AS222ER01 - G08 Distribution Transformer Cable Trench: Typically - 500mmx500mm Trench Is Shown in The Drawing

The document discusses drawings for typical 500mm x 500mm cable trenches for distribution transformers. It provides recommendations for improvements, including inserting steel plates for transformer entry and retrieval, adding an equipotential bonding point, and considering cable trays. Welding a 200mm x 12mm steel plate to the insert plate is recommended to aid in rolling transformers into position. Gravel should fill the space between the foundation and transformer.

Uploaded by

sivaram_kv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views7 pages

AS222ER01 - G08 Distribution Transformer Cable Trench: Typically - 500mmx500mm Trench Is Shown in The Drawing

The document discusses drawings for typical 500mm x 500mm cable trenches for distribution transformers. It provides recommendations for improvements, including inserting steel plates for transformer entry and retrieval, adding an equipotential bonding point, and considering cable trays. Welding a 200mm x 12mm steel plate to the insert plate is recommended to aid in rolling transformers into position. Gravel should fill the space between the foundation and transformer.

Uploaded by

sivaram_kv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 7

AS222ER01 G08 distribution transformer cable trench

Typically 500mmx500mm
trench is shown in the drawing.

AS223ER01 G08 distribution transformer cable trench

Typically 500mmx500mm
trench is shown in the drawing.

Typical distribution transformer drawings of ER223 and ER222


Observations :

A typical 500 mm x 500 mm trench is shown in the drawing.

Pro-erection Recommendations :

Insert plates/ suitable fixing arrangement for fixing a M12x 200 mm continuous steel plate to be foreseen
for transformer entry and retrieval.

A equi-potential bonding point to be foreseen in each of the transformer room Presently missing in the
Earthing implantation diagram .

If possible suitable cable trays ( 300 mm wide for the primary , 400 mm 1No + 1 duct tray for the PGT for
control.

The secondery cables in the existing line -1 are single core . If we are going in line 2 also single core there
are approx 24 No of 240 sqmm. Accommodating them for the proper job to be foreseen.

Typical distribution transformer insert plates

With out Steel plate over the insert plate


could be very difficult to roll the
transformer (Push / Pull)

Typical distribution transformer having 200 xM12 Plate welded on the insert
plate

Putting a complete 12mm thick


x 200 mm wide plate for
pushing the transformer to its
position by wheels

Typical distribution transformer placed on the foundation by rolling

This position need to be filled


with gravel of 50 to 70 mm up
to the foundation level

This position to be matched


with the foundation height
including the cable tunnel

Typical distribution transformer in fully erected position