BestPractices Thermoplastic Sep08

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

BEST PRACTICES FOR SOLVENT WELDING THERMOPLASTIC PIPING: PVC, CPVC, and ABS

By Stephen Gardiner, IPS Corporation

SUMMARY OF PRACTICE
MATERIAL PREPARATION
SOLVENT WELDING PROCEDURES FOR PLASTIC PIPE AND FITTINGS
A. TWO-STEP SOLVENT WELDING METHOD FOR PVC AND CPVC PLASTIC PIPE AND
FITTINGS
B. ONE-STEP SOLVENT WELDING METHOD FOR CPVC PLASTIC PIPE AND FITTING
(COPPER TUBE SIZE  TO 2 DIAMETER) HOT AND COLD WATER DISTRIBUTION
SYSTEMS
C. ONE-STEP SOLVENT WELDING METHOD FOR CPVC PLASTIC PIPE AND FITTING FIRE
SPRINKLER SYSTEMS
D. ONE-STEP SOLVENT WELDING METHOD FOR ABS PLASTIC PIPE AND FITTINGS
SYSTEM ACCEPTANCE (HYDROSTATIC PRESSURE) TEST
NOTE: SOLVENT WELDING IN LOW TEMPERATURE
NOTE: SAFE HANDLING OF SOLVENT CEMENT, PRIMER AND CLEANER

COPYRIGHT 2008 by IPS Corporation

Page 1 of 10

SUMMARY OF PRACTICE (refer to ASTM D 2855)


1.
To consistently make good solvent welded joints, the following should be clearly understood and
adhered to:

The joining surfaces must be softened (dissolved) and made semi-fluid.

Sufficient solvent cement must be applied to fill the gap between pipe and fitting.

Assembly of pipe and fitting must be made while the surfaces are still wet and fluid.

Joint strength develops as the solvent cement dries. In the tight part of the joint, the surfaces
will tend to fuse together; in the loose part, the solvent cement will bond to both surfaces.

2.
Penetration and dissolving can be achieved by the solvent cement itself, a suitable primer, or by
the use of both primer and solvent cement. A suitable primer will penetrate and dissolve the plastic more
quickly than solvent cement alone. In cold weather, more time and additional applications are required
(see Figure 1).
3.
More than sufficient to fill the loose part of the joint must be applied (see Figure 2). Besides filling
the gap, adequate solvent cement layers will penetrate the surfaces and also remain wet until the joint is
assembled.
4.
If the solvent cement coatings on the pipe and fittings are wet and fluid when assembly takes
place, they will tend to flow together and become one solvent cement layer. Also, if the solvent cement is
wet, the surfaces beneath them will still be soft, and these dissolved surfaces in the tight part of the joint
will tend to fuse together (see Figure 3).
5.
As the solvent dissipates, the solvent cement layer and the dissolved surfaces will harden with a
corresponding increase in joint strength. A good joint will take the required working pressure long before
the joint is fully dry and final strength is obtained. In the tight (fused) part of the joint, strength will develop
more quickly than in the looser (bonded) part of the joint. Completed joints should not be disturbed until
they have cured sufficiently to withstand handling. Joint strength develops as the solvent cement dries.
Information about the development of bond strength of solvent cemented joints is available (see Figure
4).
6.
The techniques described herein can be used to produce strong pressure-tight joints between
pipe and fittings of PVC, CPVC, and ABS., either in shop operations or in the field. However, skill and
knowledge on the part of the welder are required to obtain a good quality joint. This skill and knowledge
can be obtained by making joints under the guidance of skilled welders and testing them until good quality
joints are obtained.

