100% found this document useful (1 vote)
314 views103 pages

Fire Protection Facilities

The document discusses fire protection facilities for plants. It covers various aspects of plant design, variables that influence safety, layers of protection, hazards like fire, explosion and toxic risks. It also discusses ignition sources, methods to eliminate fire potentials, emergency material transfer, fire spread limitation, fire protective insulation, storage layout, firefighting methods, classification of fires, active fire protection systems like alarm, detection, water supply, firefighting agents and fixed/mobile systems.

Uploaded by

agusnurcahyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
314 views103 pages

Fire Protection Facilities

The document discusses fire protection facilities for plants. It covers various aspects of plant design, variables that influence safety, layers of protection, hazards like fire, explosion and toxic risks. It also discusses ignition sources, methods to eliminate fire potentials, emergency material transfer, fire spread limitation, fire protective insulation, storage layout, firefighting methods, classification of fires, active fire protection systems like alarm, detection, water supply, firefighting agents and fixed/mobile systems.

Uploaded by

agusnurcahyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 103

Fire Protection Facilities

PLANT DESIGN

Tahapan design :
Research
laboratory - scale experiment
Pilot plant
Commercial production

PLANT DESIGN

Variabel yang mempengaruhi safety :


Plant lay out
Equipment design & integrity
Operating tech. & procedure

Layer of Protection
Fisrt layer

: Safe Plant Design

Second layer : Basic proces control, operator supervision


Third layer

: Critical alarm for toxic gas and fire detection, manual


intervention.

Forth layer

: Automatic action, including process shutdown

Fifth layer
flare,

: Physical protection, eg. Pressure relief valve route to


concrete dikes

Sixth layer

: Emergency response with trained responders

HAZARD
Potentials Petro-Chem Risk ;
Fire
Explosion
Toxic

Event
Result
Local detonation
no homogenous
cloud

Vapor cloud
explosion
NONE

No ignition

Release

And
dispersionn

Detonation

Vapor cloud
detonation

No ignition

Deflagratio
n
No enhancement

Deflagratio
n

Detonation
enhancemen
by turbulencet

Detonation
homogenous
cloud

Flashfire
Vapor cloud
Detonation

transition

Vapor cloud
explosion
no transition

Deflagration

Fire

Menyadari bahwa prevention tidak pernah 100


%
berhasil, maka diperlukan perencanaan dan
desain.
Sehingga kerusakan dapat di mitigate jika
terjadi kebakaran (fire).

FIRE

Fire protection of process plant

Pasive prevention or protection


- Mencegah agar tidak timbul fire
- Membatasi efek atau penyebaranya

Active protection - - - Aktivitas


pemadaman

FIRE
-ESSENTIAL CONDITION FOR A FIRE :
1. FUEL
2. OXYGEN
3. HEAT

FIRE

FIRE

1. IGNITION SOURCES ON PROCESS PLANTS

GENERAL
FLAME
HOT WORK
HOT SURFACE
FRICTION AND IMPACT
HOT MATERIAL OR GAS
PYROPHORIC
ENGINE
CHEMICAL EFFECT
VIHECLES
ATMOSPHERIC
RADIO FREQ. & TRANSMISION
ARSON/SABOTAGE
COMPRESION
ELECTRICAL STATIC/SPARK
MECHANICAL FAILURE

INTERNAL
AUTO IGNITION COMPRESSION
REACTIVE,UNTABLE MATERIAL
CATALYTIC MATERIAL
HOT MATERIAL
HOT SURFACE
ELECTRICAL
SELF HEATING
STATIC ELECTRICITY

MENGHILANGKAN POTENSI FIRE

Hazard analysis
Process design
Equipment design
Material of Connstruction
Mechanical design & construction
Process control system
Climate and geography

