Slabs Concrete
Slabs Concrete
3. Slabs
R M Moss BSc, PhD, DIC, CEng, MICE, MIStructE O Brooker BEng, CEng, MICE, MIStructE
Designing to Eurocode 2
This chapter covers the analysis and design of slabs to Eurocode 21 which is
essentially the same as with BS 81102. However, the layout and content of
Eurocode 2 may appear unusual to designers familiar with BS 8110. Eurocode 2
does not contain the derived formulae or specific guidance on determining
moments and shear forces. This has arisen because it has been European
practice to give principles in the codes and for the detailed application to
be presented in other sources such as textbooks.
Chapter 1, originally published as Introduction to Eurocodes3, highlighted the
key differences between Eurocode 2 and BS 8110, including terminology.
Chapter 7, originally published as Flat slabs4 covers the design of flat slabs.
It should be noted that values from the UK National Annex (NA) have been
used throughout, including values that are embedded in derived formulae.
(Derivations can be found at www.eurocode2.info.) A list of symbols related to
slab design is given at the end of this chapter.
Design procedure
A procedure for carrying out the detailed design of slabs is shown in Table 1.
This assumes that the slab thickness has previously been determined during
conceptual design. More detailed advice on determining design life, actions,
material properties, methods of analysis, minimum concrete cover for
durability and control of crack widths can be found in Chapter 2, originally
published as Getting started 5.
Fire resistance
:cementZg]concretebg]nlmkrin[eb\Zmbhg
Ahpmh=^lb`g<hg\k^m^
Lmkn\mnk^lnlbg`>nkh\h]^+
A J Bond F:FL\=B<Ia=FB<><>g`
O Brooker ;>g`<>g`FB<>FBLmkn\m>
A J Harris ;L\FL\=B<FB<><>g`?@L
T Harrison ;L\Ia=<>g`FB<>?B<M
R M Moss;L\Ia==B<<>g`FB<>FBLmkn\m>
R S Narayanan?K>g`
R Webster<>g`?BLmkn\m>
Further guidance
Chapter in this publication
Standard
2: Getting started
2: Getting started
1: Introduction to Eurocodes
2: Getting started
NA to BS EN 199211
2: Getting started
BS EN 199211 Cl 4.4.1
BS EN 199211 section 5
See Figure 1
10
Check deflection
See Figure 3
11
See Table 7
12
2: Getting started
BS 8500: 2002
Note
NA = National Annex.
Table 2
Minimum dimensions and axis distances for reinforced concrete slabs (excluding flat slabs)
Standard fire
resistance
REI 60
REI 90
REI 120
REI 240
1.5 <l y /l x 2f
hs =
80
80
80
b min =
a=
20
10 g
15g
a=
hs =
100
a=
30
hs =
120
120
120
a=
40
20
25
hs =
175
175
175
a=
65
40
50
100
15g
100
20
25
b min =
a=
b min =
a=
b min =
a=
100
120
15g
200
10g
120
160
250
35
25
15g
160
190
300
45
40
30
450
700
70
60
Notes
Key
1 This table is taken from BS EN 199212 Tables 5.8 to 5.11. For flat slabs refer to
Chapter 7.
a The slab thickness hs is the sum of the slab thickness and the thickness of any
non-combustible flooring.
2 The table is valid only if the detailing requirements (see note 3) are observed and in
normal temperature design redistribution of bending moments does not exceed 15%.
3 For fire resistance of R90 and above, for a distance of 0.3l eff from the centre line of each
intermediate support, the area of top reinforcement should not be less than the following:
A s,req (x) = A s,req ( 0 ) ( 1 2.5 ( x/ l eff ) )
where:
x
A s,req ( 0 )
A s,req (x)
l eff
4 There are three standard fire exposure conditions that need to be satisfied:
R
E
I
5 The ribs in a one-way spanning ribbed slab can be treated as beams and reference can
be made to Chapter 4, Beams. The topping can be treated as a two-way slab where
1.5 < ly / lx 2.
2
18
3. Slabs
Figure 1
Flexure
No
Concrete class
C50/60?
Outside scope of
this publication
Yes
Determine K from: K =
M
bd 2 fck
Table 4
Values for K
% redistribution
Compression
reinforcement
required not
recommended for
typical slabs
No
Is K K ?
Yes
No compression reinforcement required
d (redistribution ratio) K
1.00
0.208a
10
0.90
0.182a
15
0.85
0.168
20
0.80
0.153
25
0.75
0.137
30
0.70
0.120
Key
a It is often recomended in the UK that K should be limited to 0.168 to ensure ductile failure.
Table 5
0.26 fctm bt d
fyk
where fck 25
z/d
z/d
0.05
0.950a
0.13
0.868
0.06
0.944
0.14
0.856
0.07
0.934
0.15
0.843
0.08
0.924
0.16
0.830
0.09
0.913
0.17
0.816
0.10
0.902
0.18
0.802
0.11
0.891
0.19
0.787
0.12
0.880
0.20
0.771
Key
a Limiting z to 0.95d is not a requirement of Eurocode 2, but is considered to be good practice.
