CPG Power System Maintenance
CPG Power System Maintenance
CPG Power System Maintenance
Advantageyour
single source for preventative power system main-
tenance. PowerCare Advantage provides proactive
maintenance, 24-hour emergency service, consolidated
billing and online management reportingall from one
source.
Power system maintenance program
A well-planned maintenance program is essential to the
operation of any power generation system. Cummins
Power Generation offers planned maintenance
agreements on all makes and models of generators
regardless of the manufacturer. For customers with
fewer than ten generator sets and customers outside
the U.S. and Canada, local Cummins distributors
About the author
Timothy A. Loehlein is a graduate of the
University of Minnesota with a Bachelor
of Electrical Engineering and a PE in
Minnesota. Tim has been a Cummins
Power Generation employee since 1976
in positions as Application Engineer,
Power topic #7004 | Page 4
www.cumminspower.com
2007 | Cummins Power Generation and Cummins are registered
trademarks of Cummins Inc. Our energy working for you. is a
trademark of Cummins Power Generation.
PT-7004 (04/07) Formerly PT-302
ow goes up, and the only accurate measure of
terminal voltage must be done under load. This test
is performed automatically every time the generator
is started on Cummins Power Generation generator
sets equipped with PowerCommand
. On other
generators, use a manual battery load tester to
verify the condition of each starting battery.
Cleaning batteries: Keep the batteries clean
by wiping them with a damp cloth whenever dirt
appears excessive. If corrosion is present around
the terminals, remove the battery cables and wash
the terminals with a solution of baking soda and
water (1/4-pound baking soda to one quart of water).
Be careful to prevent the solution from entering the
battery cells, and ush the batteries with clean water
when done. After replacing the connections, coat
the terminals with a light application of petroleum
jelly.
Checking specific gravity: Use a battery
hydrometer to check the specic gravity of the
electrolyte in each battery cell. A fully charged
battery will have a specic gravity of 1.260. Charge
the battery if the specic gravity reading is below
1.215.
Checking electrolyte level: Check the level of the
electrolyte in the batteries at least every 200 hours
of operation. If low, ll the battery cells to the bottom
of the ller neck with distilled water.
Generator set exercise
Generator sets on continuous standby must be able
to go from a cold start to being fully operational in a
matter of seconds. This can impose a severe burden
on engine parts. However, regular exercising keeps
engine parts lubricated, prevents oxidation of electrical
contacts, uses up fuel before it deteriorates, and, in
general, helps provide reliable engine starting. Exercise
the generator set at least once a month for a minimum
of 30 minutes loaded to no less than one-third of the
nameplate rating. Periods of no-load operation should
be held to a minimum, because unburned fuel tends
to accumulate in the exhaust system. If connecting to
the normal load is not convenient for test purposes, the
best engine performance and longevity will be obtained
by connecting it to a load bank of at least one-third the
nameplate rating.
Conclusion
Preventive maintenance for diesel engine generators
plays a critical role in maximizing reliability, minimizing
repairs and reducing long term costs. By following
generally recognized diesel maintenance procedures
and specic manufacturer recommendations for your
application, youll be assured that your standby power
system will start and run when you need it most.
For additional technical support, please contact your
local Cummins Power Generation distributor. To locate
your distributor, visit www.cumminspower.com.
Design Engineer, Technical Project Leader and Project
Manager. His current position is a Technical Specialist-
Electrical in application engineering for Cummins
Energy Solutions Business, supporting combined heat
and power (CHP) and peaking applications.