CHW Pipe Support Sample
CHW Pipe Support Sample
SyedMuzaffer
201502022TECOMNSMCHWPIPESUPPORTSYSTEMR0
FischerFZE
P.O.Box261738,
JebelAlifreeZone,
Dubai,UAE
Tel.:+96824503915
Fax:+96824503920
Mob:+96892881260
TITLE
CLIENT
CONT
PROJECT
BY
SMA
DATE
02/02/2015
Safety factor
Grade of Steel for Channel
Grade of Threaded rod
Deflection Allowed
DESIGN DATA
PIPE DETAILS
Span
1
2
3
4
5
6
7
8
1.4
275.00
4.6
L/200
N/mm
PROPOSED MATERIAL
Spacing
S.No
CHW
OD with
Pipe Od of Pipe
Insulation
dia (
(mm)
(mm)
mm)
25
33.4
183.4
32
42.2
192.2
40
48.3
198.3
50
60.3
210.3
65
73
223.0
80
88.9
238.9
100
114.3
264.3
150
168.3
318.3
REV
Channel
(MM)
(M)
kG/M
kN
620
640
650
680
700
730
780
890
2.40
2.40
2.40
2.40
3.00
3.00
3.00
3.00
3.49
4.87
6.12
8.61
13.67
18.57
27.13
51.57
0.08
0.12
0.15
0.21
0.41
0.56
0.81
1.55
Page2of19
FUS 21/2
FUS 21/2
FUS 21/2
FUS 21/2
FUS 21/2
FUS 21/2
FUS 41/2
FUS 41/2
7.8%
11.2%
14.4%
21.1%
43.6%
62.1%
33.6%
73.4%
G 8
G 8
G 8
G 8
G 8
G 8
G 10
G 10
2.9%
4.0%
5.0%
7.1%
14.1%
19.2%
15.7%
29.9%
Anchors
Utilization
EA II M 08
EA II M 08
EA II M 08
EA II M 08
EA II M 08
EA II M 08
EA II M 10
EA II M 10
2.1%
3.0%
3.7%
5.3%
10.4%
14.2%
13.4%
25.5%
TITLE
CLIENT
CONT
PROJECT
BY
SMA
DATE
02/02/2015
Safety factor
Grade of Steel for Channel
Grade of Threaded rod
Deflection Allowed
DESIGN DATA
PIPE DETAILS
Span
Spacing
N/mm
(MM)
1.4
275.00
4.6
L/200
PROPOSED MATERIAL
S.No
CHW
OD with
Pipe Od of Pipe
Insulation
dia (
(mm)
(mm)
mm)
REV
(M)
kG/M
kN
Page3of19
Anchors
Utilization
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
1
25.00
33.40
183.40
2400.00
620.00
3.49
0.08
3.10
1.40
0.12
0.14
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page4of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.02
890.00
275.00
0.21
kN.m
mm
N/mm2
kN.m
UtilizationOffischerCChannel=Mu/Ma
FUS21/2
0.08
Ok,Safe
0.12
kN
=
=
11.01
0.01
kN.m
Ok,Safe
0.12
0.14
kN/M
M
MaximumShearForceonchannel=Vu
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS21/2
FUS21/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS21/2
83.775
N
0.14 M
0.62 m
2.05E+11 N/M2
9.7E09 M4
0.27 mm
3.10 mm
0.09 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
8.61
DEFLECTION=
=
=
0.12
4.07
0.03
kN
kN
Ok,Safe
kN
=
=
0.12
1.10
5.50
0.02
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page5of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
2
32.00
42.20
192.20
2400.00
640.00
4.87
0.12
3.20
1.40
0.16
0.15
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page6of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
0.16
0.15
kN/M
M
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.02
890.00
275.00
=
=
=
0.21
0.11
0.16
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
11.01
0.01
kN.m
Ok,Safe
CheckforDeflection
ServiceLoad
=
116.92416
N
LoadDistancea=
0.15 M
Spanl=
=
0.64 m
ModulusofElasticity(ConstantforSteel)=
2.05E+11 N/M2
MomentofInertiaI(fischerCatalogue)=
9.7E09 M4
Deflection
=
0.41 mm
AllowedDeflection
=
3.20 mm
UtilizationOffischerCChannel
FUS21/2
0.13 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
12.79
DEFLECTION=
=
=
0.16
4.07
0.04
kN
kN
Ok,Safe
kN
=
=
0.16
1.10
5.50
0.03