Table 6
Minimum percentage of reinforcement required
Table 3
fck
fctm
25
2.6
0.13%
28
2.8
0.14%
30
2.9
0.15%
32
3.0
0.16%
35
3.2
0.17%
40
3.5
0.18%
Notes
1 Applicable to one-way spanning slabs where the area of each bay exceeds 30 m2,
Qk 1.25 Gk and qk 5 kN/m2
2 F is the total design ultimate load, l is the span
3 Minimum span > 0.85 longest span, minimum 3 spans
4 Based on 20% redistribution at supports and no decrease in span moments
45
3.8
0.20%
50
4.1
0.21%
First
Interior Interior
interior spans supports
support
Key
a Where fyk = 500 MPa.
3
19
Deflection
Eurocode 2 has two alternative methods of designing for deflection,
either by limiting span-to-depth ratio or by assessing the theoretical
deflection using the Expressions given in the Eurocode. The latter
is dealt with in detail in Chapter 8, originally published as Deflection
calculations7.
The span-to-depth ratios should ensure that deflection is limited to
span /250 and this is the procedure presented in Figure 3.
Figure 2
Simplified rectangular stress block for concrete up to class C50/60 from Eurocode 2
Figure 3
Figure 4
START
Determine basic l/d from Figure 5
Increase
As,prov
was the intention of the drafting committee and is in line with current UK practice.
4
20
)( )
3. Slabs
Two-way slabs
Unlike BS 8110 there is no specific guidance given in Eurocode 2 on
how to determine the bending moments for a two-way slab. The
assessment of the bending moment can be carried out using any
suitable method from Section 5 of the Code. However, co-efficients
may be obtained from Table 8 (taken from the Manual for the design of
building structures to Eurocode 29) to determine bending moments per
unit width (Msx and Msy) where:
Table 7
vRd,c resistance of members without shear reinforcement, MPa
rI =
As /(bd)
0.25% 0.54 0.52 0.50 0.48 0.47 0.45 0.43 0.41 0.40 0.38 0.36
0.50% 0.59 0.57 0.56 0.55 0.54 0.52 0.51 0.49 0.48 0.47 0.45
0.75% 0.68 0.66 0.64 0.63 0.62 0.59 0.58 0.56 0.55 0.53 0.51
1.00% 0.75 0.72 0.71 0.69 0.68 0.65 0.64 0.62 0.61 0.59 0.57
1.25% 0.80 0.78 0.76 0.74 0.73 0.71 0.69 0.67 0.66 0.63 0.61
1.50% 0.85 0.83 0.81 0.79 0.78 0.75 0.73 0.71 0.70 0.67 0.65
1.75% 0.90 0.87 0.85 0.83 0.82 0.79 0.77 0.75 0.73 0.71 0.68
2.00% 0.94 0.91 0.89 0.87 0.85 0.82 0.80 0.78 0.77 0.74 0.71
k
2.000 1.943 1.894 1.853 1.816 1.756 1.707 1.667 1.632 1.577 1.516
Table derived from: v Rd,c = 0.12 k (100r I fck)1/3 0.035 k1.5 fck 0.5
where k = 1 + R(200/d) 2 and r I = As /(bd) 0.02
Note
Msy = b sy w lx2
Where bsx and bsy are coefficients, lx is the shorter span and w (load
per unit area) is the STR ultimate limit state combination. For more
information on combinations refer toChapter 1, originally published as
Introduction to Eurocodes3.
fck
25
28
32
35
40
45
50
Factor
0.94
0.98
1.02
1.05
1.10
1.14
1.19
Figure 5
Basic span-to-effective-depth ratios
Notes
1 For two-way spanning slabs, the check should be
carried out on the basis of the shorter span.
2 This graph assumes simply supported span
condition (K = 1.0).
K = 1.5 for interior span condition
K = 1.3 for end span condition
K = 0.4 for cantilevers
3 Compression reinforcement, r, has been taken as 0.
4 Curves based on the following expressions:
l
1.5 fck r 0
+ 3.2
= K 11 +
r
d
fck
( )]
1.5
r0
1
r
where r r 0
and
l
1.5 fck r 0
+
= K 11 +
d
( r r )
fck
12
r
r0
where r > r 0 .
5
21
Figure 6
Procedure for determining flexural capacity of flanged ribs
Current practices for determining forces in ribbed and waffle slabs may also
be used for designs to Eurocode 2. Where a waffle slab is treated as a
two-way slab refer to previous section, but note that their torsional stiffness
is significantly less than for a two-way slab and the bending moment coefficients may not be applicable. Where it is treated as a flat slab reference
may be made to Chapter 7, originally published as Flat slabs4
The position of the neutral axis in the rib should be determined, and
then the area of reinforcement can be calculated depending on
whether it lies in the flange or web (see flow chart in Figure 6). The
main differences compared with BS 8110 are that the assessment of
the flange width is more sophisticated (see Figures 7 and 8).
