fact sheet

GE
Digital Energy
Kelman TRANSPORT X* portable DGA
(Dissolved Gas Analysis) and moisture in oil
Product Overview
Accurate knowledge of the condition of transformers is
essential for all electrical networks. This information allows
valuable asset capabilities to be maximised and expensive
failures to be avoided.
Dissolved Gas Analysis (DGA) is an established technique and
is recognised as the most important test in monitoring power
transformers. It is now being successfully extended to other oil
flled equipment such as tap changers and circuit
breakers.
The TRANSPORT X is a compact, portable DGA system which
is designed to analyse oil samples in the feld and obtain not
only gas level readings but also deliver diagnostics based on
standard rules.
The TRANSPORT X unit has been designed to be very rugged
and user friendly with an emphasis placed on easy feld
operation. The unit is used by over 200 companies and utilities
and has sold in excess of 1000 units worldwide.
Features & Benefts
The TRANSPORT X test uses state of the art infrared
measurement technology to give accurate, reliable results in
a matter of minutes. The TRANSPORT X product represents an
invaluable tool for Asset Management and will increase the
power of any DGA program.
Extensive feld and laboratory use worldwide has proven that
the TRANSPORT X test gives highly reliable results and that it is
genuinely suitable for feld conditions.
The TRANSPORT X equipment minimises the risk of carry-over
between tests. With the ability to go from high gassed samples
(such as tap changers) to subsequent low gassed samples (such
as main tanks) with no contamination of results the user can
confdently test all types of oil flled equipment.
Internal diagnostic software helps to translate ppm data into
valuable information by employing standard DGA interpretation
rules e.g. Duvals triangle, key gas analysis etc.
These established algorithms assist the user to analyse the
condition of the transformer. The accompanying TransportPro
PC software allows the user to download records to a PC
database for export to PERCEPTION* software or Excel.
Accurate & Sensitive
The TRANSPORT X unit has a wide detection range with
excellent accuracy for all seven fault gases.
Moisture Analysis
The unit measures water content in oil. The water concentration
can be expressed as parts per million or relative saturation.
Simple
Easy step-by-step operation. No extensive calibration, set-up or
interpretation of results required.
Fast
On-site results in less than thirty minutes.
No Consumables
The TRANSPORT X unit requires no calibration or carrier gases.
Portable & Rugged
11kg (24lbs) in a rugged convenient carry case.
DGA Diagnostics
Includes DGA diagnostic algorithms - Rogers Ratios, Duvals
Triangle, Japanese ETRA and IEEE

Key gas. Also includes user


settable Caution and Warning thresholds on all gases.
Test Gas Samples
Ability to test gas samples taken from Buchholz Relays.
GE Energy
Lissue Industrial Estate East
Lissue Road
Lisburn BT28 2RE
United Kingdom
+44 (0) 2892622915
www.gedigitalenergy.com
[email protected]

2010 General Electric Company. All rights reserved


* Trademarks of General Electric Company.
IEEE is a registered trademark of the Institute of Electrical Electronics Engineers, Inc.
IEC is a registered trademark of Commission Electrotechnique Internationale.
GEA17279 (08/10)
Additional Features
Records compatible with Kelman PERCEPTION software
from GE Energy and Transformer Oil Analyst (TOA).
Up to 20,000 records stored in internal memory.
Embedded thermal printer gives hard copy of results on-
site.
Touch screen controls for easy operation.
4 popular diagnostic algorithims available on screen for
immediete fault identifcation.
Additional Options
System Check Kit for verifcation of detector operation.
Gas test kit allows analysis of Buchholz gas samples.
Transit Case; Provides extra protection for air travel and
transportation (Rated IP66 when closed).
Sample Cooler; Allows hot oil samples to be cooled for
storage or immediete analysis.
PC Software
Includes TransportPro PC software package to allow storage
and exporting of results.
Kelman PERCEPTION
Complimentary Kelman PERCEPTION software supplied with
each TRANSPORT X for trending & analysis of results.
Technical Specifcations
PARAMETER
(Compound)
VALUE/MEETS
(Measurement Range)
Hydrogen (H
2
) 5 - 5,000 ppm
Carbon Monoxide (CO) 1 - 50,000 ppm
Carbon Dioxide (CO
2
) 2 - 50,000 ppm
Methane (CH
4
) 1 - 50,000 ppm
Acetylene (C
2
H
2
) 0.5 - 50,000 ppm
Ethane (C
2
H
6
) 1 - 50,000 ppm
Ethylene (C
2
H
4
) 1 - 50,000 ppm
Water (H
2
O) 0-100% relative humidity
(Note: Buchholz gas samples LDL is 50 ppm for all gases.
Accuracy is 30% for all gases).
Moisture in Oil Accuracy 3ppm
Measurement Accuracy** 5% or 2 ppm
(whichever is greater)
**Accuracy quoted is the accuracy of the detectors during calibration.
ENVIRONMENTAL
Temperature Range 5 - 40
o
C (41-104F)
Power Supply 115/230 Vac; 50/60Hz; 40 W
Computer Interface USB
Printout Hardcopy 2 Thermal Printer
Weight 11 KG (24 lbs) (unit only)
Size 170 X 340 X 460 mm (unit only)
Oil Sample Volume 50 ml
Gas Sample Volume 5 ml
Conforms To
EMC
Emissions and Immunity Testing Performed According to
EN61326-1:2006.
EN 61326-1: 2006 Radiated Emissions (Class A).
EN 61326-1: 2006 Conducted Emissions (Class A).
EN 61000-3-2: 2000 Steady State and Fluctuating Harmonics.
EN 61000-3-3: 2001 Flicker Testing.
IEC61000-4-2

: 2001 Electrostatic Discharge Immunity Testing.


IEC61000-4-3: 2002 Radiated Immunity.
IEC61000-4-4: 2001 Electrical Fast Transient /Burst Immunity Testing.
IEC61000-4-5: 2001 Surge Immunity Testing.
IEC61000-4-6: 2001 Conducted RF Immunity.
IEC61000-4-8: 2001 Magnetic Field Immunity.
IEC61000-4-11: 2001 Voltage Dips and Interrupts.
Safety
Safety requirements for electrical equipment for measurement, control and laboratory use.
IEC61010-1, EN61010-1, UL61010-1, CAN/CSA-C22.2 No. 61010-1.