2. EMERGENCY MATERIAL TRANSFER

DRAIN

RELIEF VALVES

FLARE SYSTEM

3. FIRE SPREAD LIMITATION

DIKING
REMOTE IMPOUNDING
FIRE WALLS
FIRE WINDOW/FIRE DOOR
FLAME ARRESTER

4. FIRE PROTECTIVE INSULATION

FIRE RESISTANCE THERMAL


INSULATION

FIRE INSULATION

5. STORAGE LAYOUT

TANK

PROCESS

UTILITY

OFFSITE FACILITY

Sarana Pemadaman

Keselamatan manusia dan perlindungan


aset merupakan alasan utama perlu
tidaknya suatu pabrik atau bangunan
dilengkapi sarana pemadam kebakaran

METODA PEMADAMAN :
- Pendinginan ( Cooling)
- Penyelimutan ( Smothering)
- Starvation ( Pengurangan sumber )
- Memutus Rantai Reaksi Pembakaran

Klasifikasi Kebakaran
(Ref. Per.Menaker & Trans. No:Per-04/Men/1980 Tgl.14
April 1980)

CLASSIFICATION OF FIRES ( PROCESS


INDUSTRIES

VAPOUR CLOUD FIRE : A. FIRE WITH NO EXPLOTION


B. FIRE RESULTING FROM EXPLOTION
C. FIRE RESULTING IN EXPLOTION
FIRE BALLS
JET FLAMES
LIQUID FIRES : A. POOL FIRES
B. RUNNING LIQUID FIRES
SOLIDS FIRES : A. FIRES OF SOLID MATERIALS
B. DUST FIRES
WAREHOUSE FIRES
FIRES ASSOCIATED WITH OXYGEN

ACTIVE FIRE PROTECTION

1. Fire Alarm System


2. Fire Detection System
3. Fire Water Supply System
4. Fire Fighting Agent
5. Fixed Fire Fighting System
6. Mobile Fire Fighting System

1. Fire Alarm System


- Adalah sistim peringatan kebakaran,
bekerja
secara manual, semi otomatis atau
otomatis.
- Pemasangan harus disesuaikan dengan
sifat tempat kerja (menghindari panik).
- Bisa berupa : bel, klakson, sirene, lampu,
dsb.

FIRE ALARM SYSTEM

Bel

Kotak Pemecah

Lampu Merah

Manual Tombol

2. FIRE DETECTION SYSTEM

Fire Detection System adalah sistim


peralatan untuk mendeteksi adanya
api/kebakaran secara tepat dan cepat
untuk diteruskan ke Fire Station.

Dalam pemasangannya, perlu diperhatikan


hal
hal sebagai berikut :
- Kecepatan meluasnya kebakaran
- sifat bahan yang dilindungi
- waktu tempuh Fire Brigade
Bila bahan-bahan tersebut cepat terbakar
dan perambatannya sangat cepat, serta
waktu tempuh Fire Brigade ke lokasi
kebakaran
lebih dari 20 menit, maka
sistim deteksi kebakaran tidak perlu
dipasang. Harus dipikirkan sistem deteksi
yang lain ( gas detection)

Fire Signatures and Commercially Available Detectors


Fire Signature/
Detector Type

ER Wave Length ER Thermal Product Product Rapid Change High Temp


1700-2900
6500-8500
< 0,1
> 0,1
in Temp.
Angstroms
Angstroms Micron Micron

UV Detector

IR Detector

Smoke Detector:
Photoelectric
Ionization
Photo Beam
Rate of Rise Heat Det.

X
X
X
X

Rate Anticipitation Heat Det.

Fixed Temperature Heat Det

Prinsip Kerja Heat Detector :

Thermal Expansion : pemuaian logam , gas,


atau cairan karena adanya kenaikan panas.

Low Melting Point Alloy : pelelehan logam


campuran yang mempunyai titik leleh
rendah.

Resistance / Temperature Effect : adanya


pengaruh tahanan listrik atau pengaruh
suhu.

Thermo Electric Effect : adanya pengaruh


panas dari listrik.

DETECTOR PANAS

A).

PEMUAIAN LANGSUNG LOGAM

LAMPU
MERAH
BEL

LOGAM
NORMAL

OPERASI

DETECTOR PANAS

B).

PEMUAIAN 2 BUAH LOGAM

LAMPU
MERAH
BEL

LOGAM

LOGAM

NORMAL

OPERASI

DETECTOR PANAS

C/D.

