Panel Detailes: Elpb-Ro Load Center Emdb - R Bottom 18 Elect Room 18 KA
Panel Detailes: Elpb-Ro Load Center Emdb - R Bottom 18 Elect Room 18 KA
LOAD CENTER
EMDB - R
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
LIGHTING 212+14 480 2 10A 10A 1 480 212+14 LIGHTING
EM LIGHTING 212+14 88 4 10A 16A 3 1000 212+14 SOCKET
SOCKET 212+14 3300 6 16A 32A 5 3300 210+12 SPLIT UNIT
SPLIT UNIT 210+12 3300 8 32A 32A 7 3300 210+12 SPLIT UNIT
SPLIT UNIT 210+12 3300 10 32A 32A 9 3300 210+12 SPLIT UNIT
SOCKET 212+14 1000 12 32A 32A 11 SPARE
SPARE 14 10A 10A 13 SPARE
SPARE 16 16A 32A 15 SPARE
SPARE 18 32A 32A 17 SPARE
4300 3388 3780 3300 4300 3780
4300 3388 3780
7600 7688 7560
LOAD
A 43.41 22848 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 34.73 18278.4 DEMMAND LOAD W
PHASE LOAD IN W
80A
ALL BRANCH BREAKERS( MCB) ARE C60N
DESIGNATION OF LOAD DESIGNATION OF LOAD
CURRENT
22848
PHASE LOAD IN W TRIP RATING
FED FROM
MAIN BREAKER : 3PH , 80A , NS160
FLOOR ROOF
VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
BOTTOM
18
FEEDER ENTRY
NO. OF WAYS
MOUNTING FLUSH MOUNTED
FEEDER CABLE SIZE 3.535 +16 MM2
PANEL DETAILES
PANEL REF.
PANEL TYPE
LOCATION
S.C RATING
ELECT ROOM
18 KA
LPB-RO
LOAD CENTER
MDB - R
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
LIGHTING 212+14 560 2 10A 10A 1 800 212+14 LIGHTING
SIGN BOARD 212+14 1000 4 16A 10A 3 560 212+14 LIGHTING
SIGN BOARD 212+14 1000 6 16A 16A 5 1000 212+14 SIGN BOARD
SIGN BOARD 212+14 1000 8 16A 16A 7 1000 212+14 SIGN BOARD
SOCKET 212+14 1000 10 16A 16A 9 1000 212+14 SOCKET
SPARE 12 10A 16A 11 800 212+14 SPARE
1000 2000 1560 1800 1560 1800
1000 2000 1560
2800 3560 3360
LOAD
A 18.47 9720 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 14.77 7776 DEMMAND LOAD W
PHASE LOAD IN W
40A
ALL BRANCH BREAKERS( MCB) ARE C60N
DESIGNATION OF LOAD DESIGNATION OF LOAD
CURRENT
9720
PHASE LOAD IN W TRIP RATING
FED FROM
MAIN BREAKER : 3PH , 40A , EZ100
FLOOR ROOF
VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
BOTTOM
18
FEEDER ENTRY
NO. OF WAYS
MOUNTING FLUSH MOUNTED
FEEDER CABLE SIZE 3.516 +10 MM2
PANEL DETAILES
PANEL REF.
