HVAC Handbook CARRIER New Edition Part 12 Water and DX System PDF
HVAC Handbook CARRIER New Edition Part 12 Water and DX System PDF
HVAC Handbook CARRIER New Edition Part 12 Water and DX System PDF
SUMMARY OF PART 12
This part of the System Design Manual presents data
and engineering procedures to guide the engineer in the practical
designing of water and DX systems.
The text of this Manual is offered as a general guide for
the use of industry and of consulting engineers in designing systems.
Judgment is required for application to specific installation, and
Carrier is not responsible for any uses made of this text.
dx systems
INDEX
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
TYPE OF SYSTEMS
SYSTEM DESCRIPTION
This system (Fig.1) consists of central water heating
and cooling equipment, fan-coil units, controls,
interconnecting piping and wiring as required.
The fan-coil units system is designed to provide
individual space temperature control without utilizing
central station air handling equipment or ductwork. Figure
2 illustrates the basic elements of the unit which include
the air inlet, filter, fan and cooling and heating coil. The
unit may be under-the-window or ceiling mounted.
Either a mixture of outdoor and return air or return air
alone is supplied to the unit. Filters clean the air. The coil
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
sufficient heat to temper the outdoor air from the
temperature at which it enters the unit to the room design
temperature (depending on the type of system).
Unit Selection
Select the room units to satisfy the following
requirements:
1. Maximum room and ventilation air cooling load,
both sensible and total.
2. Maximum room and ventilation air heating load.
3. External resistance imposed upon the unit by
additional required ductwork. The external
resistance should be considered relative to its
effect on the air volume and the cooling and
heating capacity of the unit.
The unit is normally adequate for zone depths of
approximately 20 feet. Vertical air distribution of the
perimeter unit spreads out in blanketing the exterior wall
and travels along the ceiling for a distance of 15 to 20
feet before falling toward the floor in return air circulation.
Select the fan-coil units so that the smallest units are
used coincident with the highest water temperature.
Water temperatures are usually selected between 45 F
and 50 F. A few trial unit selections give an indication if
the water temperature is acceptable.
The same water flow rate is used for heating as is
used for cooling. System heating capacity is obtained by
an adjustment of entering water temperature.
Convector heating during overnight, weekend or
holiday periods is impractical; only one room heating load
calculation with the unit fan operating is required.
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
Piping Design
Design the piping system in the normal manner. A
single piping system is used to circulate chilled or hot
water to the unit coil. Good design practice should be
followed in system layout (Part 3). A reverse return
system (Fig. 3) is recommended and should be used
whenever it is adaptable to the building layout; this
provides an inherently balanced system. Otherwise a
direct return system may be used.
In buildings with units on more than one exposure a
diversity factor should be applied as outlined in Part 3. In
addition to resulting in smaller piping, headers and
circulating pumps, diversity aids in minimizing sound
problems when the system is operating at low water
quantities. Diversity is not applied to the risers.
If more than one zone of water piping is desired,
secondary circuits can be arranged accordingly.
However, a three- or four-pipe system should be
considered before designing a zoned single piping
system.
The design water flow rate selected for the units can
influence the total system cost. The lower the flow rate,
the lower the first cost of the system piping and pump.
However a check should be made to assure turbulent
flow in the unit coil. The minimum flow per coil circuit to
maintain turbulent flow conditions for a 3/8, 1/2, or 5/8
inch OD tube is approximately 0.5, 0.7 or 0.9 gpm
respectively.
The secondary water pump is operated continuously
and should be selected for an extremely flat head
characteristic (Curve A, Fig. 4). Do not select a pump that
has a steep head characteristic (Curve B, Fig. 4).
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
amount of condensate is, therefore, a consideration when
sizing drain piping.
Vaporproof insulation is required for water piping and
runouts.
Refrigeration Load
The refrigeration load is established by the peak
building load (or block estimate) of the areas served by
the system. Such an estimate includes all the applicable
items to be found on an Air Conditioning Load Estimate
from shown in Part 1. Provide 5% allowance for
overcooling in the block load estimate.
CONTROLS
A typical control arrangement for the fan-coil unit and
secondary water coil circuit is shown in Fig. 7and 8
respectively. Figure 7 is a schematic of a control package
consisting of a solenoid valve operated from a room
thermostat in conjunction with a manual multi-speed fan
switch.
