includes: 1) The daily and peak water demand rates which are 2.94 L/sec and 7.35 L/sec respectively. Node information including hydraulic head, reduced level, and flow rates are provided. Pipes connecting the 6 nodes have diameters of 150mm and lengths ranging from 5 to 178 meters. 2) The hydrant pipe simulation with a fire flow rate of 25.77 L/sec which is the average flow plus a fire flow rate. The same 6 nodes are used with the hydrant pipe having diameters of 150-200mm and lengths matching the domestic pipe.

Uploaded by

MatAleng
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

WATER SUPPLY SYSTEM

1) INPUT FOR DOMESTIC PIPE


Water Demand

: 25410m3 (For whole building)


25410 X

Total Daily Water Demand :

1000
=254100 l/day
100

254100 1 1
x x
24
60 60

Average Flow Rate :

= 2.94 l/sec

: 2.5 x Average Flow Rate

Peak Flowrate

2.5 x 2.94 = 7.35 l/sec


Bil
1
2
3
4
5
6

Node
1
2
3
4
5
6

Draw Off
-7.35
0
0
0
0
7.35

Hydraulic Head
130
120
110
100
90
90

Reduced Level
45
46
46
46
46
46

Indicator
1
0
0
0
0
0

INPUT DOMESTIC PIPE CARDS

Bil

1ST Node

2ND Node

Pipe Diameter

Pipe Length

1
2
3
4
5

1
2
3
4
5

2
3
4
5
6

150
150
150
150
150

178
110
25.2
5
5.25

2) INPUT FOR HYDRANT PIPE


Hydrant Flow (fire flow) = Average flow + Fire flow

Roughness
Coefficient
100
100
100
100
100

2.94 + (1370 x (1/60))

25.77lit/sec

Bil
1
2
3
4
5
6

Node
1
2
3
4
5
6

Draw Off
-25.77
0
0
0
o
25.77

Hydraulic Head
130
120
110
100
90
90

Reduced Level
45
46
46
46
46
46

Indicator
1
0
0
0
0
0

INPUT HYDRANT PIPE CARDS

Bil

1ST Node

2ND Node

Pipe Diameter

Pipe Length

1
2
3
4
5

1
2
3
4
5

2
3
4
5
6

200
200
150
150
150

178
110
25.2
5
5.25

Roughness
Coefficient
100
100
100
100
100

You might also like