The document discusses generator protections, their requirements, and how they are grouped. It provides details on:
- Generators require reliable protections due to their critical role and expensive repairs if damaged.
- Protections are grouped into classes (A, B, C) based on the severity of the fault and appropriate trip response.
- Requirements and groupings may differ depending on the generator type and connection to the system.
- Standard groupings are provided for thermal and hydel generator stations.
Download as PPT, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
203 views
Gen Prot
The document discusses generator protections, their requirements, and how they are grouped. It provides details on:
- Generators require reliable protections due to their critical role and expensive repairs if damaged.
- Protections are grouped into classes (A, B, C) based on the severity of the fault and appropriate trip response.
- Requirements and groupings may differ depending on the generator type and connection to the system.
- Standard groupings are provided for thermal and hydel generator stations.
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 41
Generator Protections
- requirements and grouping of protections
Generators are power sources, first equipment in power system hierarchy hence no other equipment protection can provide back up for generators and are expensive requiring long outages for break down repairs. Generator protections have to be reliable and must have adequate redundancies in both protection functions and tripping functions Generator abnormal conditions and faults for which protections are to be provided are many Tripping functions required are also varied depending on the protection function. This requires that various functions are classified under different groups Protection requirements slightly differ depending on type of prime mover as steam turbine, hydro, gas and diesel Generator Protections - requirements and grouping of protections Trip functions also differ depending on type of generator connection to system As unit system with its transformer As with generator breaker system having breaker between generator and transformer As with a common transformer for more than one generator in case of small hydro units As with direct connection with the system in case of captive plants etc. Grouping of generator protections are for Providing different trip logics( Class A,B,C etc) Providing separate trip supplies and separate tripping relays for fail safe criterion ( DC sources, trip relays etc) Generator Protections - requirements and grouping of protections Grouping typical in thermal stations Class A protections- Emergency trips for serious faults requiring immediate total shut down of prime mover, isolation from grid and de excitation
1. Generator differential 87G 2. Over all differential 87GT 3. Stator earth fault 64G 4. Rotor earth fault second 64F 5. Over voltage 6. Over fluxing trip 99G 7. Restricted EF of transformer 64RE 8. UAT differential 87UAT 9. B/U OCR of UAT 51 UAT 10. Reverse power 32G 11. Buch and PRDS of GT and UATS 12. Inter turn 95G 13. Turbine protections like over speed 14. Trips from excitation system Trip 86 G Trip generator breakers Trip FCB Trip turbine Trip UAT breakers and initiate 6.6KV change over (If no GCB between gen. and transformer) Cut in 60% HPLP bypass Initiate LBB protection Block cosing of GCB, FCB and UAT breakers Generator Protections - requirements and grouping of protections Grouping typical in thermal stations- Class B protections Non urgent trips for faults not requiring immediate total shut down and which can be connected for tripping turbine and isolation from grid and deexcitation can be after consumption of entrapped steam in casing and occurrence of reverse power
1. Under frequency stage 2, 87G 2. Negative sequence stage 2, 46G2 3. Loss of excitation, 40G 4. GT and UAT winding temperature very high 5. GT and UAT oil temperature very high 6. Turbine trips 7. Initiation from excitation Trip 86 B Trip turbine Trip UAT breakers and initiate 6.6KV change over (If no GCB between gen. and transformer) Cut in 60% HPLP bypass
Generator Protections - requirements and grouping of protections Grouping typical in thermal stations- Class C protections Faults external to generator and transformer requiring isolation from grid only and machine can remain in house load operation if sustained
1. Under frequency stage 1, 87G1 2. GT back up OCR 3. GT back up EFR 4. Back up impedance stage 1, 21G 5. Neg. sequence stage 1, 46G! 6. Pole slip protection 78G 7. Bus bar protection Trip 86 C
Trip generator breakers Cut in 60% HPLP bypass Initiate LBB
Generator Protections - requirements and grouping of protections Grouping typical in Hydel stations Emergency trips for serious faults requiring immediate total shut down of prime mover, isolation from grid and deexcitation
1. Generator differential 87G 2. Over all differential 87GT 3. Stator earth fault 64G 4. Rotor earth fault second 64F 5. Over voltage 6. Over fluxing trip 99G 7. Restricted EF of transformer 64RE 8. UAT differential 87UAT 9. B/U OCR of UAT 51 UAT 10. Reverse power 32G 11. Buch and PRDS of GT and UATS 12. Inter turn 95G 13. Turbine protections like over speed 14. Trips from excitation system Trip 86 Y Trip generator breakers Trip FCB Trip turbine Initiate LBB protection Block cosing of GCB, FCB and UAT breakers Close main inlet valve if provided Generator Protections - requirements and grouping of protections Grouping typical in Hydel stations-Control action shut down Non urgent trips for faults not requiring immediate total shut down and which can be connected for tripping turbine and isolation from grid and deexcitation can be after closing of guide vanes
