Selection Information H-And J-Frame Thermal-Magnetic Molded Case 150 and 250 Ampere Frame-Class 611
Selection Information H-And J-Frame Thermal-Magnetic Molded Case 150 and 250 Ampere Frame-Class 611
Selection Information H-And J-Frame Thermal-Magnetic Molded Case 150 and 250 Ampere Frame-Class 611
www.SquareD.com
For the most up-to-date information
150 A H-frame
250 A J-frame
HD
HG
HJ
HL
JD
JG
JJ
JL
Number of Poles
2,3
2,3
2,3b
2,3b
2,3b
2,3b
2,3b
2,3b
15150 A
15150 A
15150 A
15150 A
150250 A
150250 A
150250 A
150250 A
240 V
25
65
100
125
25
65
100
125
480Y/277 Vac
18
35
65
100
18
35
65
100
480 Vac
18
35
65
100
18
35
65
100
600Y/347 Vac
14
18
25
50
14
18
25
50
600 Vac
14
18
25
50
14
18
25
50
125/250 Vdc
20
20
20
20
20
20
20
20
500 Vdc
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
220/240 Vac
25/25
65/65
100/100
125/125
25/25
65/65
100/100
125/125
380/415 Vac
18/18
35/35
65/65
100/100
18/18
35/35
65/65
100/100
500/525 Vac
14/14
18/18
25/25
50/50
14/14
18/18
25/25
50/50
Unit Mount
I-Line
Rear Connection
Drawout
Optional Lugs
Shunt Trip
Undervoltage Trip
Auxiliary Switches
Alarm Switch
Motor Operator
Handle Operators
Optional GF Protection
...
...
...
...
...
...
...
...
Current Range
DC
Ratings
IEC 947-2
Icu/Ics
UL/
CSA/
NOM
50/60 Hz
Special Ratings
Connections/Terminations
Unit Mount
Instantaneous-only (MCP)
...
...
...
...
...
...
...
...
Electronic
...
...
...
...
...
...
...
...
Dimensions
Dimensions
(3P Unit
Mount)
Height IN (mm)
6.4 (163)
7.5 (191)
Width IN (mm)
4.1 (104)
4.1 (104)
Depth IN (mm)
3.4 (86)
3.4 (86)
CIRCUIT BREAKERS
Interrupting Ratings
6-55