Ground Floor Load Schedule & Computations

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

GROUND FLOOR LOAD SCHEDULE & COMPUTATIONS:

BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
LIGHTING LOAD
3
SMALL APP.
4
SMALL APP.
5
AIRCON
3 HP
6
AIRCON 1.5 HP
7
REFREGERATOR
8
SPARE
9
SPARE
10
TOTAL
COMPUTATIONS
I =

BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
SMALL APP.
4
AIRCON 1HP
5
AIRCON 1HP
6
SPARE
7
SPARE
8
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
22
12
18
6
7
1
1
2
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
230
230
230
230
-----

2200
1200
1800
2160
2520
2238
1119
3000
----16237

9.57
5.22
7.83
9.39
10.96
9.73
4.87
13.04348
-----

1
1
1
1
1
1
1
1
-----

[16237+(25% x 3000)]x 0.8 D.F.


230

NO.
OUTLET
23
22
14
12
6
6
-----

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

WATTS

AMPERES

PHASE

230
230
230
230
230
230
-----

2300
2200
5040
4320
4476
4476
----22812

10.00
9.57
21.91
18.78
19.46
19.46
-----

1
1
1
1
1
1
-----

83.24

Amp

PROTECTION

15 AT
15 AT
15 AT
20 AT
20 AT
30 AT
30 AT
20 AT
-----

USE 2 # 38 mm TW 100 AT

59.09 Amp

VOLTS

[22812+(25% x 4476)] x 0.8 D.F.


230

SIZE OF WIRE &


CONDUIT

SIZE OF WIRE &


CONDUIT
2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

PROTECTION

15 AT
15 AT
30 AT
30 AT
30 AT
30 AT
-----

USE 2 # 50 mm TW 120AT

3RD FLOOR LOAD SCHEDULE & COMPUTATIONS:


BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
SMALL APP.
4
AIRCON 1HP
5
AIRCON 1HP
6
SPARE
7
SPARE
8
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
23
22
14
12
6
6
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
230
230
-----

2300
2200
5040
4320
4476
4476
----22812

10.00
9.57
21.91
18.78
19.46
19.46
-----

1
1
1
1
1
1
-----

[22812+(25% x 4476)] x 0.8 D.F.


230

SIZE OF WIRE &


CONDUIT

PROTECTION

15 AT
15 AT
30 AT
30 AT
30 AT
30 AT
-----

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

-----

USE 2 # 50 mm TW 120 AT

= 83.24 Amp

ROOF TOP FLOOR LOAD SCHEDULE & COMPUTATIONS:


BRANCH
LOAD DESCRIPTION
CKT. NO
LIGHTING LOAD
1
LIGHTING LOAD
2
SMALL APP.
3
WATER PUMP 1.5 HP
4
SPARE
5
SPARE
6
TOTAL
COMPUTATIONS
I =

NO.
OUTLET
12
11
2
1
-----

VOLTS

WATTS

AMPERES

PHASE

230
230
230
230
-----

1200
1100
720
1119
----4139

5.22
4.78
3.13
4.87
-----

1
1
1
1
-----

[4139+(25% x 1119)] x 0.8 D.F.


230

= 15.37 Amp

SIZE OF WIRE &


CONDUIT

PROTECTION

2 # 2.0 mm TW in 13 mm C
2 # 2.0 mm TW in 13 mm C
2 # 3.5 mm TW in 13mm C
2 # 3.5 mm TW in 13mm C

----USE 2 # 8.0 mm TW 30 AT

15 AT
15 AT
20 AT
30 AT
-----