Unit Control
Sensible and latent cooling capacity when the
performed by a single element cannot be adjusted to the
wide range of coil sensible heat ratios which occur in
comfort cooling. Maintenance within acceptable limits of
Find:
Water velocity in runout
Solution:
Enter Fig. 5 at water flow gpm = 1.
Read head from Curve A = 45 ft water.
Enter Fig. 6 at 45 ft water.
Read water flow from Curve C = 8.4 gpm
thru the unit.
Enter Fig. 6 at water flow = 8.4 gpm.
Read velocity from Curve D = 9.0 ft/sec in
runout.
If the water velocity is above 10 fps, two courses of
action are open:
1. Add head pressure control at the pump, or
2. Redesign the piping for a lower pressure drop so
that the pump with a lower head at shutoff can be
selected.
Optimum design of drain piping considers the type of
ventilation air supply provided. When the fan-coil unit
system handles the entire dehumidification of outdoor
and recirculated air, there is a substantial amount of
condensate from the units. However if the system draws
ventilation air from an interior zone (conditioned by a
separate system), very little condensate collects. The
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
room relative humidity is specified in order to provide
desired dry-bulb temperature. Room conditions may be
controlled by fan speed adjustment for cooling or by onoff fan control for heating. It may also be controlled by a
combination of fan speed adjustment and on-off water
flow to the heat transfer coil within the unit (or water flow
modulation).
Basic control at the unit is accomplished by a multispeed fan switch. Control of the water flow thru the unit
coil may be manual, electric or pneumatic.
Continuous design flow of chilled water thru the
cooling coil provides better maintenance of room
humidity levels. However even with multi-speed fan
control for loads below that equivalent to the minimum fan
speed, the room temperature cannot be maintained and
the fan must be shut down. Typical room temperature and
humidity conditions for a fan-coil unit with manual, threespeed fan control are illustrated in Fig. 9.
When unit fans are shut down, the chilled water to the
coils should be shut off, preferably automatically, to
prevent damage from condensation. If the chilled water is
permitted to flow, the entire unit may approach the
temperature of the chilled water, including the
condensate pan and drain line. This can lead to
condensation problems, such as water spotting and
mildew.
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
The thermostat is reset by a master outdoor air thermostat
to maintain a scheduled hot water temperature relative to
the outdoors.
Automatic summer-winner change-over control (Fig. 7)
senses the hot water temperature at the unit and reverses
the action of the room or unit thermostat for winter
operation. The thermostat opens or closes the solenoid
valve in the water line to the unit coil. The manual multispeed fan switch is adjusted by the occupant as desired.
MULTI-PIPING SYSTEM
SYSTEM DESCRIPTION
Figure 12 is a sketch of a 3-pipe system and Figure 13
shows a 4-pipe system.
The ability of a single piping system to satisfy the
constantly changing heating and cooling requirements of
individual perimeter spaces increases with the number of
zones provided. A multi-piping system provides hot and
chilled water at each fan-coil unit the year round. In effect
each unit then is a separate zone and functions
independently. Its control valve selects either hot or
chilled water for the unit coil depending on whether the
module it serves requires heating or cooling. Simple,
nonreversing thermostats may be utilized and changeover controls are not required. Design water quantities for
the heating load may be minimized.
Certain aspects of the three-pipe system should be
investigated before deciding on a system design since
three-pipe systems are covered by one or more patents.
Although the system permits substantial first cost savings
by using a common return, the operating costs are
somewhat higher than those of a four-pipe system
because of the mixing in the common return of water from
the units operating on heating with water from the units
operating on cooling.
The four-pipe system provides isolation of the hot and
cold water circuits to minimize hydraulic problems. A
single or split coil may be used at the unit. A split coil
simplifies unit piping
Two methods of operation are commonly used for
multi-piping systems. The first method gives complete
year-round temperature control in the room. Hot and cold
water are necessaryat the room until at all times of the
year. If the room temperature is too cold, hot water flows
thru the fan-coil unit. If the room temperature is too warm,
cold water flows thru the fan-coil unit. The second method
of operation has hot and cold water available at the room
unit only during the intermediate seasons. It is used when
economy of operation is paramount and adequate room
temperature control is desired. The sequence of
equipment operation is shown in Chart 1. The
temperatures at which the cooling and heating equipment
is started and stopped vary from building to building.
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
Part 12. Water and DX System | Chapter 1. Fan- Coil Unit System
thermostat setting, the fan returns to the low speed
setting; when the thermostat is satisfied, the fan and cold
water solenoid are shut off. On a drop in temperature the
fan is started on low speed and the hot water solenoid
valve is opened. On a further drop in room temperature
the fan is automatically changed to high speed.