COPYRIGHT 2008 by IPS Corporation

Page 2 of 10

Figure 1: Areas of Pipe and Fitting to be Softened (Dissolved) and Penetrated

Figure 2: Solvent Cement Coatings of Sufficient Thickness

COPYRIGHT 2008 by IPS Corporation

Page 3 of 10

Figure 3: Assembly of Surfaces While They Are Wet and Soft

Figure 4: Fused and Bonded Surfaces of Joined Pipe and Fitting

COPYRIGHT 2008 by IPS Corporation

Page 4 of 10

MATERIAL PREPARATION
1.
Cutting the Pipe. It is important to cut the pipe square. A square cut provides the surface of the
pipe with the maximum bonding area. Pipe can be easily cut with a ratchet cutter, wheel-type plastic
tubing cutter, power saw, chop saw, or fine toothed saw. Tools used to cut pipe must be designed for
plastic use and must be in good condition in accordance with the tool manufacturers recommendations. If
there is any indication of damage or evidence of cracking, cut off at least 2 inches (50mm) beyond any
visible crack. Care must be exercised if using ratchet cutters, especially at low temperatures, as they may
split the pipe if not properly used and maintained.
2.
Deburring and Beveling. Burrs and filings can prevent proper contact between pipe and fitting
during assembly, and must be removed from the outside and the inside of the pipe. A chamfering tool or a
file is suitable for this purpose. A slight bevel (approximately 10-15 chamfer and a minimum width of
3/32 of an inch) shall be placed at the end of the pipe to ease entry of the pipe into the fitting socket. This
will minimize the chance that the edges of the pipe will wipe solvent cement or will scrape softened
surface material from the fitting socket during the insertion of the pipe.
3.
Test Dry Fit of the Joint. The pipe should enter the fitting socket easily  to  of the way for a
tight interference fit. Contact between pipe and fitting is essential in making a good joint. This contact
allows the solvent cement to effectively join the pipe and fitting.
4.
Cleaning. Using a clean dry rag, wipe any dirt and moisture from the fitting socket and the pipe
end. Moisture will slow the cure time, and at this stage of assembly, excessive water can reduce joint
strength.
5.
Applicator Size. Use an applicator that is properly sized for the pipe and will completely coat the
surfaces of the pipe and fittings with primer and solvent cement. Dauber-type applicators will give
adequate coverage on pipe diameters that are approximately twice the diameter of the dauber-ball. Swab
or roller-type applicators are preferable on larger diameter pipe surfaces of 4 and above.

COPYRIGHT 2008 by IPS Corporation

Page 5 of 10

SOLVENT WELDING PROCEDURES FOR PLASTIC PIPE AND FITTINGS


A. TWO-STEP SOLVENT WELDING METHOD FOR PVC AND CPVC PLASTIC PIPE AND FITTINGS
1.
Apply primer to the inside of the fitting socket. Be aggressive and work the solvents into the
surface to break down the surface tension and to soften the surfaces.
2.

Apply primer to the pipe end, equal to the depth of the fitting socket. Be aggressive.

3.

Apply primer to the inside of the fitting socket.

4.
While the primer is still wet and the surfaces are soft, apply a full, even layer of solvent cement,
equal to the depth of the fitting socket, to the pipe end. Like the primer, be aggressive. Remember to
apply enough solvent cement to fill the gap between the pipe and fitting.
Use PVC solvent cement that meets ASTM D 2564 on PVC plastic pipe and fittings.
Use CPVC solvent cement that meets ASTM F 493 on CPVC plastic pipe and fittings.
For CPVC potable water systems, use a purple primer and orange CPVC solvent cement in
accordance with UPC 605.16.2.
5.

Apply a thin layer of solvent cement to the inside of the fitting socket.
5.1
This will prevent puddling of the solvent cement inside of the pipe or fitting. Excessive
solvent cement applied to the fitting socket can cause the joint to clog and the wall of the pipe or
fitting to weaken due to softening by the trapped solvents.

6.
Apply a second full, even layer of solvent cement to the pipe end. Excessive solvent cement on
the pipe outer diameter (O.D.) can be easily wiped away after assembly.
7.
Without delay, while the solvent cement is still wet, assemble the pipe and fitting, and twist a 
turn as the pipe is being inserted, if possible. Once the pipe end has reached the fitting socket stop, do
not turn any further; doing so could break any fusion that is starting to occur.
8.

Hold the pipe and fitting together for approximately 30 seconds to avoid push out.