1. GT and UAT winding temperature very high 2. GT and UAT oil temperature very high 3. Bearing temperatures very high Trip 86 X
Trip turbine Trip GCB after guide vane is fully closed Trip FCB after tripping of GCB
Generator Protections - requirements and grouping of protections Grouping typical in Hydel stations stations- Class C protections Faults external to generator and transformer requiring isolation from grid only and machine can remain in rated speed and voltage
1. Under frequency stage 1, 87G1 2. GT back up OCR 3. GT back up EFR 4. Back up impedance stage 1, 21G 5. Neg. sequence stage 1, 46G! 6. Bus bar protection Trip 86 E
Trip generator breaker
Generator Protections - requirements and grouping of protections Grouping typical in Hydel stations- Electrical shut down Electrical Faults requiring isolation from grid and de excitation only and machine can remain in rated speed
1. Under frequency stage 2, 87G2 2. Back up impedance stage 2, 21G 3. Neg. sequence stage 1, 46G! 4. Loss of excitation 40G
Trip 86 Z
Trip generator breaker Trip FCB Generator Protections - requirements and grouping of protections Grouping typical in Hydel stations Some Protections require closure of penstock gate also To cut off water in put before guide vane closing time For governor non functioning when trip is initiated and GV closure is not assured Such protections are Over speed both mechanical and electrical Governor failure Machine speed more than 115% and GV has not started closing
Generator Protections - requirements and grouping of protections
In thermal units the class B trip is always converted to Class A trip by
If connected to grid motoring starts after turbine trip and entrapped steam in casing is consumed, causes reverse power and class A trip
If in isolated grid condition, after turbine trip under frequency occurs tripping GCB, turbine trip anded with GCB trip causes tripping of FCB also Generator Protections - requirements and grouping of protections
Requirements as per CBIP recommendations
Stator earth fault 95%, Genr. Diff., loss of exctn, rev. power, Over voltage, U/F, Rotor EF, inter turn (for split phase) for all generators 100% stator earth fault as optional for machines >10 MVA but must for machines>100 MVA Back up Z for machines>10 MVA and Voltage controlled over current for machines<10 MVA Pole slipping for machines >100 MVA Over fluxing for machines >10 MVA Dead machine protection for machines >100 MVA Generator Protections - Stator earth fault protection Are caused by insulation failure in stator winding, transformer LV winding, bus duct insulators and all other components connected to generator terminals Insulation failure could occur because of defective insulation, ageing, over voltages If earth fault is with in stator winding then earth fault current is to be limited and quickly isolated Higher and sustained earth fault current flowing from winding to stator core at the fault causes arcing at the core, loss of core lamination insulation, welding and erosion of laminations Such damages to core require extensive down times and high repair costs Hence the earth fault currents of the generators are limited by adopting high resistance grounding of generator neutrals Total ungrounded system may cause arcing grounds and high transient over voltages due to ferro resonance Generator Protections - Stator earth fault protection Generator neutrals are grounded through high resistance grounding By combination of NGT and NGR for large machines connected to grid through GT By resistance directly connected to neutral for smaller machines with lower generator voltages NGT and NGR are sized such that the effective resistance connected at the neutral has Minimum value to limit the current to about 15 amps Maximum value not greater than the total residual value of capacitive reactance(3 times phase value) in the generator circuit comprising winding capacitance, any surge capacitance connected, all connected cables capacitances, winding capacitances of transformers etc.(R<X c /3N 2 ).This higher limit to avoid reduced capacitance discharge rate and higher transient voltages Also if too less resistance then the voltage available across NGR for relay will be less reducing sensitivity NGT is a typical single phase distribution transformer with primary winding rated to 1.5 times generator ph-N voltage or equal to line to line voltage so that the reactance will be less and withstands voltage surges Generator Protections - Stator earth fault protection Example: For generator rated 11 KV and 100 MW, Total capacitance= Gen. winding C+ Gen.Tr. LV winding C + Surge capacitance + All cables Capacitance + Bus duct capacitance+ aux tr. Winding C + any other connected capacitance = say 0.3 micro. Farad/ phase Total residual capacitance= 3*C= 0.9 micro Farad. Capacitive Imp.