This control arrangement offers the advantage of
longer operation at minimum sound level with close
temperature regulation. For a few hours of peak load the
fan is automatically changed to high rpm to give
maximum heating or cooling capacity.
CHAPTER 2. DX SYSTEMS
SYSTEM DESCRIPTION
SYSTEM FEATURES
ENGINEERING PROCEDURE
Fig. 21 Dry Expansion Reciprocating Liquid Chilling Package with Evaporative Condenser
Fig. 22 Flooded Liquid Chiller and Reciprocating Compressors with Evaporative Condenser
EQUIPMENT SELECTION
When selecting equipment, primary considerations
involve the evaporator, condensing media and
component balancing.
Evaporator selection is logically the first step in the
selection of equipment for a basic refrigeration system,
whether direct expansion or chilled water. In order to
satisfy the established conditions of air quantity and
entering and leaving wet- and dry-bulb temperatures, a
specific coils surface is required. Direct expansion air
cooling coils may therefore be selected without having to
consider the refrigeration machine or condenser. The
selection of the refrigeration machine requires the
determination of the refrigerant temperature from the
cooling coil selection. This invariably proves more
economical than the completely arbitrary choice of an
initial refrigerant temperature.
Chilled water quantity and temperature are predetermined for air conditioning or process work. The
Fig. 23 Reciprocating Liquid Chilling Package with Air-Cooled Condensers, Three Compressors
together as a system, performance requirements are
satisfied.
Balancing of the components of a basic refrigeration
system is covered in Part 7. In general more than one
combination of components meets the performance
required of the system. Examination of several such
combinations should be made to determine the optimum
design.
The selection and balancing of system components
influences the initial operating cost of the system. If
optimum first cost is desired, compressor design, suction
and head pressures are secondary; if optimum operating
cost is desired, pressures are of primary importance.
Fig. 24 Reciprocating Liquid Chilling Package with Air-Cooled Condensers, Four ,Compressors
3. Reduces horsepower per ton of refrigeration.
When the balanced capacity of a combination of
compressor and evaporative condenser is slightly
undersize, it is normally more economical to add a
subcooling coil than to select the next larger combination.
The capacity of the condenser and compressor is
increased by the same amount because with subcooled
liquid each pound of refrigerant evaporated does more
work. While increasing the capacity of the system,
subcooling does not require any additional horsepower.
Therefore the horsepower per ton of refrigeration is
reduced.
Fig. 25 Typical Wiring Diagram for Evaporative Condenser Installation, 208-220 Volts, with
Single Pumpout Compressor Control and Crankcase Heater
multiple or single compressors, condensers and
evaporators are selected for a system.
Remote condenser type reciprocating liquid chiller
packages require field-fabricated refrigerant piping
between the compressors and condensers. Piping design
and condenser selection should be made as
recommended in Part 3.
Figures 23 and 24 illustrate a layout for a
reciprocating water chiller package utilizing air-cooled
Fig. 26 Typical Wiring Diagram for Evaporative Condenser Installation, 208-220 Volts, with
Pumpdown Compressor Control
CONTROLS
A basic electric control arrangement is shown in Fig.
25 and 26. An electric control is particularly suited to this
type of application because of the number of
interconnections required between the controls and motor
starters.
Single pumpout compressor control with crankcase
heater is shown. It minimizes the accumulation of liquid
refrigerant in the compressor crankcase during system
A
Applications
DX systems
fan-coil unit system
C
Controls
DX systems
fan-coil unit system
four-pipe
three-pipe
two-pipe
Cooling load, room
fan-coil unit system
D
DX systems
engineering procedure
equipment selection
piping design
system description
system features
E
Engineering procedure
DX systems
fan-coil unit system
four-pipe
three-pipe
two-pipe
Equipment selection
DX system
F
Fan-coil unit system
controls
engineering procedure
piping design
refrigeration load
room cooling load
room heating load
unit selection
system description
system features
type
multi-piping
single-piping
H
Heating load
Multi-piping fan-coil unit
system
Heating load, room
fan-coil unit system
L
Liquid chillers, description
dry expansion coolers
flooded cooler
P
Piping design
DX system
fan-coil unit system
four-pipe
three-pipe
two-pipe
R
Refrigeration load
fan-coil unit system