PEMUAIAN CAIRAN / GAS

LAMPU MERAH
BEL

MEMBRANE

GAS/CAIRAN

NORMAL

OPERASI

Penempatan Detektor Panas


1. Pada langit-langit : minimum 4 inch dari dinding. Bila
pada dinding : 4 12 inch dari langit-langit.
2. Untuk langit-langit yang rata, jarak antara detektor
tidak boleh melebihi jarak maksimum sesuai
spesifikasi teknis masing-masing detektor.
3. Bila langit - langit terdiri dari balok-balok, jarak
antar detektor maksimum 50% dari jarak untuk
langit-langit rata.
4. Untuk langit-langit miring, 1 detektor harus dipasang
paling jauh 3 feet diukur dari puncak langit-langit.
Untuk langit-langit dengan tinggi 10 30 feet, jarak
antar detektor harus dikalikan faktor reduksi.

FAKTOR REDUKSI
TINGGI LANGIT2 (FT)

0 10
10 12
12 14
14 16
16 18
18 20
20 22
22 24
24 26
26 28
28 30

% X JARAK YANG DIIZINKAN

100
91
84
77
71
64
58
52
46
40
34

SMOKE DETECTOR
Prinsip kerja :
Pemecahan atom (Ionisasi):
Partikel asap
akan menyebabkan perubahan ion dalam
ruang
detector
yang
kemudian
akan
menggerakkan relay.
Sumber radioaktif yang umum dipakai adalah
Americium-241.

Photo Electric Cells :


Bekerja atas dasar perubahan intensitas
cahaya. Cahaya akan menjadi kabur bila
terkena asap.
Pengurangan
intensitas
tersebut akan menyebabkan detektor
bekerja.

FLAME DETECTOR :
Flame detector akan mendeteksi api atas
dasar cahaya yang dipancarkan api dan
frekuensi modulasi nyala.
Jenisnya : UV dan Infrared Detector. Panjang
gelombang UV harus kurang dari 2.900
Angstroom (agar tidak menangkap cahaya
UV dari matahari).

SISTIM ALIRAN LISTRIK DETEKTOR


Sistim Tertutup : Aliran listrik selalu ada
pada jaringan tersebut, dan bila ada
pengaruh asap / panas ,maka aliran listrik
akan terputus.
Sistim Terbuka : Aliran listrik tidak ada
didalam jaringan tersebut. Apabila ada
pengaruh asap / panas pada detektor,
barulah terjadi aliran listrik dan kemudian
menggerakkan relay.

Pemeriksaan, Pengujian dan Pemeliharaan Deteksi dan Alarm Kebakaran:


Fire Alarm System
Fire Detector
Manual Station, Horn, Bell
Sistim Alarm Suara
Sistim Alarm Telegrafis
Check Visual

bulanan

Check 3 bulanan

Initiating Device Circuit


Signaling Devices Circuit
Two Way Communication

Check 6 bulanan

Remote Announciator
Fuse; Rating
Tegangan tiap Cell Battery

NO

EXTINGUISMENT

CLASSOFFIRE
A:GREEN

B:RED

C:BLUE

WATER

GOOD

VERYPOOR

HAZARDOUS

CARBONDIOXIDE

POOR

GOOD

GOOD

FOAM

FAIR

GOOD

GOOD

DRYCHEMICAL
ORDINARYFORM

POOR

GOOD

GOOD

DRYCHEMICAL
MULTYPURPOSE

GOOD

GOOD

GOOD

HLOGENATEDHYDROCARBON

GOOD

GOOD

GOOD

CLASSA:FIREINVOLVINGORDINARYSOLIDFUELSSUCHASWOOD,
PAPER,ANDSOON.
CLASSB:FIREINVOLVINGLIQUIDANDGASEOUSFUELS.
CLASSC:FIREINENERGIZEDELECTRICCIRCUITSANDEQUIPOMENT
CLASSD:FIREINVOLVINGCOMBUSTIBLEMETAL

Sistim Pemadam Air


Sistim pemancar air (water sprinkler system) adalah
Instalasi pemadam kebakaran yang terintegrasi antara sistim perpipaan, alarm, kerangan pengontrol
dan katup pemancar air (sprinkler) yang ditempat
kan pada bangunan.
Bahaya Ringan : apartemen, perkantoran, gedung
pertemuan, hotel, dsb.
Bahaya Sedang : pabrik pengalengan, pabrik elektronik, pencucian, dsb.
Bahaya Tinggi : kilang minyak / petrokimia, pabrik
asphalt, hangar pesawat, dsb.