= 1/ (2*3.14*50*0.9*10 -6 ) = 3538 ohms The effective resistance in Neutral should not be> 3538. Taking this as 3538 ohms The current through resistance with earth fault at line terminal = 11000/ root 3*3530 = 1.8 amps The current through the capacitance will also be same1.8 amps Total fault current = 1.8+J 1.8 = 2.55 amps, hence OK Earthing Transformer rating Prim. Voltage = 6.35 KV but considering the field forcing during faults standard 11 Kv rating chosen Generator Protections - Stator earth fault protection Example: Earthing Transformer rating Prim. Voltage = 6.35 KV but considering the field forcing during faults standard 11 Kv rating chosen KVA rating = (1.8*1.3)*( 11) = 25.74 KVA ( Factoring 1.3 for field forced V) Considering that the transformer duty as 30 seconds max. and transformers will have 6 times rating for this period, Cont. rating = 25.74/6= 5 KVA, 10 KVA can be chosen Secondary voltage can be as required and 220 or 110 volt is chosen Considering relay voltage rating. Say 110 volt is chosen Earthing resistance rating The secondary current = 1.8 *1.3*(11000/110) = 234 amps The resistance on secondary = effective resistance / (Turns) 2 = 3538/ 100 2 = 0.35 ohms , the actual resist. To be connected will be this, Less transformer winding resistance (This can be neglected) The resist. is to be 0.35 ohms with a current rating of 234 amps for 30 seconds Generator Protections - Stator earth fault protection Duty rating of NGT and NGR are for 30 seconds since earth faults are connected for tripping. 30 seconds rating is normally met by considering 1/6 of calculated KVA value of NGT A voltage operated relay connected across NGR detects the earth faults. Relay set to trip on over voltage threshold The setting of the relay is to detect faults up to 95% of winding. This gives 5% of ph-N voltage on NGT secondary as the pick up to be set. Increasing sensitivity by lesser pick up setting may cause mal operation. Also time delay of 2-5 sec. adopted to discriminate for faults on HV side of transformer due to inter winding capacitance of GT, for VT secondary faults, for transients etc. Hence relay is called 95% stator earth fault relay Relay is tuned to fundamental and immune to third harmonics Earth fault voltage can also be detected by connecting a similar relay in open delta of VTs primary of which are in star and earthed For larger machines both relays are provided one as main and other as stand by Generator Protections- Stator earth fault protection
Voltages during a full line to ground fault across open delta Generator Protections- Stator earth fault protection
Voltages during a full line to ground fault across open delta Generator Protections - Stator earth fault protection Because of minimum pick up setting to avoid mal operation of EFR the relay can detect earth faults only up to some 95% of winding. Balance 5% winding is blind zone Though earth fault currents for faults in 95-100% is very less, the earth faults if left un detected can cause Higher earth fault currents if a second earth fault occurs and core damages System will operate as a direct grounded system by passing NGT and NGR Hence for larger units of 100 MVA and above 100% stator earth fault relay is provided. To detect faults near to neutral principles used are Third harmonic detection- A third harmonic voltage of about 1% of rated voltage is developed which is distributed across winding to earth capacitance and NGT. Loss of third harmonic voltage or variation in distribution of third harmonic in NGT and line sensed to detect earth faults By injection of voltage signal at NGT Generator Protections - Stator earth fault protection Relay connected across NGR and tuned to third harmonic and set to operate as under voltage relay for 100% stator earth fault These relays require tuning for optimum setting at different load conditions. Difficult to assess third harmonic voltage generation and available value across relay. Are found to mal operate hence connected to alarm at some places Relays detecting variation in ratio of voltages across neutral and line or detecting difference between them as differential detection are also used. This provides better overlap of 95% and 100% relays. If fault is more nearer to neutral the third harmonic voltage across neutral is more and across line is less. If fault is more away from neutral it is vise versa
In injection principle a set of coded pulsed voltage is injected across a section of NGR and a set as reference to detecting relay. Relay evaluates the stator insulation resistance by comparing the reference and the signal across NGR and a fault is detected when the measured resistance is less than set value. Generator Protections - Stator earth fault protection Third harmonic detection principles which can be used are Under voltage detection as V 3N < V set Differential as V 3L * K - V 3N > V set Ratio of difference and sum as a*V 3N - V 3L < k*(V 3N + V 3L )
The setting of 0-95% relay and 95-100% relay are to be such that they overlap for a minimum of 10% for ensuring that fault at any point will not go undetected For under voltage type the third harmonic at no load and at min. operating voltage, at Neutral is to be measured and the setting to be less than this, 50 to 75%. Measurements at site of the third harmonic at all load conditions should be done to decide optimum setting since this values are specific to machine and its connected system. Better if the relay has a test point to give this out put. To avoid un intended operation supervision by PT connected voltage supervision, 70% voltage setting, so that relay operates only after voltage is built up Supervision by GCB contacts Supervision by FCB contacts Generator Protections - Stator earth fault protection
Zones of protection with 3 rd
