0% found this document useful (0 votes)
125 views8 pages

Simple Loop1

This document appears to be calculations for expansion loops on three different sized pipes. It includes inputs like pipe diameter, wall thickness, bend radius, loop height and width, guide spacing, and material properties. It then shows the calculations for properties like pipe inertia, flexibility factor, centroid of inertia, bending moment, stress, guide force, and anchor load. It notes the stress is too high for one of the pipes and includes notes about default and maximum suggested values.

Uploaded by

josediaz141
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views8 pages

Simple Loop1

This document appears to be calculations for expansion loops on three different sized pipes. It includes inputs like pipe diameter, wall thickness, bend radius, loop height and width, guide spacing, and material properties. It then shows the calculations for properties like pipe inertia, flexibility factor, centroid of inertia, bending moment, stress, guide force, and anchor load. It notes the stress is too high for one of the pipes and includes notes about default and maximum suggested values.

Uploaded by

josediaz141
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 8

Aker Kvaerner (Solent office)

Proj' No'
Calc' No'
142/
Area No'
Item Tag
Ref' Drg' No'
Sheet No'

PROJECT
SUBJECT FLAT EXPANSION LOOP CALCULATION
PR'P'D BY
CH'K'D BY
APP'D BY
DATE
DATE
DATE

Of

Colour key :
Loop width

mandatory input
optional input

Guide sp. 2

Loop height

Anchor or Line Stop

intermediate result
final result
error / warning

Guide sp. 1
Guides

Anchor distance
Notes

Line No.

6"-1001

8"-2002

12"-3003

Location

grid 1 & 11

grid 2 & 22

grid 3 & 33

Outside Dia' [mm]

168.3

219.1

304.8

Wall thk' [mm]

7.112

6.350

6.350

Bend Rad' [mm]

228.6

304.8

381.0

Ec (N/mm )
Anchor dist' [m]

2.034E+05
100.000

2.034E+05
100.000

2.034E+05
100.000

Des' temp' (ref')[C]

5 - 427

5 - 427

5 - 427

Material or PipeSpec'
[ref']

CS-1

CS-1

CS-1

Exp' Rate [mm/m]

5.761

5.761

5.761

Total Exp' [mm]

576.1

576.1

576.1

Loop height [mm]

5500

6000

6500

Loop width [mm]

5500

6000

6500

Guide sp' 1 [mm]

12000

12000

12000

Guide sp' 2 [mm]

18000

18000

18000

Exp' anchor load [N]

7969

10154

15732

Guide load [N]

1767

2538

4334

368.2

405.5

472.4

Exp' stress [N/mm2]


Allow' stress [N/mm ]

172.0

172.0

172.0

Friction coeff'

0.00

0.00

0.00

Pipe weight [N/m]

0.0

0.0

0.0

Frict' anchor
load [N]
Total Anchor
load [N]

7969

10154

15732

WARN Stress TOO HIGH !!


Suggested default
= 1.25 x Sc

Suggested maximum
= 70kN per beam

NOTES :

Simple-loop.xls

Pipe Dia, D =

168.3

[mm]

Wall thk.

7.112

[mm]

Cold Modulus, Ec

203395

Loop height, H =

5500.0

[mm]

Loop width, W =

5500.0

1st Guide spacing, G =

12000.0

[mm]

2nd Guide spacing =

18000.0

1.172E+07

[mm4]

Elbow radius, R

228.6

[mm]

Flex. characteristic, h

0.250

Bend SIF,

2.27

Total exp., S

576.1

[mm]

Length, L = G - 8R+2H+2RK =

30639.62

[mm]

Dim., Y = (2W - G)(H/2)/L =

-89.7531

[mm]

Pipe Inertia, I

Pipe Modulus, Z 1.393E+05


Pipe mean radius, r2

80.6

Flexibility factor, K

6.59

I CG =2(W-2R)(H/2)2+2RK(H/2-0.363R)2+(((H-2R)3)/6)+(G-2W)*(H/2)2-(L*Y2)
I CG = 172309690432 [mm3]
Mp = Fx (H/2 + Y) =

21200437

[Nmm]

M = greater of Mp & Mc =

22630984

[Nmm]

Stress = M**D/(2*I) =

368

[MPa]

Guide force, GF = Mp / G2 * 1.5 =

1767

[N]

Fx =S I E / ICG =

7969

Mc = Fx (H/2 - Y) = 22630984

[MPa]
[mm]
[mm]
[mm3]
[mm]

[N]
[Nmm]

Pipe Dia, D =

219.1

[mm]

Wall thk.

6.350

[mm]

Cold Modulus, Ec

203400

Loop height, H =

6000.0

[mm]

Loop width, W =

6000.0

1st Guide spacing, G =

12000.0

[mm]

2nd Guide spacing =

18000.0

2.403E+07

[mm4]

Elbow radius, R

304.8

[mm]

Flex. characteristic, h

0.171

Bend SIF,

2.92

Total exp., S

576.1

[mm]

40035.95

[mm]

0.0000

[mm]

Pipe Inertia, I

Length, L = G - 8R+2H+2RK =
Dim., Y = (2W - G)(H/2)/L =

Pipe Modulus, Z 2.194E+05


Pipe mean radius, r2

106.4

Flexibility factor, K

9.65

I CG =2(W-2R)(H/2)2+2RK(H/2-0.363R)2+(((H-2R)3)/6)+(G-2W)*(H/2)2-(L*Y2)
I CG = 277362533901 [mm3]
Mp = Fx (H/2 + Y) =

30461503

[Nmm]

M = greater of Mp & Mc =

30461503

[Nmm]

Stress = M**D/(2*I) =

406

[MPa]

Guide force, GF = Mp / G2 * 1.5 =

2538

[N]

Fx =S I E / ICG =

10154

Mc = Fx (H/2 - Y) = 30461503

[MPa]
[mm]
[mm]
[mm3]
[mm]

[N]
[Nmm]

Pipe Dia, D =

304.8

[mm]

Wall thk.

6.350

[mm]

Cold Modulus, Ec

203400

Loop height, H =

6500.0

[mm]

Loop width, W =

6500.0

1st Guide spacing, G =

12000.0

[mm]

2nd Guide spacing =

18000.0

6.632E+07

[mm4]

Elbow radius, R

381.0

[mm]

Flex. characteristic, h

0.109

Bend SIF,

3.95

Total exp., S

576.1

[mm]

Length, L = G - 8R+2H+2RK =

58307.76

[mm]

Dim., Y = (2W - G)(H/2)/L =

55.7387

[mm]

Pipe Inertia, I

Pipe Modulus, Z 4.352E+05


Pipe mean radius, r2

149.2

Flexibility factor, K

15.19

I CG =2(W-2R)(H/2)2+2RK(H/2-0.363R)2+(((H-2R)3)/6)+(G-2W)*(H/2)2-(L*Y2)
I CG = 493978960165 [mm3]
Mp = Fx (H/2 + Y) =

52006044

[Nmm]

M = greater of Mp & Mc =

52006044

[Nmm]

Stress = M**D/(2*I) =

472

[MPa]

Guide force, GF = Mp / G2 * 1.5 =

4334

[N]

Fx =S I E / ICG =

15732

Mc = Fx (H/2 - Y) = 50252275

[MPa]
[mm]
[mm]
[mm3]
[mm]

[N]
[Nmm]

History
1. Original loop formula developed by ????? (scan in sheet)
2. Results are found to be conservative compared to Caesar.
2. This spreadsheet modified from original uncertain origin by SEB July 03.
3.

QA.
Scan in QA from Caesar etc.

You might also like