3. Fire Water Supply System


Sistim penyediaan air pemadam didasarkan
pada kebutuhan maksimum pada kondisi
yg
terjelek, pada kebakaran :
- tanki timbun atmospheric
- pada proses unit
- tanki bertekanan
- dll
dengan minimum residual pressure 100 psig
Bila sumber air bukan dari sumber air bebas,
harus mampu beroperasi selama 10 jam
(IP
Part 3, Refining Safety Code)

PROCESS UNIT FIRE WATER REQUIREMENT


TYPE OF PROCESS UNIT:
Atmospheris Dist, vacuum or combination unit
with up to 15,900 m3/d (100,000 bpcd) through
put; traeting plants; asphalt stills; athers.

MIN. FIRE WATER DEMAND:


795 m3/h

or

3.500 gpm

Atmospheric Dist, vacuum or combination units


with up to 15,900 m3/d (100,000 bpcd) or higher
throughput; catalytic cracking units.

908

4.000

Light end units containing volatile oils and hydro


gen, such as reformers, catalytic desulfulizers,
fluid catalytics cracker, high pressure units
(over 100 psi).

1.135

5.000

Lube oil plants and blending facilities (excluding


propane extraction units).

454

2.000

Jaringan Pipa Pemadam


Berupa jaringan yang menghubungkan masing-masing sisi dari keempat
sisi dari blok-blok area proses ( loops ).
Ukuran pipa pemadam minimum 8 ; yang lateral minimum 6 NPS dan
maksimum tekanan kerja pada jaringan tidak boleh lebih dari 180 psi.
Pada pompa pemadam dipasang relief valve untuk mengcegah adanya
tekanan lebih ( over pressure ) pada waktu low flow, untuk melindungi
pompa.
Pada setiap persimpangan jaringan dipasang kerangan pembagi dalam
jumlah yang cukup.
Tidak diperbolehkan lebih dari 6 buah peralatan proteksi kebakaran
( mis: hidrant, monitor, dll) atau system yang dilepas / tidak difungsi
kan pada saat yang sama.

Sambungan
Suplai air pemadam dari pompa pemadam tidak boleh disambungkan
secara permanen ke peralatan proses, kecuali hanya untuk penanggulangan kebakaran.
Air pemadam harus dijaga agar tidak terkontaminasi dengan gas dan
cairan yang mudah terbakar.
Sambungan sementara ke jaringan air pemadam dapat diizinkan, dengan syarat sbb:
Tekanan pada proses/fasilitas harus lebih rendah dari tekanan ter
rendah sistem air bakaran.
Harus dipasang check valve.
Fire Departemen harus diberitahu sebelumnya.
Harus dibuat pengaturan ntuk melepas sambungan dengan cepat
bila terjadi emergency.
Jaringan air pemadam harus selalu berisi air bertekanan.

EGS 629 :

FIRE PROTECTION AND LOSS PREVENTION


REFINERIES AND PETROLEUM PLANTS

- Minimum Fire Water Syatem Capacity 681 m3/h ( 3.000 gpm )


- Fixed Water Spray System 57 m3/h ( 250 gpm )
- Fire Water Supply : Tanki harus mampu menampung minimal
6 jam operasi pada kapasitas pompa terpasang.
- Residual Pressure minimal 100 psi.
- Hydrant Spacing : 45 m to 60 m ( 150 ft to 200 ft ).
- Hose reel pada tempat-tempat yang tidak dilengkapi fixed water
spray atau monitor.
- Monitors : 500 1.000 gpm ( 114 227 m3/h )
- Pump Test : - Pump rating NFPA 20
- 140 % of rated pressure with 0 gpm flow
- 100 % of rated pressure with 100 % of rated flow
- 65 % of rated pressure with 150 % of rated flow

4. FIRE FIGHTING AGENTS


PADAT :
Pasir/tanah : Efektif untuk memadamkan
kebakaran klas B (tumpahan/ceceran
minyak).
Tepung Kimia (Dry Chemical/Powder) :
Tepung Kimia Regular: Na Bicarbonat
(merk dagang; PLUS 50 C).