harmonic differential detection Zones of protection with 3 rd
harmonic under voltage detection
Voltage distribution without fault Voltage distribution with fault near line terminal Voltage distribution with fault near neutral For a machine with measured 3 rd harmonic of --- 11 V at Neutral and 47 V at line in no load --- 141 V at Neutral and 197 V at line in full load Generator Protections - Rotor earth fault protection Rotor earth faults can be caused by insulation failure in rotor winding, slip rings, current carrying leads, etc Rotor DC system is an un earthed system and hence a single earth fault will not result in any harmful current and machine still be safely operated A second earth fault if occurs can cause High fault currents burning the winding and damage. A part of rotor winding is shorted resulting in un ablanced magnetic pull and very high vibrations of machine Hence the rotor earth faults are to be detected at least to give an alarm and taken out of service at the earliest opportunity for rectification If a second earth fault occurs machine should be immediately tripped Provision for detecting first rotor earth fault and second rotor earth fault required Generator Protections - Rotor earth fault protection Detection of rotor earth fault is by injecting a DC or AC voltage between one end of rotor winding and earth. A sensitive transductor circuit and relay detects current flow when rotor earth fault occurs. A pick up value of 1 ma can be set for sensitivity. Second rotor earth fault detection is by preparing a wheat stone bridge circuit with rotor winding from positive to earth, rotor winding from negative to earth, as two arms and two adjustable potentiometers as other two arms. Relay is connected as null point detector. If a second earth fault occurs then bridge is out of balance and relay operates. This provides a reliable protection. Alternatively AC voltage is injected with one end to earth and other end through two coupling capacitors one to positive and other to negative. RC bridge principle is used. Earth fault causes unbalance of the bridge which is detected. The setting values are in terms of insulation resistance 5 K as first stage and 2 K as second stage trip. There is no second rotor earth fault detection circuit separate. For brush less excitation system with rotating diodes separate slip rings for connecting rotor earth fault leads are provided
Generator Protections - Inter turn fault protection Caused by turn to turn insulation failure and results in local heating With split phase winding inter turn fault protection is provided by a high impedance differential protection. Cts in each split winding of a phase are cross connected with a relay across. If no inter turn fault ther is no circulating current. When inter turn fault occurs the EMF developed by a faulty split phase winding will be less than healthy winding and results in circulating current. Modern large machines are not provided with split phase winding. For these windings inter turn faults detection is by open delta VT out put. The VT primaries in star and star point connected to generator star point directly Generator Protections - Loss of excitation protection Loss of excitation can be caused by extreme under excited operation, mal operation of AVR, by inadvertant tripping of FCB ( Total loss of excitation) Loss of excitation condition results in increased load angle and machine reaching stability limits Machine running with total loss of excitation runs as induction generator absorbing MVAR from system, may cause system loading and under voltages Higher stator currents and induced currents in rotor and rotor heating. More pronounced in cylindrical rotors than in salient pole machines. In salient pole machines the damper winding provides a path for circulation of rotor induced currents Hence loss of excitation is to be detected and machine tripped For very small machines under current relay connected in field circuit can be provided. Setting of current level which depends on load is difficult Generator Protections - Loss of excitation protection For all utility machines measurement of impedance seen by the machine which will be in the fourth quadrant is used. A distance protection principle is used Impedance characteristic is off set circle with centre on -X axis The two points on X axis are determined by half of transient direct axis reactance and saturated direct axis synchronous reactance Immune to recoverable power swings Time delay of 2-5 seconds provided to discriminate transients To trip instantly if the terminal voltage dips to less than say 70% which indicates that grid is not able to supply the reactive power consumed by the machine Also an integrated timer provided to take care of oscillating operating point which enters the characteristic and leaves momentarily. (Pulsating relay out put) Generator Protections - Loss of excitation protection