Where a slab is formed with permanent blocks or a with a topping
thickness less than 50 mm and one-tenth of the clear distance
between ribs it is recommended that a longitudinal shear check is
carried out to determine whether additional transverse reinforcement is
required (see BS EN 199211, Cl 6.2.4).
Table 8
Bending moment coefficients for two-way spanning rectangular slabs
supported by beams
Type or panel
and moments
considered
1.0
1.25
1.5
1.75
Long-span
coefficients
for all values
of ly /lx
START
No
Concrete class
C50/60?
Outside scope
of this
publication
Yes
Determine l0 (see Figure 7) and beff from:
beff = (bw + beff1 + beff2) where
beff1 = (0.2b1 + 0.1 l0) 0.2 l0 b1
beff2 = (0.2b2 + 0.1 l0) 0.2 l0 b2
Note: The flange width at the support will be
different from that at mid-span.
For symbols refer to Figures 7 and 8
Determine K from: K =
M
bd 2 fck
2.0
Calculate depth to neutral axis x from:
Interior panels
x = 2.5 (d z)
Negative moment
at continuous edge
0.031
0.044 0.053
0.059 0.063
0.032
Positive moment
at midspan
0.024
0.034 0.040
0.044 0.048
0.024
Yes
Is x 1.25hf
Neutral axis in
flange.
Design as
rectangular
section.
No
Negative moment
at continuous edge
0.039
Positive moment
at midspan
0.029
0.050 0.058
0.063 0.067
0.037
Neutral axis in web
Calculate moment capacity of flange from:
0.038 0.043
0.047 0.050
0.028
and
0.039
0.059 0.073
0.083 0.089
0.037
Positive moment
at midspan
0.030
0.045 0.055
0.062 0.067
0.028
Kf =
M MR,f
fck bw d 2
Is Kf K
No
Yes
0.047
0.066 0.078
0.087 0.093
0.045
Positive moment
at midspan
0.036
0.049 0.059
0.065 0.070
0.034
6
22
Redesign
section
3. Slabs
Figure 7
Figure 8
Selected symbols
Symbol
Definition
Value
Ac
bh
As
As2
As, prov
As, reqd
beff
bt
bmin
bw
Effective depth
d2
fcd
fck
fctm
hf
Flange thickness
hs
Slab thickness
leff
The minimum clear distance between bars should be the greater of:
Bar diameter
Aggregate size plus 5 mm
20 mm
l0
l/d
lx, ly
(d z)/0.4
xmax
Lever arm
a cc
gm
r0
Rfck /1000
As/bd
As2/bd
7
23
3. Slabs
References
1 BRITISH STANDARDS INSTITUTION. BS EN 199211: Eurocode 2: Design of concrete structures Part 11 General rules and rules for buildings. BSI, 2004.
2 BRITISH STANDARDS INSTITUTION. BS 81101: The structural use of concrete Part 1, Code of practice for design and construction. BSI, 1997.
3 NARAYANAN, R S & BROOKER, O. How to design concrete structures using Eurocode 2: Introduction to Eurocodes. The Concrete Centre, 2005.
4 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Flat slabs. The Concrete Centre, 2006.
5 BROOKER, O. How to design concrete structures using Eurocode 2: Getting started. The Concrete Centre, 2005.
6 BRITISH STANDARDS INSTITUTION. BS EN 199212, Eurocode 2: Design of concrete structures. General rules structural fire design, BSI 2004.
7 WEBSTER, R & BROOKER, O. How to design concrete structures using Eurocode 2: Deflection calculations. The Concrete Centre, 2006.
8 MOSS, R M & BROOKER, O. How to design concrete structures using Eurocode 2: Beams. The Concrete Centre, 2006.
9 THE INSTITUTION OF STRUCTURAL ENGINEERS/THE INSTITUTION OF CIVIL ENGINEERS. Manual for the design of concrete building structures to
Eurocode 2. IStructE/ICE, 2006.
Acknowledgements
The content of this publication was produced as part of the project Eurocode 2: transition from UK to European concrete design standards. This
project was part funded by the DTI under the Partners in Innovation scheme. The lead partner was the British Cement Association. The work was
carried out under the guidance of the Concrete Industry Eurocode 2 Group, which consists of representatives from:
Alan Baxter and Associates Arup British Cement Association British Precast Building Research Establishment Clark Smith Partnership
Concrete Innovation and Design Construct Department for Trade and Industry Office of the Deputy Prime Minister The Concrete Centre
The Concrete Society Quarry Products Association.
Ref: TCC/03/18
ISBN 1-904818-28-5
24 published January 2006, revised December 2006
First
The Concrete Centre and British Cement Association
All advice or information from The Concrete Centre is intended for those who will evaluate the significance and limitations of its contents
and take responsibility for its use and application. No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by The Concrete Centre or its subcontractors, suppliers or advisors. Readers should note that publications from
The Concrete Centre are subject to revision from time to time and they should therefore ensure that they are in possession of the
latest version. This publication has been produced following a contract placed by the Department for Trade and Industry (DTI); the
views expressed are not necessarily those of the DTI.