3.

FIRE FIGHTING AGENTS

Lanjutan PADAT

Potassium Bicarbonate (PURPLE K)


Potassium Carbonate (MONNEX)
Potassium Chlorida (SUPER K)
(Digunakan untuk kebakaran klas B dan C )

Tepung Kimia Serba Guna: bahan bakunya monoammonium


phosphate dan potassium (digunakan untuk kebakaran klas A, B
dan C)

Tepung Khusus untuk kebakaran klas D, bahan bakunya


campuran K,Ba,Na,Ca Chlorida. (Foundary Flux Dow
Chemical; TEC John Kerr & Co, England)

CAIR
Air
:
Cocok untuk memadamkan
kebakaran Klas A dan B. Mudah,murah,
daya serap tinggi ( 152 BTU/Lbs).
Busa : Kumpulan gelembung-gelembung
cair
(bubbles)
yang
mengapung
dipermukaan zat cair dan mengalir pada
permukaan bahan padat.
Efektif untuk kebakaran klas A dan B.

Berdasarkan proses terbentuknya, dibedakan :

Busa Kimia ( karena reaksi kimia).


Busa Mekanik ( karena proses mekanis,
adukan dari bahan pembentuk busa,air
bertekanan dan udara.
Berdasarkan
Daya
dibedakan :
Low Expansion Foam
Medium Expansion Foam
kali
High Expansion Foam
kali

Pengembangan,
: < 20 kali
: 20 200
: 200 1.000

Foam Tank Protection


Number of Foam Outlets Required for Fixed Roof Tank
:
Diameters of Tank (Feet) :
Number of Foam Chamber :
Up to 80
81 120
121 140
141 160
161 180
181 200
Over 201

1
2
3
4
5
6
1 additional for
each 5000 ft2
Foam Application Rates 0,10 gpm/ft2 ( 4,1 lpm/m2 )
Hydrocarbon Discharge Times:
Flash Point 100 to 140 oF
: 20 minutes
Flash Point below 100 oF
: 30 minutes
Crude Petroleum
: 30 minutes

MENENTUKAN JENIS DISCHARGE DEVICES


UNTUK CONE ROOF TANKS:
Foam Chamber (pada umumnya)
Slang pemadam tidak boleh digunakan untuk cone roof tank
dengan diameter lebih 30 ft ( 9 m) atau tinggi tanki melebihi
20 ft ( 6 m ).
Monitor tidak dapat digunakan untuk cone roof tanks dengan
diameter lebih 60 ft ( 18 m ).
Kecepatan rambat foam tidakboleh melebihi 10 ft/sec ( untuk
jenis minyak Class B), atau 20 ft/sec. untuk cairan lain.
( untuk menentukan inlet pipa. )

SARANA PEMADAM TAMBAHAN


UNTUK TANKI PENIMBUN
Selain sarana pemadam utama, diperlukan sarana tambahan
Untuk proteksi kebakaran kecil (fixed system atau portable) ,
Dengan minimum flow rate 50 gpm ( 189 lpm ).
Jumlah minimum slang dan discharge time :
Diamater Tanki
( Feet ) ( Meter)
s/d 35
35 65
65 95
95 120
> 120

s/d 11
11 20
20 29
29 37
> 37

Jumlah minimum slang


yang diperlukan ( pce )
1
1
2
2
3

Minimum Discharge
Time ( minutes )
10
20
20
30
30

DISCHARGE TIME & APPLICATION RATE FOR CONE ROOF TANK

Fuel Protected

Foam
Concentrate

Hydrocarbon
Flash Point
Protein
Between 100oF
Fluoroprotein
o
o
- 200 F(38-93 C) AFFF
Hydrocarbon
FP below 100oF
(38oC) or liquid
Heated above
Flash Point (FP)
Crude Oil
Alcohol :
Methanol/
Ethanol

