0% found this document useful (0 votes)
81 views1 page

Provision of Differential Relays

This document provides specifications for a 10 MW IPP project, including: 1) Current and potential transformer specifications with ratings for metering and protection. 2) Relay specifications including overcurrent, earth fault, inverse time, and reverse power protection. 3) Auxiliary relays for trip circuit supervision and anti-pumping functions. 4) Metering requirements including ammeter with communication and selector switch.

Uploaded by

Jeya Kannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views1 page

Provision of Differential Relays

This document provides specifications for a 10 MW IPP project, including: 1) Current and potential transformer specifications with ratings for metering and protection. 2) Relay specifications including overcurrent, earth fault, inverse time, and reverse power protection. 3) Auxiliary relays for trip circuit supervision and anti-pumping functions. 4) Metering requirements including ammeter with communication and selector switch.

Uploaded by

Jeya Kannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CLIENT: M I 5.

SHANTHA PROJ ECTS LIMITED


PROJ ECT: 1 X 10 MW IPP
REVISION: 01, DATE: 24/01/2012
SL.Nol DESCRIPTION SPECIFICATION Mls, SIEMENS LIMITED
45
No 1 1
Current Rating 1200A 1250
CT Metering 3 Nos. 800 Al1A Class-0.5. 15VA
1000A 11A - (Wound) ...
. Cpre 1 - 15VA, CL - 0.5
1000A 11A - (Wound)
./
CT Protection 3 Nos. 500 Al1A Class-5P10, 15VA Core 2 - 15VA, CL 5P10
,
1 No. - Instantaneous Over Current

Relay,
Relay 2 : Numerical relay
1No Instantaneous earth fault relay,
comprising of following function
(with IEC 103 Protocol)
50/51, 50N/51N, 86 95, 27, 2, 32
1No IDMT over current relay,
YES (ANTIPUMPING IS AN
Relay
1 No. IDMT ElF Relay, INCLUDED FEATURE OF OUR
BREAKER HENCE SEPARA,J E
1no Reverse power relay,
RELAY IS NOT PROVIDED.)
Under Voltage Relay, Reverse
Auxiliary Relay:
Power Relay,
Relay 1 : Master Trip Relay - VAJ H
1 no Trip Circuit Supervision Relay
13-1 no.'"
& Anti Pumping Relay
Dv/Dt & Df/Dt lI Q~lilflD~l!R:v\(1iI ;l!J t!'flrq~
(11KV/~3)/(110V/~3) I (110V/.J3)
(11KVN3)/(110V/.J3) I (110V/~3) ,
PT
CI.D.5, 100 VAI CL 3P, 100VA
Core 1 : 100 VA, CL - 0.5
Core 2: 100VA, CL 3p .......
MF meter with RS 485
Meters communication, Ammeter 1 No with YES /'
selector switch.
ACCESSORIES
a BKR Control Switch 1 NO
,-
b Local I Remote switch 1 NO
,-
c Indicating Lamps (LED Type) 1 SET
./
d SPACE HEATER +Thermostat 1 NO
......
e PUSH BUTTONS 1 SET
-
f MCB'S 1 SET".
9
Hooter 1 NO......--
h Panel Illumination Lamp
.1NO~
AW POWER ENGINEERS PRIVATE LIMITED - CHENNAI - 40 5 OF 9