Corrosion resistant coatings, where applicable, are utilized to extend the life of
copper alloy sprinklers beyond that which
would otherwise be obtained when exposed to corrosive atmospheres. Although
corrosion resistant coated sprinklers have
passed the standard corrosion tests of the
applicable approval agencies, the testing is
not representative of all possible corrosive
atmospheres. Consequently, it is recommended that the end user be consulted
with respect to the suitability of these corrosion resistant coatings for any given corrosive environment. The effects of ambient
temperature, concentration of chemicals,
and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the
sprinklers will be exposed.
WARNINGS
The Series EC-11 and EC-14 Extended Coverage Sprinklers described herein must be installed and maintained in compliance with
this document, as well as with the applicable
standards of the National Fire Protection Association, in addition to the standards of any
other authorities having jurisdiction. Failure
to do so may impair the performance of
these devices.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
IMPORTANT
Always refer to Technical Data Sheet
TFP700 for the INSTALLER WARNING
that provides cautions with respect to
handling and installation of sprinkler
systems and components. Improper handling and installation can permanently
damage a sprinkler system or its components and cause the sprinkler to fail to
operate in a fire situation or cause it to
operate prematurely.
Model/Sprinkler
Identification
Number
TY5137 - Upright, 11.2K
TY5237 - Pendent, 11.2K
TY6137 - Upright, 14.0K
TY6237 - Pendent,14.0K
TY5137 is a redesignation
G1894, and S2510.
TY5237 is a redesignation
G1893, and S2511.
TY6137 is a redesignation
G1896, and S2610.
TY6237 is a redesignation
G1895, and S2611.
for C5137,
for C5237,
for C6137,
for C6237,
TFP220_EN
Page2 of 8
TFP220_EN
3/4 **
NPT
WRENCH
FLAT
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector*
ESCUTCHEON PLATE
SEATING SURFACE
1
2
2-7/16
(61,9mm)
UPRIGHT &
PENDENT
* Temperature rating is
indicated on deflector
3
4
** Pipe thread
connections per ISO
7/1 can be provided
on special request.
5
6*
NOMINAL MAKE-IN
1/2 (12,7 mm)
UPRIGHT
SECTION
CROSS
PENDENT
FIGURE 1
SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT
14.0 K-FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT
SPRINKLER FINISH (See Note 5)
HAZARD
TYPE
LIGHT
UPRIGHT
K=11.2 (TY5137)
PENDENT
K=11.2 (TY5237)
K=14.0 (TY6237)
ORDINARY
Refer to Table B for
UL and C-UL
Sensitivity Rating
and
Refer to Table C for
FM
Sensitivity Rating
REC. PENDENT
K=11.2 (TY5237)
K=14.0 (TY6237)
With Style 30
Escutcheon
UPRIGHT
K=11.2 (TY5137)
K=14.0 (TY6137)
and
PENDENT
K=11.2 (TY5237)
K=14.0 (TY6237)
REC. PENDENT
K=11.2 (TY5237)
K=14.0 (TY6237)
With Style 40
Escutcheon
TEMP.
BULB
LIQUID
135F/57C
Orange
155F/68C
Red
175F/79C
Yellow
200F/93C
Green
286F/141C
Blue
135F/57C
Orange
155F/68C
Red
175F/79C
Yellow
200F/93C
Green
286F/141C
Blue
135F/57C
Orange
155F/68C
Red
175F/79C
Yellow
200F/93C
Green
286F/141C
Blue
135F/57C
Orange
155F/68C
Red
175F/79C
Yellow
200F/93C
Green
NATURAL
BRASS
CHROME
PLATED
WHITE*
POLYESTER
LEAD
COATED
1, 2, 3**, 4
1, 2, 4
1, 2, 4
1, 2, 3, 4
N/A
1, 2, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 4
1, 2, 4
N/A
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the City of New York under MEA 177-03-E.
5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant
Sprinklers.
* Frame and Deflector only. Listings and approvals apply to color (Special Order).
** Pendent Only.
N/A: Not Available
TFP220_EN
Page3 of 8
LIGHTHAZARD
ORDINARY HAZARD
57C
68C
79C
93C
141C
57C
68C
79C
93C
141C
AREA
STYLE
14 x 14
14 x 14
14 x 14
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR
QR
QR
QR
QR
QR
QR
QR
QR
QR
QR
QR
SR
N/A
N/A
16 x 16
16 x 16
16 x 16
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
N/A
N/A
18 x 18
18 x 18
18 x 18
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
N/A
N/A
20 x 20
20 x 20
20 x 20
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
QR*
QR*
N/A
SR*
SR*
N/A
SR*
SR*
N/A
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
SR
N/A
N/A
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS
(SEE TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
LIGHTHAZARD
ORDINARY HAZARD
57C
68C
79C
93C
141C
57C
68C
79C
93C
141C
AREA
STYLE
14 x 14
14 x 14
14 x 14
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
16 x 16
16 x 16
16 x 16
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
18 x 18
18 x 18
18 x 18
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
20 x 20
20 x 20
20 x 20
Up. or Pend.
