LT Fault Level Calculation
LT Fault Level Calculation
ENGINE
ALTERNATOR
MTU
Leroy Sommer
2756 Amps
0.417
The max power the prime mover can generate is the total fuel stop power which
is =1.17xtotal rated power (Kva)
=1.17x6000
=7020 KVA
As such IMAX =KVA max / 3xV
=7020 /3 X415
=9.77Ka
Isc of generator is 21 KA.this means that the individual generator can withstand
system max current.
As per IEC34 the max. Current capacity of alternator is only 3 times the rated
current for 3 seconds, in our case it is 3X2756=8268 Amps which is less than
IMAX and therefore the alternator is safe.
The breaker will have min 50 KA Fault level.
Here we have considered peak short circuit current which is =2 X Isc X
Short circuit ratio i.e =2 X 21 X 0.417=12.38 Ka
However in such system the thermal stability of bus bars is a must.
Copper development Association of UK has devised a formula, which is in
existence till date and is defined as under;
Temp rise in degree centigrade per second =1.25(I/A) 2 X 10-8
Where I is in Amps ,A is in Sq Inch.
In our case I is considered as Imax which is 9770 Amps ,and A(area of busbar)
= 5X200X10 /25.4 X25.4=15 Sq inch.
The temp rise per second as per above formula is 0.17 deg. C which is
negligible. Therefore thermal stability of bus bars is also ensured.
-----------------------X----------------------