Offset mho characteristic (single) traditionally used. Offset mho characteristic (single) traditionally used. 2 zone Offset mho characteristic recommended for present day large machines with X d > 1 pu. Z1 with time delay of 0.1s and Z2 with time delay of 05-08 s. Generator Protections - Negative sequence protection Negative sequence currents are caused by unbalanced loading of generator, a broken conductor in transmission line or extreme condition by pole discrepancy in the breaker Causes double frequency eddy currents induced in rotor surface and excessive local heating of rotor body, retaining ring etc. Prolonged negative sequence operation may require dismantling and inspection of rotor The negative sequence heating limit of the rotor is stated by machine manufacturer as Continuous allowable negative sequence current Constant K which is equal to I 2 2 *t giving the heating constant. K is about 8 to 10 for turbo alternators and 20 for Hydro A relay to detect the negative sequence current through negative sequence filter is provided. One element to alarm with a definite time delay of 5 seconds and one to provide trip on inverse characteristic are provided
Generator Protections - Back up protection Back up protection for generator for un cleared line faults or bus faults when bus bar protection does not operate A back up EFR connected in transformer neutral provides back up for un cleared earth faults in the system Back up impedance relay connected to generator side currents and voltages provides back up protection for ph-ph faults on HV side of transformer Alternatively for generators directly connected to loads voltage controlled OCR provides back up protections. Voltage restrained over current for smaller sets as back up protections. Impedance is set to reach up to end of longest line connected to bus. Time delay of 1.5 to 2 seconds to allow line protections to operate in zone3 time. Phase shift of GT is compensated by aux. VT connected in same vector group for the relay to see correctly the ph-ph faults on HV side Generator Protections - Pole slipping protection Occurs when machine goes out of step with the system caused by delayed fault clearance or by operation of machine in severe under excited condition Results in pulsating torque on rotor shaft and system disturbance. More pronounced in turbo alternators which have lesser angular moment of inertia and weight per MVA. Hydro machines have higher values and hence pole slipping is not critical. In large turbo machines pole slipping protection provided to trip the machine Over current supervision provided for pole slipping to avoid mal operation Detection of pole slip condition by measuring time taken for the operating point to move from one directional relay characteristic (blinder) to another is measured. If the time taken is more than set value pole slip is detected. During power system faults the operating point moves almost instantly. Alternatively pole slip condition is sensed by counting the no. of slips. Whenever operating point crosses impedance line connecting point of transient reactance of generator and point of system reactance. No. of slips to trip and angle of operating point are set. Min slip frequency is also monitored for decision to trip.
Generator Protections - Reverse power and low forward power Reverse power condition may occur due to failure of prime mover with machine on grid and with or with out excitation Turbine tripping or mal operation of governing or inadvertent closing of control valves etc. Inadvertent closing of penstock gate in case of hydro units For sequential tripping without load throw off and for consuming entrapped steam in turbine casing the planed outage of thermal units is done by tripping the turbine first allowing the unit to run till reverse power condition occurs. Reverse power or low forward power in case of thermal units is undesirable because no or reduced steam flow with rotor rotating causes over heating of turbine blade tips. Due to its importance two channels are provided for reverse power protections Low forward protection has breaker close condition supervision with about 10 sec. time delay Reverse power trip has two logics. One to trip with 1 sec. delay when turbine has already tripped. Other logic is to trip with about 10 sec. delay when there is no turbine trip. For hydro units it is less detrimental but in reaction turbines churning of water in pit occurs. Reverse power condition other than when intended syn.condenser operation is done is not desirable . Hence rev. power protection is being provided for hydro units also now. The motoring power consumed is 1 % for thermal and 2 % for hydro. It is as high as 40% for gas turbine Generator Protections - Application of Numerical relays Numerical generator protection are widely used now a days. Numerical relays were initially introduced for distribution, motor, transmission lines. Due to conservative requirement of reliability and cost consideration for development of hardware and soft ware considering lesser quantities in demand it has taken time for Numerical generator protection relay coming into service. Numerical relays are multi functional, one relay providing many protection functions and other ancillary functions Are built around microprocessor( Mainly DSP with digital filters), A to D converters, multiplexers. All input signals are first digitized with adequate sampling rate and all protection function computation are mathematically performed on these digitized signals using DSP algorithms like ,DFT, Walsh functions, FFT, least squares method etc. Sampling rate of A to D converter to be at least twice the frequency of signals to be computed. Normally 12 to 16 samples per cycle adopted Generator Protections - Application of Numerical relays Numerical generator relay has the following advantages that come with any digital system Multi functional, one relay provides many protection functions resulting in reduction of space and