3p4w and 3p3w Basic Calculation

The document describes the basic calculations for determining total power in 3-phase 4-wire and 3-phase 3-wire electrical systems. For a balanced 3-phase 4-wire system, the total power is equal to 3 times the voltage between line and neutral multiplied by the current and power factor. For a balanced 3-phase 3-wire system, the total power can also be calculated as 3 times the voltage between line and neutral multiplied by the current and power factor. Total energy is calculated by multiplying total power by time.

Uploaded by

iamdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
495 views1 page

3p4w and 3p3w Basic Calculation

The document describes the basic calculations for determining total power in 3-phase 4-wire and 3-phase 3-wire electrical systems. For a balanced 3-phase 4-wire system, the total power is equal to 3 times the voltage between line and neutral multiplied by the current and power factor. For a balanced 3-phase 3-wire system, the total power can also be calculated as 3 times the voltage between line and neutral multiplied by the current and power factor. Total energy is calculated by multiplying total power by time.

Uploaded by

iamdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Basic Calculation System 3Phase 4Wires (3 Elements)

Ptotal = PphaseA + PphaseB + PphaseC


PABC = PA + PB + PC
PABC = VA.IA.Cos A + VB.IB.Cos B + VC.IC.Cos C
VA = Voltage between Phase A and Neutral
VB = Voltage between Phase B and Neutral
VC = Voltage between Phase C and Neutral
If the load is Balance, then :
VA.IA = VB.IB = VC.IC
VL-N.I
Cos A = Cos B = Cos C Cos
PABC = VL-N.I.Cos + VL-N.I.Cos + VL-N.I.Cos
PABC = 3.VL-N.I.Cos
Energy

P_total = 3.VL-N.I.Cos
Wh_total = 3.VL-N.I.Cos time

Basic Calculation System 3Phase 3Wires (2 Elements)


Ptotal = PphaseA + PphaseC
PAC = PA + PC
PAC = VBA.IA.Cos( A+30) + VBC.IC.Cos( C-30)
Cos(X+Y) = CosX . CosY + SinX . SinY
Cos(X-Y) = CosX . CosY - SinX . SinY
VBA = Voltage between Phase B and Phase A
VBC = Voltage between Phase B and Phase C
If the load is Balance, then :
VBA.IA = VBC.IB VL-L.I
Cos A = Cos C
Cos
PAC

Sin30

= VBA.IA.Cos( A+30) + VBC.IC.Cos( C-30)


= VL-L.I.Cos( +30) + VL-L.I.Cos( -30)

= VL-L.I. (Cos. Cos30 + Sin . Sin30) + VL-L.I. (Cos. Cos30 - Sin . Sin30)
= VL-L.I. Cos. Cos30 + VL-L.I.Sin . Sin30 + VL-L.I.Cos. Cos30 - VL-L.I.Sin . Sin30
= VL-L.I. Cos. Cos30 + VL-L.I.Cos. Cos30 + VL-L.I.Sin . Sin30 - VL-L.I.Sin .

= VL-L.I. Cos. Cos30 + VL-L.I.Cos. Cos30


= VL-L.I. Cos. Cos30 + VL-L.I.Cos. Cos30
1
1
= VL-L.I. Cos.
3 + VL-L.I.Cos.
3
2
2
2
= VL-L.I. Cos.
3
2
= 3 . VL-L.I. Cos VL-L = VL-N. 3
= 3 . 3 .VL-N.I.Cos
= 3.VL-N.I.Cos
Daya
Energy

P_total = 3.VL-N.I.Cos
Wh_total = 3.VL-N.I.Cos time