PANEL TYPE
LOCATION
S.C RATING
ELECT ROOM
18 KA
LPB-TY
FABRICATED
MDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
ROOM PANEL 2 208+10 2300 2 32A 32A 1 2300 208+10 ROOM PANEL 1
ROOM PANEL 4 208+10 2300 4 32A 32A 3 2300 208+10 ROOM PANEL 3
ROOM PANEL 6 208+10 2300 6 32A 32A 5 2300 208+10 ROOM PANEL 5
ROOM PANEL 8 208+10 2300 8 32A 32A 7 2300 208+10 ROOM PANEL 7
ROOM PANEL 10 208+10 2300 10 32A 32A 9 2300 208+10 ROOM PANEL 9
ROOM PANEL 12 208+10 2300 12 32A 32A 11 2300 208+10 ROOM PANEL 11
ROOM PANEL 14 208+10 2300 14 32A 32A 13 2300 208+10 ROOM PANEL 13
ROOM PANEL 16 208+10 2300 16 32A 32A 15 2300 208+10 ROOM PANEL 15
ROOM PANEL 18 208+10 2300 18 32A 32A 17 2300 208+10 ROOM PANEL 17
ROOM PANEL 20 208+10 2300 20 32A 32A 19 2300 208+10 ROOM PANEL 19
ROOM PANEL 22 208+10 2300 22 32A 32A 21 2300 208+10 ROOM PANEL 21
ROOM PANEL 24 208+10 2300 24 32A 32A 23 2300 208+10 ROOM PANEL 23
ROOM PANEL 26 208+10 2300 26 32A 32A 25 2300 208+10 ROOM PANEL 25
ROOM PANEL 28 208+10 2300 28 32A 32A 27 2300 208+10 ROOM PANEL 27
ROOM PANEL 30 208+10 2300 30 32A 32A 29 2300 208+10 ROOM PANEL 29
CORRIDOR LIGHTING 212+14 288 32 10A 10A 31 288 212+14 CORRIDOR LIGHTING
SPARE 34 16A 10A 33 200 212+14 CORRIDOR FCU
CORRIDOR SPOT LIGHTING SPOT 212+14 250 36 10A 10A 35 SPARE
SPARE 38 32A 32A 37 SPARE
SPARE 40 32A 32A 39 SPARE
SPARE 42 32A 32A 41 SPARE
11750 11500 11788 11500 11700 11788
11750 11500 11788
23250 23200 23576
LOAD
A 133 70026 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 106.4 56020.8 DEMMAND LOAD W
CURRENT
DESIGNATION OF LOAD
PHASE LOAD IN W TRIP RATING PHASE LOAD IN W
DESIGNATION OF LOAD
70026
FEEDER ENTRY MOUNTING: FLUSH MOUNTED
MAIN BREAKER : 3PH , 160A , NS250 42 NO. OF WAYS FEEDER CABLE SIZE 3.5*95 +50 MM2
VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
PANEL DETAILES
PANEL REF. ELECT ROOM LOCATION FLOOR TYPICAL
PILOT LIGHTS
BRANCH BREAKERS( MCB) No. (31 TO 36) ARE C60N
REMAINING BRANCH BREAKERS( MCB) ARE C60H
PANEL TYPE 36 KA S.C RATING
160A
FED FROM BOTTOM
EPB-TY
LOAD CENTER
EMDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
CORRIDOR LIGHTING 212+14 272 2 10A 10A 1 288 212+14 CORRIDOR LIGHTING
PATH ROOM LIGHTING 212+14 360 4 10A 10A 3 648 212+14 PATH ROOM LIGHTING
PATH ROOM LIGHTING 212+14 396 6 10A 10A 5 684 212+14 PATH ROOM LIGHTING
EM LIGHTING 212+14 100 8 10A 16A 7 750 212+14 CORRIDOR SOCKET
CORRIDOR SOCKET 212+14 750 10 16A 10A 9 92 212+14 EM LIGHTING
REF. SOCKET 212+14 750 12 16A 16A 11 750 212+14 REF. SOCKET
REF. SOCKET 212+14 750 14 16A 16A 13 750 212+14 REF. SOCKET
REF. SOCKET 212+14 750 16 16A 16A 15 750 212+14 REF. SOCKET
SPARE 18 16A 10A 17 SPARE
1146 1860 1122 1434 1490 1788
1146 1860 1122
2580 3350 2910
LOAD
A 16.8 8840 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 13.44 7072 DEMMAND LOAD W
40A
CURRENT
DESIGNATION OF LOAD
PHASE LOAD IN W TRIP RATING PHASE LOAD IN W
ALL BRANCH BREAKERS( MCB) ARE C60N