spares. Less drift in accuracy over time, temperature, frequency variation, ageing etc. which are pronounced for analog devices and electro mechanical parts Protection characteristics can be more adoptive since they can be implemented by mathematical DSP algorithms Can be immune to transients, CT saturation etc. PF and frequency independent functioning in cases like reverse power detection at low pf etc possible Imposes very less burden on CT and PT Self diagnostic feature which carries out diagnostic routine and annunciates relay non availability Logics built around soft ware blocks and hence easily configurable and can be changed at site with out any wiring modifications. Can accept external logic in puts with isolation Wide and universal range of settings available and and need not be specific regarding setting range for reordering Generator Protections - Application of Numerical relays Ease of testing and commissioning Provides following ancillary functions in addition to protection functions Measurements and display of parameters. Al input values and also computed values like PF, negative sequence , differential current, residual voltage, residual current etc can be displayed which are very useful for commissioning and fault finding Can store events in non volatile memory with time stamping which can be retrieved for analysis. Time synchronising with external time base like GPS is possible for correct event time Settings are soft ware built and hence can be changed with out requiring adjustments of pots etc and retesting. More than one group of settings can be stored and switched from one group to another as per requirement Can provide disturbance recording feature also Communication capability to communicate with a PC, a central PC from where all up loading and down loading of relay data can be done. Integration with other devices and station SCADA with industry standard protocols are becoming a possibility Generator Protections - Application of Numerical relays Numerical relays have following disadvantages Multi functional and hence one relay failure leads to loss of many protection functions. Any change of settings is to be carefully down loaded and prone to human errors etc. Faulty relays can not be replaced easily like draw out type discreet relays and requires disconnection and reconnection of many wires. Module wise replacement is not still recommended Configuration of numerical relays to be carefully chosen to provide required reliability and optimum cost For large machines Two numerical generator relays as main 1 & 2 Separate transformer numerical relay Discreet relays for back up OCR and EFR For medium sized machines One numerical relay and set of discreet relays for some important functions like 64G, 21G etc For small size machines one numerical relay may be adequate
Generator Protections - Application of Numerical relays The following are to be considered while selecting a numerical generator relay What are the protection functions provided. This varies depending on the number of analog inputs relay can take. Ideally it shall take at least 10- 6 current, 3 voltage and one NGT voltage to be able to provide the standard functions Whether each protection function meets the requirement for ex. Rev power could be a single phase measurement instead of 3 phase, under impedance is circular with origin centre which may result in load encroachment when set to reach longest line etc. HMI user friendliness and ease of scrolling and reading values. Primary requirement is to be able to note the trip operated with ease and quickness from the relay front. Function tripped measuremnts associated with that function to be easily readable with out connecting PC Parameters displayed Event log memory and disturbance recording features Ease of programming and PC soft ware with GUI features to build logics
Generator Protections - Application of Numerical relays Networking capability of relays with regard to connecting all relays to central PC. Some times same manufacturer supplies diferent version numerical relays for generator, transformer nad line which may not be possible to be connected to common bus Communication ports preferably with out any converters Adoptability of universal protocols like IEC-60870-5-101 to 105 and DNP 3 etc for connection to third party devices Pass word security with different levels In numerical relays more functions load the processor computing capability. The functions are processed sequentially one after the other The repetition rate of computation of a function in a cycle decided by priority, time delay, operating speed etc. The requirements are to be met
Generator Protections - Initial commissioning Initial commissioning is important phase when all functions get checked dynamically establishing correct CT/PT connections, polarities, trip functions etc. Sequence of commissioning Generator short circuit run conducted with generator terminals shorted and excitation built up slowly Measurements of all CT currents, stability and operation check of generator differential, negative sequence Generator and transformer short circuit run conducted with transformer terminals shorted Stability and operation of over all differential, impedance protections etc Single phase ground at HV terminal run Stability and operation of restricted earth fault Stator earth fault run with ground on one stator terminal and slow excitation Stator earth fault operation check