9.
A bead of solvent cement must be around the entire socket fitting entrance. With a clean, dry
cloth, remove the excess solvent cement from the pipe and fitting socket entrance. This will allow the
solvent to evaporate from within the joint.

COPYRIGHT 2008 by IPS Corporation

Page 6 of 10

B. ONE-STEP SOLVENT WELDING METHOD FOR CPVC PLASTIC PIPE AND FITTING (COPPER
TUBE SIZE  TO 2 DIAMETER) HOT AND COLD WATER DISTRIBUTION SYSTEMS
1.
Apply yellow CPVC solvent cement to the pipe end. Be aggressive to break down the surface
tension and to soften the surfaces.
Use CPVC solvent cement that meets ASTM F 493 on CPVC plastic pipe and fittings.
For CPVC potable water systems, use yellow CPVC one-step solvent cement in accordance with
UPC 605.16.2.
2.
Without re-dipping the dauber, apply a very light layer of solvent cement to the inside of the fitting
socket.
2.1
This will prevent puddling of the solvent cement inside of the pipe or fitting. Excessive
solvent cement applied to the fitting socket can cause the joint to clog and the wall of the pipe or
fitting to weaken due to softening by the trapped solvents.
3.
Without delay, while the solvent cement is still wet, assemble the pipe and fitting, and twist a 
turn as the pipe is being inserted, if possible. Once the pipe end has reached the fitting socket stop, do
not turn any further; doing so could break any fusion that is starting to occur.
4.

Hold the pipe and fitting together for approximately 30 seconds to avoid push out.

5.
A bead of solvent cement must be around the entire socket fitting entrance. With a clean, dry
cloth, remove the excess solvent cement from the pipe and fitting socket entrance. This will allow the
solvent to evaporate from within the joint.

COPYRIGHT 2008 by IPS Corporation

Page 7 of 10

C. ONE-STEP SOLVENT WELDING METHOD FOR CPVC PLASTIC PIPE AND FITTING FIRE
SPRINKLER SYSTEMS
1.
Apply red CPVC solvent cement to the pipe end. Be aggressive to break down the surface
tension and to soften the surfaces.
1.1

Use CPVC solvent cement that meets ASTM F 493 on CPVC plastic pipe and fittings.

1.2
For CPVC fire sprinkler systems, use red CPVC one-step solvent cement that have been
specifically investigated and tested for this use, and approved by the pipe and fittings
manufacturers.
2.
Without re-dipping the dauber, apply a light layer of solvent cement to the inside of the fitting
socket.
2.1
This will prevent puddling of the solvent cement inside of the pipe or fitting. Excessive
solvent cement applied to the fitting socket can cause the joint to clog and the wall of the pipe or
fitting to weaken due to softening by the trapped solvents.
3.
Apply a second full, even layer of solvent cement to the pipe end. Excessive solvent cement on
the pipe O.D. can be easily wiped away after assembly.
4.
Without delay, while the solvent cement is still wet, assemble the pipe and fitting, and twist a 
turn as the pipe is being inserted, if possible. Once the pipe end has reached the fitting socket stop, do
not turn any further; doing so could break any fusion that is starting to occur.
5.

Hold the pipe and fitting together for approximately 30 seconds to avoid push out.

6.
A bead of solvent cement must be around the entire socket fitting entrance. With a clean, dry
cloth, remove the excess solvent cement from the pipe and fitting socket entrance. This will allow the
solvent to evaporate from within the joint.
7.
Sprinkler heads shall be installed only after all of the CPVC pipe and fittings, including the
sprinkler head adapters, are solvent welded and allowed to cure for a minimum of 30 minutes.

COPYRIGHT 2008 by IPS Corporation

Page 8 of 10

D. ONE-STEP SOLVENT WELDING METHOD FOR ABS PLASTIC PIPE AND FITTINGS
1.
Apply ABS solvent cement to the pipe end. Be aggressive to break down the surface tension and
to soften the surfaces.
1.1

Use ABS solvent cement that meets ASTM D 2235 on ABS plastic pipe and fittings.

