ID FD PA Logic System
ID FD PA Logic System
SYSTEM
February 5, 2
PMI Revision 00
START PERMISSIVES
February 5, 2
PMI Revision 00
TRIPS
(3 min)
February 5, 2
PMI Revision 00
PA FAN
START PERMISSIVES
February 5, 2
PMI Revision 00
TRIPS
Fan bearing temperature very high.
Trip from FSSS (MFT).
Discharge damper fails to open.
February 5, 2
PMI Revision 00
ID FAN
START PERMISSIVES
Hyd. coupling Scoop position minimum.
Inlet guide vane position minimum.
Bearing temperature not high.
Oil temp. and oil level in Hyd. coupling OK.
Lube oil pressure adequate.
Both inlet and outlet dampers closed.
Other ID fan not running or Any FD fan running.
February 5, 2
PMI Revision 00
TRIP CONDITION
Fan/Motor bearing temperature very high.
Lube oil pressure very low.
Post purge furnace pressure Hi/Low from FSSS.
Discharge dampers/ suction damper fail to open
within specified time (3 min.)
Hydraulic coupling bearing temp. very high
Hydraulic coupling oil temp. very high.
February 5, 2
PMI Revision 00
PERMISSIVES
Discharge valve 1 open.
Discharge valve 2 open.
Motor cavity temp. not high.
Pump cavity suction manifold differential
temp. not high.
Motor cooling water flow adequate.
February 5, 2
PMI Revision 00
TRIPS
February 5, 2
PMI Revision 00
February 5, 2
PMI Revision 00
10
February 5, 2
PMI Revision 00
11