0% found this document useful (0 votes)
78 views9 pages

Report File On PLCC at Jaipur2

PLCC is used for telemetry and telecontrol in power systems, transmitting data over power lines using carrier frequencies between 30-500 kHz. It allows for remote transmission of data as well as protection of transmission lines. Key components of a PLCC system include transmitters and receivers, hybrids and filters, line tuners, coupling capacitors, and protection equipment to handle over voltages. The goal of PLCC is reliable transmission of data for carrier protection relaying, communication between stations, and telemetry of electrical quantities over long distances.

Uploaded by

reetujvvnl
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views9 pages

Report File On PLCC at Jaipur2

PLCC is used for telemetry and telecontrol in power systems, transmitting data over power lines using carrier frequencies between 30-500 kHz. It allows for remote transmission of data as well as protection of transmission lines. Key components of a PLCC system include transmitters and receivers, hybrids and filters, line tuners, coupling capacitors, and protection equipment to handle over voltages. The goal of PLCC is reliable transmission of data for carrier protection relaying, communication between stations, and telemetry of electrical quantities over long distances.

Uploaded by

reetujvvnl
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 9

Use of PLCC in modern electrical power system is mainly for telemetry and telecontrol.

Tele
means remote. Telemetry refers to science of measurement from remote location.
Different types of data transmission system can be used depending upon the network requirement
and conditions.
Main data transmission system for telemetry and telecontrol are:
1. Use of telephone lines
2. Use of separate cables
3. Power Line carrier communication
4. Radio wave micro wave channel

PLCC Panel Block Diagram

For large power system power line carrier communication is used for data transmission as well as
protection of transmission lines. Carrier current has a frequency range of 30 to 200 kHz in
USA and 80 to 500 kHz in UK.
Each end of transmission line is provided with identical PLCC equipment consisting of
equipment:
1. Transmitters and Receivers
2. Hybrids and Filters
3. Line Tuners
4. Line Traps
5. Power amplifier
6. Coupling capacitors
Distance protection relay in relay panel at one end of the transmission line gets the input from
CT and CVT in line. The output of relay goes to modem of PLCC.

PLCC scheme

The output of PLCC goes to coupling capacitor and then to transmission line and travels to
another end where it is received through coupling capacitor and inputted to relay and control panel
at that end.
Go to Content

Major goal/Application of PLCC


PLCC in modern electrical power system substation is mainly used for following purpose:
1. Carrier protection relaying of transmission line so that:
1. Inter trip command can be issued by relay due to tripping of circuit breaker at any one
end.
2. To trip the line circuit breaker nearest to the fault, this is done by:
a) Distance protection relay (V/I characteristics)
b) Differential comparison method
c) Phase comparison method
2. Station to station communication between operating personnel
3. Carrier telemetring, electrical quantities that are telemetered are kW, kVA, kVAR,
Voltage and Power factor etc.
Following methods are used for telemetring as well as telecontrol:
0. Simplex

1. Duplex
2. Multiplex
3. Time division Multiplex
Many factors will affect the reliability of a power line carrier (PLC) channel.
The goal is to get a signal level to the remote terminal that is above the sensitivity of the receiver,
and with a signal-to-noise ratio (SNR) well above the minimum, so that the receiver can make a
correct decision based on the information transmitted.
If both of these requirements are met then the PLC channel will be reliable.
The factors affecting reliability are:
1. The amount of power out of the transmitter.
2. The type and number of hybrids required to parallel transmitters and receivers.
3. The type of line tuner applied.
4. The size of the coupling capacitor in terms of capacitance.
5. The type and size, in terms of inductance, of the line trap used.
6. The power line voltage and the physical configuration of the power line.
7. The phase(s) to which the PLC signal is coupled.
8. The length of the circuit and transpositions in the circuit.
9. The decoupling equipment at the receiving terminal (usually the same as the transmitting
end).
10. The type of modulation used to transmit the information, and the type of demodulation
circuits in the receiver.
11. The received signal-to-noise ratio (SNR).
The above list may not be all inclusive, but these are the major factors involved in the success or
failure of a PLC channel.
Go to Content

Main Components of PLCC


1. Coupling Capacitor

PLCC component - Coupling Capacitor

Coupling capacitor connects the carrier equipment to the transmission line. The coupling
capacitors capacitance is of such a value that it offers low impedance to carrier
frequency (1/C) but high impedance to power frequency (50 Hz).
For example 2000pF capacitor offers 1.5M to 50Hz but 150 to 500kHz.
Thus coupling capacitor allows carrier frequency signal to enter the carrier equipment.
To decrease the impedance further and make the circuit purely resistive so that there is no
reactive power in the circuit, low impedance is connected in series with coupling capacitor to form
resonance at carrier frequency.
Go to Content

2. Line trap Unit


The carrier energy on the transmission line must be directed toward the remote line terminal and
not toward the station bus and it must be isolated from bus impedance variations. This task is
performed by the line trap.
The line trap is usually a form of a parallel resonant circuit which is tuned to the carrier energy
frequency.
A parallel resonant circuit has high impedance at its tuned frequency, and it then causes most of
the carrier energy to flow toward the remote line terminal. The coil of the line trap provides a low
impedance path for the flow of the power frequency energy.
Since the power flow is rather large at times, the coil used in a line trap must be large in terms of
physical size.

Hence a line trap unit/Wave trap is inserted between busbar and connection of coupling capacitor
to the line. It is a parallel tuned circuit comprising of inductance (L) and capacitance (C). It has low
impedance (less than 0.1?) for power frequency (50 Hz) and high impedance to carrier frequency.
This unit prevents the high frequency carrier signal from entering the neighboring line.
Go to Content

3. Transmitters and Receivers


The carrier transmitters and receivers are usually mounted in a rack or cabinet in the control
house, and the line tuner is out in the switchyard.
This then means there is a large distance between the equipment and the tuner, and the
connection between the two is made using a coaxial cable.