Style 30 Recessed
Style 40 Recessed
QR*
QR*
N/A
QR*
QR*
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS
(SEE FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
Page4 of 8
TFP220_EN
Technical
Data
Design
Criteria
Approvals
UL and C-UL Listed. FM Approved. (Refer to
Table A for complete approval information
including corrosion resistant status. The approvals apply to the service conditions indicated in the Design Criteria section.)
The Series EC-11 and EC-14 Extended Coverage Sprinklers must only be installed in
accordance with the applicable UL and CUL Listing or FM Approval requirements
as indicated below. Only the Style 30 or 40
Recessed Escutcheon is to be used for recessed installation, as applicable (Ref. Table
A, B, and C).
2.
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame............................................................Bronze
Button...........................................................Bronze
Sealing Assembly..................................................
.................................. Beryllium Nickel w/Teflon
Bulb.............................................Glass (3mmdia.)
Compression Screw.................................Bronze
Deflector......................................................... Brass
Unobstructed, combustible or non-- combustible, ceiling construction with a deflector to ceiling/roof deck distance of 1 to 12
inches (25 to 300 mm).
Obstructed, non-combustible, ceiling
construction with a deflector location below
structural members of 1 to 6 inches (25
to 150 mm) and a maximum deflector to
ceiling/roof deck distance of 22 inches (550
mm).
3.
The Series EC-11 and EC-14 Sprinklers having been specifically tested and listed for
non-combustible obstructed construction
are permitted to be used within trusses
or bar joists having non-combustible web
members greater than 1 inch (25.4 mm)
when applying the 4 times obstruction
criteria rule defined under Obstructions to
Sprinkler Discharge Pattern Development.
4.
5.
Patents
U.S.A. Patent Numbers 5,366,022; 5,579,846;
5,584,344; 5,609,211; 5,862,994; and
5,865,256.
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the
rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate
and flow water.
etc.
UL and C-UL Specific Application Listing Requirements For Installation Under
Concrete Tees The Series EC-11 and EC-14
Extended Coverage Upright and Pendent
Sprinklers (TY5137, TY5237, TY6137 &
TY6237) have a UL and C-UL Specific Application Listing for use under concrete tees
when installed as follows:
1.
2.
3.
FM Approval
Requirements
The Series EC-11 and EC-14 Extended Coverage Sprinklers are to be installed in accordance with the applicable Factory Mutual
Loss Prevention Data Sheet for limited use
in buildings of specific roof construction
and for the protection of certain specific
ordinary hazard (non-storage and/or nonflammable or combustible liquid) occupancies. Information provided in the FM Loss
Prevention Data Sheets relate to, but are not
limited to, hydraulic design, ceiling slope
and obstructions, minimum and maximum
allowable spacing, and deflector-to ceiling
distance. These criteria may differ from UL
and/or NFPA criteria, therefore the designer
should review and become familiar with
Factory Mutual requirements before proceeding with design.
TFP220_EN
1/21/8
(12,73,2 mm)
FACE OF
SPRINKLER
FITTING
Page5 of 8
2-7/8 DIA.
(73,0 mm)
2-1/4 DIA.
(57,2 mm)
FITTING SIDE
TOWARDS SPRINKLER
FITTING
1/8
(3,2 mm)
WRENCH
RECESS
(END A)
MOUNTING
SURFACE
MOUNTING
PLATE
CLOSURE
1-3/8 (34,9 mm)
1-1/8 (28,6 mm)
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
FIGURE 2
SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
5/81/4
(15,96,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2-7/8 DIA.
(73,0 mm)
2-1/4 DIA.