Protein
Fluoroprotein
AFFF

Foam Chamber
Application Rate Disch.Time
gpm/ft 2 lpm/m2
Minutes

Monitor/Hand Hose Line


Application Rate Disch.Time
gpm/ft2 lpm/m2
Minutes

0.10
0.10
0.10

4.10
4.10
4.10

30
30
30

0.16
0.16
0.16

6.50
6.50
6.50

50
50
50

0.10
0.10
0.10

4.10
4.10
4.10

55
55
55

0.16
0.16
0.16

6.50
6.50
6.50

65
65
65

Protein
Fluoroprotein
AFFF

0.10
0.10
0.10

4.10
4.10
4.10

55
55
55

0.16
0.16
0.16

6.50
6.50
6.50

65
65
65

ARC
3X3
3X6

0.17
0.15
0.10

6.90
6.10
4.10

55
55
55

0.17
0.16
0.16

6.90
6.50
6.50

65
65
65

Floating Roof Tank :


Number of Foam Outlet : 1 for each 40 ft of
circumference with a 12 in. high foam dam; and 1
for each 80 ft of circum
ference with a 24 in. high foam dam.
Foam Application Rates : 0,30 gpm/ft2 (12,2 lpm/m2)
of annular ring area, above seal.
Foam hand lines and Monitors for Tank Protection:
Foam Application Rates 0,16 gpm/ft2 ( 6,5 lpm/m2).
Discharge Times : FP < 100 oF
65 minutes
FP 100 140 oF
50 minutes
Crude oil
65 minutes

Jenis Foam Concentrate:


Regular Protein Foam : Dibuat dari protein
hewani/tumbuhan, stabilizer solvent dan germicide ( 3
6% ).
Fluoroprotein Foam : Penambahan fluoroprotein
surfactant
pada
protein
foam
meningkatkan
keseimbanagn dengan dry chemical dan tidak mudah
terbakar. ( 3 6%).
Alcohol Foam : Foam khusus untuk polar solvent.
komposisi kimia polar solvent, mengandung oxigen,
nitrogen atau sulfur.
Aqueous Film Forming Foam (AFFF) : Foam yang
membentuk lapisan film tipis, mempunyai daya
pengembangan rendah, sangat cocok untuk kebakaran

GAS :
Gas Asam Arang (CO2):
Disimpan dalam fase cair dalam tabung
bertekanan 1.000 1.200 psi.
Memadamkan dengan cara penyelimutan ,
dilution dan sedikit pendinginan ( 1 lb CO 2 cair
berubah menjadi +/- 8 Ft3 ); 1,5 kali berat udara.
Keunggulannya: bersih, murah, mudah didapat,
tidak beracun, self expelling.
Kerugiannya: tempat/wadah berat, tidak cocok
untuk ruang terbuka, pada konsentrasi tinggi
mengganggu pernafasan (oxygen deficiency)

CAIRAN MUDAH MENGUAP :


HALON (Halogenated Hydrocarbon) : Untuk
memadam kan kebakaran klas A, B dan C
dengan
cara
memutus
rantai
reaksi
pembakaran.
Keunggulan : bersih, mudah didapat, murah,
lebih cepat pemadamannya dibanding media
lain pada ukuran yang sama.
Kelemahan : tidak efektif ditempat terbuka,
beracun, merusak lingkungan (kini dilarang,
dan diganti clean agent lain seperti FM 200,
NAF III, Energen, dsb).

PENGGANTIAN HALON DI PERTAMINA


SK Dirut No.Kpts-220/C0000/98-S0 ; tgl. 11 Desember 1998
(Pedoman No.A-001/C0320/98-S0 ; tgl. 11 Desember 1998
Tentang Penggantian Bahan Pemadam Api Halon).
Ref: NFPA 2001: tentang Standard on Clean Agent Fire
Extinguishing System.
- Pemanfaatan penggunaan sisa Halon sampai tahun 2007.
- Dibentuk Halon Bank Pertamina di seluruh operasi Pertamina
untuk menangani permintaan penggantian Halon kebutuhan
dikalangan intern Pertamina.
- Dibentuk Halon Bank Nasional ( Kementerian LH kerja
sama
dengan PT Garuda Indonesia ) untuk keperluan diluar Pertamina.
- Media Pengganti Halon : Inergen-541; FE; FM-100; FM-200 ;
NAF S III; NAF P III; AF 11E, dsb.