PLCC component - Transmitters and receivers

The coaxial cable provides shielding so that noise cannot get into the cable and cause
interference. The coaxial cable is connected to the line tuner which must be mounted at the base
of the coupling capacitor.
If there is more than one transmitter involved per terminal the signal must go through isolation
circuits, typically hybrids, before connection to the line tuner.
Go to Content

4. Hybrids and Filters

The purpose of the hybrid circuits is to enable the connection of two or more transmitters together
on one coaxial cable without causing intermodulation distortion due to the signal from one
transmitter affecting the output stages of the other transmitter. Hybrids may also be required
between transmitters and receivers, depending on the application.
The hybrid circuits can, of course, cause large losses in the carrier path and must be used
appropriately. High/low-pass and band-pass networks may also be used, in some applications, to
isolate carrier equipment from each other.

5. Line Tuners
The purpose of the line tuner in conjunction with the coupling capacitor is to provide low
impedance path for the carrier energy to the transmission line and a high impedance path to the
power frequency energy.
The line tuner/coupling capacitor combination provides a low impedance path to the power line by
forming a series resonant circuit tuned to the carrier frequency.
On the other hand, the capacitance of the coupling capacitor is high impedance to the power
frequency energy. Even though the coupling capacitor has high impedance at power frequencies,
there must be a path to ground in order that the capacitor may do its job. This function is provided
by the drain coil, which is in the base of the coupling capacitor. The drain coil is designed to be low
impedance at the power frequency and because of its inductance it will have high impedance to
the carrier frequency.
Thus the combination of the line tuner, coupling capacitor, and the drain coil provide the necessary
tools for coupling the carrier energy to the transmission line and blocking the power frequency
energy. One last function of the line tuner is to provide matching of impedance between the carrier
coaxial cable, usually 50 to 75 ohms, and the power line which will have an impedance of 150 to
500 ohms.
Go to Content

6. Master Oscillator and Amplifiers


High frequency carrier signal is generated in oscillator.
Oscillator can be crystal oscillator with which operation for a particular bandwidth can be achieved.
The output voltage of a oscillator is held constant by voltage stabilizer.

The output of oscillator is fed to amplifier so that loses in transmission can be compensated.
Losses occurring in carrier current is termed as attenuation of carrier signal.
They are mainly: Losses in coupling equipment which are constant losses for a given carrier
frequency bandwidth.

PLCC component - Master oscillator and amplifiers

Line losses vary with length line, size of line, weather condition etcThese losses for
underground line is more than overhead line.
Frequency spacing is a process using different carrier frequency in two adjacent transmission
lines. Wave trap/Line trap help in accomplishing this.
Go to Content

7. Protection and earthing of coupling equipment


Over voltage can be caused due to lightning, switching and sudden loss of load etc.
They produce stress on coupling equipment and line trap units. Non linier resistor in series
with protective gap is connected across the line trap unit and inductor of coupling unit.
The gap is adjusted to spark at a set value of over voltage.

Protection and earthing of coupling equipment

Coupling unit and PLCC equipment are earthed through a separate and dedicated system, so
that ground potential rise of station earthing system does not affect the reference voltage
level/Power supply common ground of the PLCC equipment.
In this regard that is earthing of PLCC and other communication/Instrumentation/Electronic
equipment please refer to NEC Article 645 for data centers (IT equipment.)
Top

Advantages of Digital PLCC over Analog ones


1.
2.
3.
4.
5.

Immune to noise in processing and storage stages, as it is completely digital.


Digital: Require less no. of circuits (hardware), since Digital Processor is a single chip.
Processing is accurate and reliable.
Frequency conversion is done in a single step (Digital Conversion).
Digital processing allows the application of a wide range of mathematics. (Analog
processing is limited by the availability of devices to perform desired functions, while)
6. Equalization is perfect: High-resolution digital filtering gives very flat filter response as
desired.
7. The performance of digital circuits, opposed to analog, is relatively independent of actual
component values in the implementing circuit. Therefore, digital systems more reliably
reproduce the desired responses in spite of temperature variations or component aging.
8. In addition, in digital circuits there is little need for component matching.
9. Simplified Production: Lower Parts count and improved testability.
Power Line Carrier (PLC) Signal propagation along high voltage lines depends entirely on the
construction of transmission lines, mainly on the configuration and characteristics of all conductors
and on the ground resistance optimum coupling allows to make the best use of a given
transmission line.

Transposition may introduce additional attenuation which can generally not be predicted with
simple rules. Most transposition schemes result in high attenuation poles at certain frequencies
such frequencies cannot be used for PLC communications.
Forbidden Frequency Ranges may be determined as explained in CIGRE Paper 35-02, Senn/Morf
Optimum PLC Arrangement on Transposed Single Circuit power Lines (August, 1984)
In critical cases, however, computer calculation may be necessary, for which the following
data is required:
1. Height of each conductor above ground (at the towers)
2. Sag of conductors (between towers)
3. Horizontal distance (between conductors)
4. Number of conductors per phase (single or if bundle spacing)
5. Outer diameter of conductors, material of conductors
6. Number of strands at the circumference (outer strands)
7. Diameter of strands
8. Same information (a) to (g) for ground wires
9. Total length of transmission line
10. Sketch of phasing arrangement showing type and number of transpositions and distance
between transpositions (if double system, each scheme required separately)
11. Earth resistivity in Ohm meters, if not known, state whether around 300 or 1000 or 3000
communication separately.
12. Coupling arrangement (phase to ground of phase to phase)
13. Available carrier frequency range

You might also like