Reverse Power Relay

The T2000 Reverse Power Relay protects generator prime movers from reverse power by measuring voltage and current inputs to calculate active power. If active power becomes negative and exceeds the preset level for the entire preset delay time, the output relay and LED will activate to trip the generator breaker. It has adjustable trip levels from 2-20% and delay times from 2-20 seconds. The relay provides protection for generators in both marine and land-based applications and is certified by major marine classification societies.

Uploaded by

kirananne
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
253 views2 pages

Reverse Power Relay

The T2000 Reverse Power Relay protects generator prime movers from reverse power by measuring voltage and current inputs to calculate active power. If active power becomes negative and exceeds the preset level for the entire preset delay time, the output relay and LED will activate to trip the generator breaker. It has adjustable trip levels from 2-20% and delay times from 2-20 seconds. The relay provides protection for generators in both marine and land-based applications and is certified by major marine classification societies.

Uploaded by

kirananne
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

T2000 Reverse Power Relay

Protection of generator prime movers


against reverse power
Visual indication of power, pick-up
and relay tripping
High precision digital countdown
timer for delayed output
Direct Line-Line supply where neutral
is not available
Accepts high supply voltage variations:
50 - 110%
Cost effective and highly reliable
compact design
50 hours burn-in before final test
Operating temperature range:
-20C to +70C
Certified by major marine
classification societies
Flame retardant enclosure
DIN rail or screw mounting

Function

The T2000 measures the voltage across


phases L1 and L2 (or between L1 and
neutral for L-N operation) and the
current through a current transducer
attached on phase L1.
The T2000 calculates I x cos F, repre
senting the active power. If the active
power becomes negative and exceeds
the preset level (2 - 20%), the pick-up
LED will indicate and the delay timer
will be started.
After the preset time (2 - 20 sec.) has
expired, the output relay and LED will
be activated, provided that the reverse
power level was exceeded for the entire
delay time.

Installation

Typical setting of reverse power: For


diesel engines 8%, delay 10 sec. and for
turbines 4%, delay 10 sec.
Example of setting:
Required trip level: 8%
Generator rating: 714A at PF = 0.8
I p max: 714 x 0.8 = 571A
Current transformer: 800/5A
Setting: 8 x 571/800 = 5.7%
It is important that the phase where the
current is measured always is connected
to terminals 1 or 2. See connection
diagram.
For L- L operation terminal 3 is
connected to the next phase in the phase
sequence. For L- N operation terminal 3
is connected to neutral.
It is important that the phase sequence
is correct and the current transformer
side nearest the generator side is connec
ted to terminal 5.

Troubleshooting

1) If the relay operates on forward load,


the wiring to terminals 5 and 6 are
interchanged.
2) If the relay is not operating in any
power direction and there is voltage
on terminals 1 and 3 or terminals 2
and 3, check that current is floating
in the current circuit terminals 5 and 6.
3) If the relay trips at different levels
when the tests are repeated, check
that the voltage and current inputs
have the correct phase relationship
and that the phase sequence is correct.
4) If the relay trips in situations with
high motor loads, check (as in 3) that
the voltage and current inputs have
the correct phase relationship and
that the phase sequence is correct.
100

Fixing holes
2 x 4,5 mm.

7.5

85
115

The LED based pick-up indication is


ideal for testing. The T2000 can be
tested by reducing the speed on the
generator, until the pick-up LED
indicates exceeding the preset reverse
power level.

Dimensions in mm.

Dimensions.

70

Together with the T2100 Excitation Loss


Relay, the T2500 Overcurrent and Short
Circuit Relay and the T2700 Power
Relay, the T2000 provides the optimal
solution for complete generator protec
tion, both in marine and land-based
applications. The T2000 is type approved
by major marine classification societies.

The output relay is a latching relay. The


latching can be reset or disabled by
bridging terminals 13 and 14.

50

The T2000 Reverse Power Relay will


under parallel operation prevent the
generator from running as a motor, thus
protecting the prime mover (e.g. a
diesel engine) by tripping the generator
breaker, and at the same time avoiding
overload on the remaining generators
with a possible blackout of the system.

10

Application

Specifications
T2000 Reverse Power Relay
G

L - L SUPPLY

13
RESET
14
7
8
9
10

1
2
3

5
6

L1

C/B TRIP

L2

L3

LOAD

L - N SUPPLY

13
RESET
14
7
8
9
10

C/B TRIP

1
2
3

5
6

L1

L2

L3

LOAD

Connection diagram. Relay shown de-energized.

Type Approvals and Certificates


The T2000 has been approved by the
following marine classification societies:

Trip level

2 - 20% IN

Delay

2 - 20 sec.

Max. voltage

660V

Voltage range

50 - 110%

Consumption

Voltage 5VA at U N
Current 0.3VA at I N

Continuous current

2 x IN

Frequency range

45 - 400Hz

Output relay

Normally de-energized, latching, resetable

Contact rating

AC: 400V, 5A, 1250VA


DC: 150V, 5A, 120W

Overall accuracy

5%

Repeatability

1%

Operating temperature

-20C to +70C

Dielectric test

2500V, 50Hz

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,


EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure material

Polycarbonate. Flame retardant

Weight

0.5kg

Dimensions

70 x 100 x 115mm (H x W x D)

Installation

35mm DIN rail or 4mm (3/16) screws

The specifications are subject to change without notice.

Type Selection Table


Standard types: I N = 5A

Type

Main office:
SELCO A/S
Betonvej 10
DK-4000 Roskilde
Denmark
Phone: + 45 7026 1122
Fax:
+ 45 7026 2522
e-mail: [email protected]
www.selco.com

IN

Supply

T2000.0010 230V

5A

L-N

T2000.0020 450V

400V

5A

L-L

T2000.0030 127V

120V

5A

L-N

T2000.0040 110V

100V

5A

L-L

T2000.0050 110V

100V

5A

L-L

T2000.0060 230V

1A

L-N

T2000.0070 660V

5A

L-L

T2000.0080 450V

400V

5A

L-N

T2000.0090 127V

120V

5A

L-L

T2000.0100 110V

100V

1A

L-L

T2000.0110 450V

400V

5A

L-L

T2000.0120 480V

415V

5A

L-L

T2000.0130 230V

5A

L-N

T2000.0140 230V

5A

L-L

T2000.0150 480V

415V

1A

L-L

T2000.0160 450V

400V

1A

L-L

Function

No time delay

Delay 0.2 - 2.0 sec.

No time delay
No time delay

Other supply voltages and combinations are available on request.

T2095-51 E