DESIGNATION OF LOAD
8840
FED FROM BOTTOM FEEDER ENTRY MOUNTING FLUSH MOUNTED
MAIN BREAKER : 3PH , 40A , EZ100 18 NO. OF WAYS FEEDER CABLE SIZE 3.5*16 +10 MM2
PANEL TYPE 18 KA S.C RATING VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
PANEL DETAILES
PANEL REF. ELECT ROOM LOCATION FLOOR TYPICAL
LPB-GR
LOAD CENTER
MDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
SALOON LIGHTING 212+14 600 2 10A 10A 1 468 212+14 SALOON LIGHTING
MAIN ENTRACE LIGHTING 212+14 432 4 10A 10A 3 300 212+14 WALL LIGHTING
COVE LIGHTING 212+14 300 6 10A 10A 5 648 212+14 MAIN ENTRACE LIGHTING
COVE LIGHTING 212+14 72 8 10A 10A 7 72 212+14 COVE LIGHTING
COVE LIGHTING 212+14 1080 10 10A 10A 9 1080 212+14 COVE LIGHTING
NAJAF LIGHTING 212+14 1500 12 16A 10A 11 40 212+14 COVE LIGHTING
NAJAF LIGHTING 212+14 1500 14 16A 16A 13 1500 212+14 NAJAF LIGHTING
CONTROL ROOM SOCKET 212+14 1200 16 16A 16A 15 1500 212+14 NAJAF LIGHTING
MANEGMENT ROOM SOCKET 212+14 800 18 16A 16A 17 1200 212+14 MANEGMENT ROOM SOCKET
CONTROL ROOM FCU 212+14 200 20 10A 10A 19 200 212+14 SALOON FCU
SALOON FCU 212+14 200 22 10A 10A 21 200 212+14 MANEGMENT ROOM FCU
SALOON FCU 212+14 200 24 10A 10A 23 200 212+14 SALOON FCU
EAST COLUM LIGHTING 212+14 900 26 16A 10A 25 200 212+14 SALOON FCU
SPARE 28 10A 16A 27 900 212+14 WEST COLUM LIGHTING
SPARE 30 10A 16A 29 SPARE
2800 2912 3272 2088 3980 2440
2800 2912 3272
4888 6892 5712
LOAD
A 33.23 17492 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 26.59 13993.6 DEMMAND LOAD W
DESIGNATION OF LOAD
17492
MOUNTING FLUSH MOUNTED
MAIN BREAKER : 3PH , 63A , EZ100 30 NO. OF WAYS FEEDER CABLE SIZE 3.525 +10 MM2
FEEDER ENTRY
CURRENT
DESIGNATION OF LOAD
PHASE LOAD IN W TRIP RATING PHASE LOAD IN W
VOLTAGE & FREQ.: 220/ 380 V , 60 HZ S.C RATING
FED FROM BOTTOM
PANEL DETAILES
PANEL REF. ELECT ROOM LOCATION FLOOR GROUND
ALL BRANCHES BREAKERS MCB C60N
PANEL TYPE 18 KA
63A
ELPB-GR
LOAD CENTER
EMDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
SALOON LIGHTING 212+14 400 2 10A 10A 1 288 212+14 SALOON LIGHTING
SALOON LIGHTING 212+14 500 4 10A 10A 3 700 212+14 SALOON LIGHTING
EM LIGHTING 212+14 96 6 10A 10A 5 1080 212+14 ELEVATOR AREA LIGHTING
EM LIGHTING 212+14 72 8 10A 10A 7 72 212+14 EM LIGHTING
EAST STAIRS LIGHTING PANEL 212+14 1080 10 16A 10A 9 1080 212+14 WEST STAIRS LIGHTING PANEL
SPARE 12 10A 10A 11 40 212+14 ENTTRACE LIGHTING
SPARE 14 10A 10A 13 SPARE
CONTROL ROOM SOCKET 212+14 1200 16 20A 16A 15 1000 212+14 SCECO ROOM PANEL
SALOON SOCKET 212+14 800 18 20A 16A 17 1200 212+14 MANEGMENT ROOM SOCKET
ROLLING SHATTER 212+14 800 20 20A 16A 19 800 212+14 ROLLING SHATTER
SPARE 22 20A 16A 21 SPARE
SPARE 24 20A 10A 23 SPARE
896 2780 1272 2320 2780 1160
896 2780 1272
3216 5560 2432
LOAD
A 21.3 11208 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 17.04 8966.4 DEMMAND LOAD W
50A
CURRENT
DESIGNATION OF LOAD
PHASE LOAD IN W TRIP RATING PHASE LOAD IN W