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page7of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
3
40.00
48.30
198.30
2400.00
650.00
6.12
0.15
3.25
1.40
0.21
0.15
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page8of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
0.21
0.15
kN/M
M
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.03
890.00
275.00
=
=
=
0.21
0.14
0.21
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
11.01
0.02
kN.m
Ok,Safe
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS21/2
FUS21/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS21/2
146.784
N
0.15 M
0.65 m
2.05E+11 N/M2
9.7E09 M4
0.54 mm
3.25 mm
0.17 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
16.63
DEFLECTION=
=
=
0.21
4.07
0.05
kN
kN
Ok,Safe
kN
=
=
0.21
1.10
5.50
0.04
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page9of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
4
50.00
60.30
210.30
2400.00
680.00
8.61
0.21
3.40
1.40
0.29
0.16
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page10of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
0.29
0.16
kN/M
M
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.04
890.00
275.00
=
=
=
0.21
0.21
0.29
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
11.01
0.03
kN.m
Ok,Safe
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS21/2
FUS21/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS21/2
206.652
N
0.16 M
0.68 m
2.05E+11 N/M2
9.7E09 M4
0.87 mm
3.40 mm
0.26 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
25.51
DEFLECTION=
=
=
0.29
4.07
0.07
kN
kN
Ok,Safe
kN
=
=
0.29
1.10
5.50
0.05
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page11of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
5
65.00
73.00
223.00
3000.00
700.00
13.67
0.41
3.50
1.40
0.57
0.16
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page12of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
0.57
0.16
kN/M
M
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.09
890.00
275.00
=
=
=
0.21
0.44
0.57
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
11.01
0.05
kN.m
Ok,Safe
CheckforDeflection
ServiceLoad
=
410.17875
N
LoadDistancea=
0.16 M
Spanl=
=
0.7 m
ModulusofElasticity(ConstantforSteel)=
2.05E+11 N/M2
MomentofInertiaI(fischerCatalogue)=
9.7E09 M4
Deflection
=
1.90 mm
AllowedDeflection
=
3.50 mm
UtilizationOffischerCChannel
FUS21/2
0.54 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
54.16
DEFLECTION=
=
=
0.57
4.07
0.14
kN
kN
Ok,Safe
kN
=
=
0.57
1.10
5.50
0.10
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page13of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
6
80.00
88.90
238.90
3000.00
730.00
18.57
0.56
3.65
1.40
0.78
0.17
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS21/2
G8
EAIIM08
C25/30
Page14of19
SMA
02/02/2015
0
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
0.78
0.17
kN/M
M
FUS21/2
FUS21/2
FUS21/2
FUS21/2
FUS21/2
=
=
=
0.13
890.00
275.00
=
=
=
0.21
0.62
0.78
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
11.01
0.07
kN.m
Ok,Safe
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS21/2
FUS21/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS21/2
