Codes & Standards: ASME Section I Boiler and Pressure Vessel Code For Fired Vessels
Codes & Standards: ASME Section I Boiler and Pressure Vessel Code For Fired Vessels
ASME Section I Boiler and Pressure Vessel Code for Fired Vessels
Requirements
Conditions
Single Valve
SIZING
Number of valves
Superheater
Reheater
Required Capacity
Set pressure
Blowdown
OTHER
Tightness
Pressures above 15 psig, up to and including 70 psig = 2 psi. Pressures over 70 psig, up to and including 300 psig = 3%. Pressures over 300 psig, up to and including 1000 psig = 10 psi.
Pressures over 1000 psig = 1%.
Minimum Blowdown - Minimum blowdown, regardless of set pressure, is 2 psi. For pressures above 100 psig, the blowdown shall not be less than 2% of the set pressure.
Maximum Blowdown - After blowing down, all valves set at pressures of 375 psi or greater shall close at a pressure not lower than 96% of their set pressure, except that all drum valves
installed on a single boiler may be set to reseat at a pressure not lower than 96% of the set pressure of the lowest set drum valve. For pressures below 375 psi, blowdown shall not exceed that
specified in the following table:
Set Pressure, psi
15-66
67-250
251-374
Maximum Blowdown
4 psi
6% of set pressure
15 psi
A tightness test shall be conducted at the maximum expected operating pressure, but at a pressure not exceeding the reseating pressure of the valve. When testing, a valve exhibiting no visible signs
of leakage shall be considered tight.
Boiler Design Pressure (psig)
Nameplate Stamping
Multiple Valves
15 to 300
301 to 1000
1001 to 2000
2000 and above
Valves shall be stamped with ASME Symbol V. Official stamped relieving capacity is at 3% accumulation or 2 psig, whichever is greater.
Note: The following information has been extracted from the ASME Boiler and Pressure Vessel Code Section I (2001) to be used purely as a reference source and is not intended to be a complete reproduction of that
document. Paragraphs PG-67.1, PG-67.2, PG-67.3, PG-72.1, and PG-72.2 are referenced.
CS.1
Sizing Condition
UG - 125(c), UG - 134(a),
UG - 134(e)
UG - 125(c)(1), UG - 133(a),
UG - 134(e)
UG - 125(c)(2), UG - 133(b),
UG - 134(e)
UG - 125(c)(3), UG - 134(e)(2)
Sizing
Set Point
(Note: The pressure setting of each
valve shall include the effects of
static head and constant back
pressure.)
The set pressure tolerance, (plus or minus), of pressure relief valves shall not exceed 2 psi (13.6kPa) for
pressures up to and including 70 psi (483 kPa) and 3% for pressures above 70 psi (483 kPa).
Blowdown
Valves designed and capacity tested in accordance with Code Section VIII are capable of being set for 7% Blowdown. Section VIII does not require a specific blowdown setting
by the valve manufacturer. (The user should specify the required blowdown that will permit reclosing of valve above the normal operating pressure.)
Tightness
UG - 136(d)(2)
Code requires a tightness test be conducted at the maximum expected operating pressure. This maximum pressure is not to exceed the resealing pressure of the valve. Then
testing with either water or steam, a valve exhibiting no visible signs of leakage shall be considered adequately tight. Leakage tests conducted with air shall be in accordance
with industry standards.
Note: The following information has been extracted from the ASME Boiler and Pressure Vessel Code Section I (1998) to be used purely as a reference source and is not intended to be a complete reproduction of that document.
CS.2