ALL BRANCHES BREAKERS MCB C60N
DESIGNATION OF LOAD
11208
FED FROM TOP FEEDER ENTRY MOUNTING FLUSH MOUNTED
MAIN BREAKER : 3PH , 50A , EZ100 24 NO. OF WAYS FEEDER CABLE SIZE 3.516 +10 MM2
PANEL TYPE 18 KA S.C RATING VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
PANEL DETAILES
PANEL REF. ELECT ROOM LOCATION FLOOR GROUND
LPB-MZ
LOAD CENTER
EMDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
RESAURANT LIGHTING 212+14 252 2 10A 10A 1 432 212+14 RESAURANT LIGHTING
COVE LIGHTING 212+14 720 4 10A 10A 3 480 212+14 WALL LIGHTING
COVE LIGHTING 212+14 400 6 10A 10A 5 1400 212+14 COVE LIGHTING
MANEGMENT ROOM LIGHTING 212+14 560 8 10A 10A 7 252 212+14 CORRIDOR LIGHTING
SERVICE AREA LIGHTING 212+14 800 10 10A 10A 9 160 212+14 MIRROR LIGHTING
RESAURANT SOCKETS 212+14 1200 12 16A 10A 11 396 212+14 RESAURANT LIGHTING
MANEGMENT ROOM SOCKETS 212+14 1200 14 16A 16A 13 1000 212+14 MANEGMENT ROOM SOCKETS
ARC LIGHTING 212+14 2000 16 20A 10A 15 200 212+14 MANEGMENT ROOM FCU
WATER HEATER 212+14 1200 18 20A 20A 17 2000 212+14 ARC LIGHTING
HAND DRYER 212+14 1500 20 20A 20A 19 1500 212+14 HAND DRYER
MANEGMENT ROOM FCU 212+14 200 22 10A 20A 21 1200 212+14 WATER HEATER
SPARE 24 16A 10A 23 SPARE
2800 3720 3512 3796 2040 3184
2800 3720 3512
6596 5760 6696
LOAD
A 36.2 19052 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 28.96 15241.6 DEMMAND LOAD W
63 A
CURRENT
DESIGNATION OF LOAD
PHASE LOAD IN W TRIP RATING PHASE LOAD IN W
ALL BRANCH BREAKERS( MCB) ARE C60N
DESIGNATION OF LOAD
19052
FED FROM BOTTOM FEEDER ENTRY MOUNTING FLUSH MOUNTED
MAIN BREAKER : 3PH , 63A , EZ100 24 NO. OF WAYS FEEDER CABLE SIZE 3.535 +16 MM2
PANEL TYPE 18 KA S.C RATING VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
PANEL DETAILES
PANEL REF. ELECT ROOM LOCATION FLOOR: MEZZANINE
ELPB-MZ
LOAD CENTER
EMDB
WIRE SIZE WIRE SIZE
AWG B Y R NO. BREA. BREA. NO. B Y R AWG
RESAURANT LIGHTING 212+14 416 2 10A 10A 1 588 212+14 RESAURANT LIGHTING
EM LIGHTING 212+14 104 4 10A 10A 3 288 212+14 RESAURANT LIGHTING
MANEGMENT LIGHTING 212+14 336 6 10A 10A 5 708 212+14 WC LIGHTING
SERVICE AREA SOCKET 212+14 800 8 16A 10A 7 64 212+14 EM LIGHTING
EM LIGHTING 212+14 64 10 10A 16A 9 1000 212+14 RESAURANT SOCKET
SPARE 12 10A 16A 11 800 212+14 MANEGMENT ROOM SOCKETS
SPARE 14 16A 16A 13 SPARE
SPARE 16 16A 16A 15 SPARE
SPARE 18 10A 10A 17 SPARE
336 168 1216 1508 1288 652
336 168 1216
1844 1456 1868
LOAD
A 9.819 5168 CONNECTED LOAD W
0.8 DEMMAND FACTOR
A 7.855 4134.4 DEMMAND LOAD W
VOLTAGE & FREQ.: 220/ 380 V , 60 HZ
MOUNTING FLUSH MOUNTED
FEEDER CABLE SIZE 3.516 +10 MM2
PANEL DETAILES
PANEL REF.
PANEL TYPE
LOCATION
S.C RATING
ELECT ROOM
18 KA
FLOOR MEZZANINE
PHASE LOAD IN W
40A
ALL BRANCH BREAKERS( MCB) ARE C60N
DESIGNATION OF LOAD
FED FROM
MAIN BREAKER : 3PH , 40A , EZ100
BOTTOM
18
FEEDER ENTRY
NO. OF WAYS
DESIGNATION OF LOAD
CURRENT
5168
PHASE LOAD IN W TRIP RATING