(57,2 mm)
MOUNTING
PLATE
1-3/8 (34,9 mm)
7/8 (22,2 mm)
FIGURE 3
SERIES EC-11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
FIGURE 5
W-TYPE 22 RECESSED
SPRINKLER WRENCH
WRENCH
HEX
Page6 of 8
TFP220_EN
LIGHT HAZARD
0.10 GPM/FT2
GROUP I
ORDINARY HAZARD
0.15 GPM/FT2
GROUP II
ORDINARY HAZARD
0.20 GPM/FT2
DESCRIPTION
AREA
GPM
PSI
GPM
PSI
GPM
PSI
14 x 14
16 x 16
18 x 18
20 x 20
30
33
40
7.2
8.7
12.8
30
39
49
60
7.2
12.1
19.1
28.7
39
51
65
80
12.1
20.7
33.7
51.0
14 x 14
16 x 16
18 x 18
20 x 20
30
33
40
7.2
8.7
12.8
30
39
49
60
7.2
12.1
19.1
28.7
39
51
65
80
12.1
20.7
33.7
51.0
14 x 14
16 x 16
18 x 18
20 x 20
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
39
49
60
7.8
12.3
18.4
51
65
80
13.3
21.6
32.7
14 x 14
16 x 16
18 x 18
20 x 20
37
37
40
7.0
7.0
8.2
39
49
60
7.8
12.3
18.4
51
65
80
13.3
21.6
32.7
1 ft. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3.785 lpm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/min
TABLE D
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS
Installation
The Series EC-11 and EC-14 Sprinklers must
be installed in accordance with the following instructions:
NOTES
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid from
the bulb. With the sprinkler held horizontally,
a small air bubble should be present. The diameter of the air bubble is approximately
1/16 inch (1,6 mm) for the 135F/57C to 3/32
inch (2,4 mm) for the 286F/141C temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint should
be obtained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30 ft.lbs.
(40.7 Nm) of torque is to be used to install
sprinklers. Higher levels of torque may distort
the sprinkler inlet with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate for insufficient
adjustment in an Escutcheon Plate by underor over-tightening the Sprinkler. Readjust the
position of the sprinkler fitting to suit.
TFP220_EN
Care and
Maintenance
The Series EC-11 and EC-14 Sprinklers must
be maintained and serviced in accordance
with the following instructions:
NOTE
Before closing a fire protection system main
control valve for maintenance work on the
fire protection system that it controls, permission to shut down the affected fire protection
systems must be obtained from the proper
authorities and all personnel who may be affected by this actionmust be notified.
Page7 of 8
The owner is responsible for the inspection, testing, and maintenance of their fire
protection system and devices in compliance with this document, as well as with
the applicable standards of the National
Fire Protection Association (e.g., NFPA 25),
in addition to the standards of any other
authorities having jurisdiction. The installing contractor or sprinkler manufacturer
should be contacted relative to any questions.
It is recommended that automatic sprinkler
systems be inspected, tested, and maintained by a qualified Inspection Service in
accordance with local requirements and/or
national codes.
Limited Warranty
Products manufactured by Tyco Fire & Building Products (TFBP) are warranted solely to
the original Buyer for ten (10) years against
defects in material and workmanship when
paid for and properly installed and maintained under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warranty is
given for products or components manufactured by companies not affiliated by
ownership with TFBP or for products and
components which have been subject to
misuse, improper installation, corrosion, or
which have not been installed, maintained,
modified or repaired in accordance with applicable Standards of the National Fire Protection Association, and/or the standards
of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at
TFBPs sole option. TFBP neither assumes,
nor authorizes any person to assume for it,
any other obligation in connection with the
sale of products or parts of products. TFBP
shall not be responsible for sprinkler system
design errors or inaccurate or incomplete
information supplied by Buyer or Buyers
representatives.
In no event shall TFBP be liable, in contract,
tort, strict liability or under any other legal theory, for incidental, indirect, special
or consequential damages, including but
not limited to labor charges, regardless of
whether TFBP was informed about the possibility of such damages, and in no event
shall TFBPs liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu of
any and all other warranties express or
implied, including warranties of merchantability and fitness for a particular purpose.
This limited warranty sets forth the exclusive remedy for claims based on failure of
or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal
theory.
This warranty will apply to the full extent
permitted by law. The invalidity, in whole or
part, of any portion of this warranty will not
affect the remainder.
Page8 of 8
TFP220_EN
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the Sprinkler
Identification Number (SIN), quantity, and
temperature rating.Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for availability.
Recessed Escutcheon:
Specify: Style (specify 30 or 40) Recessed
Escutcheon with (specify finish), P/N (specify).
Note: This document is a translated document. Translations of any materials into languages other than English are intended solely as a convenience to the non-English-reading
public. Translation accuracy is neither guaranteed nor implied. If any questions arise related to the accuracy of the information contained in the translation, please refer to the
English version of document TFP220 which is the official version of the document. Any discrepancies or differences created in the translation are not binding and have no legal
effect for compliance, enforcement or any other purposes. www.quicksilvertranslate.com.
TYCO
FIRE PRODUCTS,
451451
North
Cannon
Avenue,
Lansdale,
Pennsylvania
19446 19446
TYCO FIRE
& BUILDING
PRODUCTS,
North
Cannon
Avenue,
Lansdale,
Pennsylvania