1SDC200034M0201
1SDC200034M0201
1SDC200034M0201
1 oct 2004
Introduction ....................................................................................................................... 1
Wiring diagrams ................................................................................................................ 1
ATS010 unit Power Supply ............................................................................................... 1
Circuit Breakers accessories............................................................................................. 2
Auxiliary components ........................................................................................................ 4
Introduction
ATS010 is an electronic Automatic Transfer Unit, which is employed together with ABB
SACE Low Voltage Circuit breakers.
This documents provides application information for ATS010:
- wiring diagrams according to the type of circuit breaker
- power requirements for the electronic unit
- required accessories for the circuit breakers
- required additional devices (auxiliary devices)
Wiring diagrams
Wiring diagrams for ATS010 are published on the ABB Library as:
ITSCE-RM0020001
ITSCE-RM0021001
ITSCE-RM0022001
1SDM000033R0001
ABB SACE
1 oct 2004
Isomax S3-S4-S5
Isomax S6-S7
Tmax T4-T5
Isomax S3-S4-S5
Isomax S6-S7
Tmax T4-T5
ABB SACE
1 oct 2004
The following supply voltages can be used for the motor operator and opening/closing
releases:
Emax
24V DC
48V DC
60V DC
110V DC (*)
24V AC
30V AC
48V AC
60V AC
110V..127V AC
220V..250V AC
Isomax S3-S4-S5
24V DC
48V DC
60V DC
110V DC(*)
100V...127V AC
220V...250V AC
Isomax S6-S7
24V DC
48V DC
60V DC
110V DC (*)
110V AC
120V...127V AC
220V...250V AC
Tmax T4-T5
24V DC
48V DC (*)
60V DC (*)
110V DC (*)
24V AC
48V...60V AC
110V...125V AC
220V...250V AC
(*) Only listed values are allowed. Do not use other supply
voltages (e.g., 54V DC, 100V DC, 120V DC).
ABB SACE
1 oct 2004
Auxiliary components
The following auxiliary components are employed, as shown in the wiring diagrams:
- Q61/1, Q61/2 protection devices
- K1, K2 contactors
- KC1, KC2, KO1, KO2 contactors
<= 10 kA
<= 15 kA
ABB SACE
1 oct 2004
<= 50 kA
> 50 kA (**)
(**) NOTE: if allowed by application, 6A fuses gG6 can be used for lower short-circuit current too
K1, K2 contactors
These interlocked contactors are used only if application is Without safety auxiliary
voltage.
Their purpose is to switch power supply to the motor operators or opening/closing coils
of the circuit breakers between Normal and Emergency power supply.
ABB Code
110V...127V AC
VB6-30-01 110V...127VAC
220V...250V AC
VB6-30-01 220V...250VAC
ABB Code
Emax
Isomax S6-S7
Tmax T4-T5
24V DC
48V DC
60V DC
110V..125VDC
BC6-30-10-1.4 24VDC
BC6-30-10-1.4 48VDC
BC6-30-10-1.4 60VDC
BC6-30-10-1.4 110VDC
Isomax S3-S4-S5
24VDC
48VDC
60VDC
110..125VDC
BC6-22-00 24VDC
BC6-22-00 48VDC
BC6-22-00 60VDC
BC6-22-00 110..125VDC
ABB SACE
1 oct 2004