5. FIXED Fire Fighting System


Adalah sistim pemadam kebakaran yang
instalasinya
dipasang tetap, sehingga
mengurangi pemakaian personil maupun
peralatan pemadam kebakaran.
Unsur-unsur utama dari sistim pemadam
tetap :
- sistim deteksi kebakaran
- sistim alarm kebakaran
sistim
pemadam
kebakaran
(otomatis/manual)
Media pemadam yang digunakan : air, busa,

Jenis Sistim Sprinkler


Sistim pipa basah (wet pipe system) : berisi air
bertekan an diseluruh sistim dan dihubungkan dengan
sumber air. Pada katup pengontrol utama dilengkapi katup
check alarm electrical berdasarkan aliran air. Bila satu atau
lebih katup pemancar air terbuka
oleh panasnya
kebakaran, tekanan air dalam pipa berkurang, maka
tekanan air dari bawah pipa utama (main riser) menekan
clapper pada posisi terbuka, dan air mengalir ke sprinkler
yang terbuka.

Sistim pipa kering (dry pipe system) : disebut


sistim pipa kering, karena didalam sistim perpipaan diatas
katup pipa kering diganti oleh udara bertekanan. Katup
pipa kering berfungsi untuk menahan air keluar dari sistim
perpipaan sampai kebakaran dapat membuka sprinkler.

F/W Sprinkler Water Discharge Rates


Pressure at Sprinkler
Inlet ( psi)
20
30
40
50
75
100

Range of Discharge
Rates ( gpm )
12 - 14
14 - 17
16 - 19
18 - 22
22 - 26
25 - 30

Standard Sprinkler Discharge Rates


Pressure at Sprinkler
Inlet ( psi )
7
10
20
30

Range of Discharge
Rates ( gpm )
14 16
16 19
23 26
28 32

TEMPERATURE RATINGS, CLASSIFICATION


AND COLOR CODINGS

Max.Ceiling : Temperature: Temp.Classification: Color Code: GlassBulb Colors:


Temp (oC) Rating ( oC
38

57 to 77

Ordinary

66
107
149
191
246
329

79 to 107
121 to 149
163 to 191
204 to 246
260 to 302
343

Intermediate
High
Extra High
Very Extra High
Ultra High
Ultra

Uncolored
or Black
White
Blue
Red
Green
Orange
Orange

Orange or Red
Yellow or Green
Blue
Purple
Black
Black
Black

PROTECTION AREA AND MAXIMUM SPACING


Construction
Type

Light Hazard

Ordinary Hazard Extra Hazard

Prot.ection Spacing Protection Spacing


Area (ft2 ) ( ft )
Area ( ft2)
( ft )

High Piled Storage

Protection Spacing Protection


Area ( ft2 ) ( ft )
Area ( ft2 )

Spacing
( ft )

Noncombustible obstructed
And unobstructed.
Combustible unobstructed

225

15

130

15

100

12

100

12

Combustibleobstructed

168

15

130

15

100

12

100

12

Stock of Spare Sprinkler:


System dengan :
< 300 sprinkler
300 1000 sprinkler
> 1000 sprinkler

Stock : 6 sprinkler
Stock : 12 sprinkler
Stock : 24 sprinkler

Sistim Pemadam Busa


Fixed
System
:
Adakah
sistim
yang
mempunyai instalasi lengkap dari pusat station
busa, sistim perpipaan dan penyaluran, sampai
outlet pada bahaya yang dilindungi dilengkapi
pompa yang terpasang tetap.
Semifixed System : Sistim dipasang tetap,
mempunyai discharge outlet. Dihubungkan
dengan sistim perpipaan sampai jarak aman.