557.16
N
0.17 M
0.73 m
2.05E+11 N/M2
9.7E09 M4
2.94 mm
3.65 mm
0.80 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G8
G8
EAIIM08
EAIIM08
80.42
DEFLECTION=
=
=
0.78
4.07
0.19
kN
kN
Ok,Safe
kN
=
=
0.78
1.10
5.50
0.14
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page15of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
7
100.00
114.30
264.30
3000.00
780.00
27.13
0.81
3.90
1.40
1.14
0.18
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS41/2
G10
EAIIM10
C25/30
Page16of19
SMA
02/02/2015
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
1.14
0.18
kN/M
M
FUS41/2
FUS41/2
FUS41/2
FUS41/2
FUS41/2
=
=
=
0.21
2580.00
275.00
=
=
=
0.62
0.34
1.14
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
16.13
0.07
kN.m
Ok,Safe
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS41/2
FUS41/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS41/2
814.02
N
0.18 M
0.78 m
2.05E+11 N/M2
5.33E08 M4
0.96 mm
3.90 mm
0.25 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G10
G10
EAIIM10
EAIIM10
33.65
DEFLECTION=
=
=
1.14
7.24
0.16
kN
kN
Ok,Safe
kN
=
=
1.14
1.10
8.50
0.13
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page17of19
Mu=P.a
InputData:
PipeSize
CHWPipedia
OdofPipe
ODwithInsulation
SpacingofSupports
SpanofChannel
WeightofPipeandInsulation
PointLoadonChannel
Alloweddeflection(L/200)
FactorofSafetyforDesign
DesignPointLoadP=
Distancea=
8
150.00
168.30
318.30
3000.00
890.00
51.57
1.55
4.45
1.40
2.17
0.21
0
0
0
BY
DATE
REV
mm
mm
mm
mm
mm
kg/m
kN
mm
kN
M
LOADDIAGRAM
ProposedSections:
ProposedCChannel:
ProposedThreadedrod:
Anchor
GradeofConcrete
FUS41/2
G10
EAIIM10
C25/30
Page18of19
SMA
02/02/2015
0
0
0
BY
DATE
REV
SMA
02/02/2015
0
SectionsCheck:
DesignPointLoad=
LoadDistancea=
TheChannelisaSimplySupportedBeam.
MaximumBendingMomentontheCchannel
SectionModulus(fischerSamontecCatalogue)
GradeofSteel
AllowablebendingmomentMafor
UtilizationOffischerCChannel=Mu/Ma
MaximumShearForceonchannel=Vu
2.17
0.21
kN/M
M
FUS41/2
FUS41/2
FUS41/2
FUS41/2
FUS41/2
=
=
=
0.45
2580.00
275.00
=
=
=
0.62
0.73
2.17
kN.m
mm
N/mm2
kN.m
Ok,Safe
kN
=
=
16.13
0.13
kN.m
Ok,Safe
AllowableShearForce=Va
UtilizationOffischerCChannel=Vu/Va
FUS41/2
FUS41/2
CheckforDeflection
ServiceLoad
=
LoadDistancea=
Spanl=
=
ModulusofElasticity(ConstantforSteel)=
MomentofInertiaI(fischerCatalogue)=
Deflection
=
AllowedDeflection
=
UtilizationOffischerCChannel
FUS41/2
1547.235
N
0.21 M
0.89 m
2.05E+11 N/M2
5.33E08 M4
2.72 mm
4.45 mm
0.61 Ok,Safe
CheckforThreadedRod
MaximumTensionforceinthethreadedrod=
AllowableTensionForce(AllowableloadTable)
UtilizationOffischerThreadedrod
CheckforAnchor
MaximumTensionforceintheAnchor
Concretestrengthfactor"fb,N"
AllowableTensionForce(AsperEAIITable)
UtilizationOffischerAnchor
Proof:
TotalUtilization=
Ok,TheSupportisSafe
G10
G10
EAIIM10
EAIIM10
73.43
DEFLECTION=
=
=
2.17
7.24
0.30
kN
kN
Ok,Safe
kN
=
=
2.17
1.10
8.50
0.25
kN
Ok,Safe
Theuserhastheresponsibilitytocheckwhetherthepresentconditionsonsiteandtheanchors,settingtoolsetc.intendedtousecomplywiththeconditionsgiven.Theultimate
responsibilityforselectingtheproductfortheindividualapplicationiswiththecustomer
Page19of19
Mu=P.a