1.2

Primer shall NEVER be used when solvent welding ABS pipe and fittings.

2.
Without re-dipping the dauber, apply a very light layer of solvent cement to the inside of the fitting
socket.
2.1
This will prevent puddling of the solvent cement inside of the pipe or fitting. Excessive
solvent cement applied to the fitting socket can cause the joint to clog and the wall of the pipe or
fitting to weaken due to softening by the trapped solvents.
3.
Apply a second full, even layer of solvent cement to the pipe end. Excessive solvent cement on
the pipe O.D. can be easily wiped away after assembly.
4.
Without delay, while the solvent cement is still wet, assemble the pipe and fitting, and twist a 
turn as the pipe is being inserted, if possible. Once the pipe end has reached the fitting socket stop, do
not turn any further; doing so could break any fusion that is starting to occur.
5.

Hold the pipe and fitting together for approximately 30 seconds to avoid push out.

6.
A bead of solvent cement must be around the entire socket fitting entrance. With a clean, dry
cloth, remove the excess solvent cement from the pipe and fitting socket entrance. This will allow the
solvent to evaporate from within the joint.

COPYRIGHT 2008 by IPS Corporation

Page 9 of 10

SYSTEM ACCEPTANCE (HYDROSTATIC PRESSURE) TEST


1.
Set time is the time required before the joint can be carefully handled. Refer to the solvent
cement manufacturer for recommended set times.
2.
Cure time is the time required before the system can be hydrostatically pressure tested. Refer to
the solvent cement manufacturer for recommended cure times.
Cure time is dependent upon pipe diameter, solvent cement viscosity, ambient temperature, humidity,
and the dry-joint tightness (interference fit). As a general rule, relatively short cure periods are satisfactory
for high-ambient temperatures with low humidity, small pipe sizes, quick-drying solvent cements, and
tight-fitting joints. Longer cure periods are required for low temperatures, large pipe sizes, slow-drying
solvent cements, loose joints, and relatively high humidity.
3.
Hydrostatic pressure test should be 150% of the system design pressure and held at
this pressure until the system is checked for leaks, or follow the requirements of the applicable
code, whichever is higher.
3.1
tests.

Shade backfill, leaving all joints exposed so that they can be examined during pressure

3.2
On long runs, pressure tests should be performed on sections not longer than 5000 feet
(1500 meters).
3.3
DANGER! Air or compressed gas must never be used for system acceptance
testing. Use HYDROSTATIC PRESSURE TEST ONLY. System failure when using
compressed air or gas for system acceptance testing can result in bodily injury, death
and/or property damage.
3.4
If a leak is found, the joint must be cut out and discarded. A new section can be installed
using coupling, mechanical repair joint, or a union. Mechanical repair joints or unions should be
used in accessible areas only.
NOTE: SOLVENT WELDING IN LOW TEMPERATURE
Using a little extra care, successful solvent welded joints can be made at temperatures as low as -15F (26C). In cold weather, solvents penetrate and soften the thermoplastic pipe and fitting surfaces more
slowly than in warm weather. The thermoplastic is also more resistant to solvent attack. Therefore, it
becomes even more important to pre-soften surfaces of the pipe and fittings with an aggressive primer.
Because of slower evaporation of the solvents, a longer cure time is necessary.
NOTE: SAFE HANDLING OF SOLVENT CEMENT, PRIMER AND CLEANER
1.
Solvent cement, primer, and cleaner for plastic pipe are made from flammable liquids and should
be kept away from all sources of ignition. Good ventilation should be maintained to reduce fire hazard and
to minimize the breathing of solvent vapors. Avoid contact with skin and eyes.
2.
Refer to ASTM F 402, Standard Practice for Safe Handling of Solvent Cements, Primers, and
Cleaners Used for Joining Thermoplastic Pipe and Fittings, plus the cautionary notes contained in the
Material Safety Data Sheets (MSDSs) supplied by the material supplier.

COPYRIGHT 2008 by IPS Corporation

Page 10 of 10

You might also like