COMPONENTS OF COMPLETE FOAM SYSTEM

Sistim Dry Chemical / Carbon Dioxide / Halon


Ada 2 metoda dasar penggunaan dry chemical, halon
carbon dioxide, dsb. sebagai media pemadam api.
Media disemburkan kedalam ruangan tertutup untuk
menimbulkan suatu kondisi pemadaman ke seluruh
volume ruangan ( TOTAL FLOODING ).
Media disemburkan langsung ke obyek yang terbakar
untuk memadamkan, tanpa berdasarkan pada ruang
an ( LOCAL APPLICATION).

6. MOBILE FIRE FIGHTING SYSTEM


Fire Trucks :
Water Tender, Foam Tender, Powder Tender
Water/Foam Tender ( Dual Agent )
Water/Foam/Powder Tender ( Tripple Agent )
Pada Fire Trucks, biasanya
penggerak
pompanya menggunakan mesin kendaraan
yang di
lengkapi PTO (Power Take Off).
Pemasangan pompa pemadam ada disamping
(side mounted) atau dibelakang (rear
mounted)
kendaraan.

EGS 629 : FIRE PROTECTION AND LOSS PREVENTION


REFINERIES AND PETROLEUM PLANTS
Plant Fire Trucks :
Plant Throughput (bbl/d):

Minimum Protections:

Up to 50.000

: 1 - Foam Truck

50.000 250.000

: 2 - Foam Truck one with articulated


boom and turret nozzle.
1 Auxiliary vehicle with 450 Kg dry
chemical and AFFF.
1 Rescue van with entry suit, safety
equipment.

Over

: 3 Foam Trucks
1 Auxiliary vehicle
1 Rescue van

250.000

Fire Pump
Trailer/Skid Mounted/Portable Fire Pumps Berdasarkan
konstruksi dan prinsip kerja, pompa dibedakan atas :
Pompa torak (Reciprocating) : single/double acting
Pompa baling-baling (Centrifugal): single/multi stage
Kapasitas tertulis 250 GPM 250 gpm pada 150 psi

Klasifikasi fire pumps (USA) :


Klas A : Pada 200 psi mengalirkan air 70%
kapasitas
dan pada 250 psi
mengalirkan 50% kapasitas
Klas B

: Pada 200 psi mengalirkan air 50%


kapasitas
dan pada 250 psi mengalirkan 1/3

Fire Extinguishers
Alat pemadam api berat (skid mounted / trailer,
dsb)
Alat pemadam api ringan (APAR) : Berat
maksimum 55 lbs dan dapat dioperasikan 1
orang.
Media pemadam : air, busa, tepung kimia,
halon, gas.
Cara kerja :
jenis pompa tangan
stored pressure
gas cartridge
self generating
Fire Rating :
1 A setara 1,25 gallon air
1 B untuk 1 square feet

NFPA : Penentuan jumlah alat pemadam api atas


dasar tingkat bahaya.

Tingkat Bahaya Rendah : bahan bakar klas A,


jumlah
sedikit ( kantor, ruang pertemuan,
ruang kelas, dsb).
Tingkat Bahaya Sedang : bahan bakar klas A
dan B, jumlah agak besar (toko kelontong,
gudang, bengkel)
Tingkat Bahaya Tinggi : bahan bakar klas A dan
B
dalam
jumlah
besar
(kilang
minyak/petrokimia, bengkel bengkel besar,
proses pencelupan, pelapisan,dsb).

Penyebaran APAR menurut Kep. Menaker & Trans.


RI No. PER-04/MEN/1980 tanggal 14 April 1980
tentang
syarat-syarat
pemasangan
dan
pemeliharaan APAR, tidak boleh melebihi 15 meter.

Ukuran minimum APAR untuk Klas A :


TYPE BAHAYA
RENDAH
SEDANG
TINGGI

KEMAMPUAN
APAR

JARAK MIN
(FEET)

2A
2A
4A

75
75
75

Ukuran minimum APAR klas B :


TYPE BAHAYA
RENDAH
SEDANG
TINGGI

KEMAMPUAN APAR
5B
10 B
10 B
20 B
30 B
40 B

JARAK MIN (FEET)


30
50
30
50
30
50