This document summarizes the lighting and electrical design for an elementary school submitted to the ASCE Charles Pankow Foundation Architectural Engineering Student Competition. Key aspects include:
1) A lighting design that uses indirect pendant fixtures to provide uniform illumination in classrooms, while also incorporating daylighting and manual shades to control natural light.
2) An electrical system powered by on-site natural gas microturbines that allows the school to function independently as an emergency shelter.
3) A focus on high-performance and sustainable design standards to create a cost-effective and energy-efficient building that stimulates learning.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
79 views45 pages
2013-05 LightingElectrical
This document summarizes the lighting and electrical design for an elementary school submitted to the ASCE Charles Pankow Foundation Architectural Engineering Student Competition. Key aspects include:
1) A lighting design that uses indirect pendant fixtures to provide uniform illumination in classrooms, while also incorporating daylighting and manual shades to control natural light.
2) An electrical system powered by on-site natural gas microturbines that allows the school to function independently as an emergency shelter.
3) A focus on high-performance and sustainable design standards to create a cost-effective and energy-efficient building that stimulates learning.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45
Lighting/Electrical Systems |
ASCE Charles Pankow Foundation Architectural Engineering Student Competition
Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community
Our team submitted designs in the following categories:
Building Integration Design Structural Systems Mechanical Systems Lighting/Electrical Systems Innovative Construction Management and Construction Methods Lighting/Electrical Systems ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013
Lighting/Electrical Systems | 1 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Executive Summary This report details the lighting/electrical system of our teams elementary school design for submission in the 2013 ASCE Charles Pankow Foundation Architectural Engineering Student Competition. The elementary school was designed through an integrated approach, which allowed factors affecting the lighting/electrical system to be addressed by the entire project team.
The lighting/electrical design can be summarized by the following statements:
Combined heat and power (CHP) is utilized with four (4) 65 kW on-site natural gas microturbines, totaling 260 kW peak electric power and 1,100 MBH of peak collectable waste heat.
School is designed to apply for LEED Gold under LEED 2009 for Schools New Construction and Major Renovations. Energy models predict that the building uses 29% less energy than the ASHRAE 90.1 2007 Appendix G Baseline model and is anticipated to receive an EnergyStar Rating of 85.
Lighting design that is cost effective and easy to maintain while still remaining visually interesting and comfortable as a school and as a community center.
Reliable power system with available off-grid electric generation (microturbines) for the safe and effective function of the building as a natural disaster shelter.
Multi-tiered 24/7 security system to prevent possible threats to school children and aid the building staff in maintaining a safe environment for the community.
Table of Contents Lighting/Electrical Narrative
Building a Better Community 2 Lighting Design 3 Electrical Design 9 Fire Alarm Design 13 Telecom Design 14 Codes and Standards 15
Drawings Mech/Elec Integration Overview E1 Basement Lighting Plan E2 1 st Floor Lighting Plan E3 2 nd Floor Lighting Plan E4 3 rd Floor Lighting Plan E5 Basement Power Plan E6 1 st Floor Power Plan E7 2 nd Floor Power Plan E8 3 rd Floor Power Plan E9 Riser Diagrams E10
Lighting/Electrical Systems | 2 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Building a Better Community In 2011, The New York Times ranked Reading as the poorest city in the United States on the basis of having the largest percentage of its population living in poverty. This affects not just the wellbeing of the people living in Reading but also the future by not having proper educational experiences during their childhood.
The mission of the Charles Pankow Foundation is to advance innovations in building design and construction, so as to provide the public with buildings of improved quality, efficiency, and value. The 2013 ASCE Charles Pankow Foundation Student Competition forwards this mission by challenging students to use an integrated design method to create a high-performance elementary school located in the urban setting of Reading, Pennsylvania.
Project Goals Using an integrated design, we as a group formed these three core values. Our teams core values would then be the basis of what drove decision making throughout the design process.
1. Build a better Reading community through construction and implementation of the school program
Select lighting/electrical systems that will aid in the enhancement of the school as a center for learning as well as a multi-purpose community facility Create a safe secure building and site for such activities
2. Design the elementary school to high-performance standards
Low maintenance system that is highly efficient and environmentally conscious Lighting design to stimulate curiosity amongst the students
3. Utilize an integrated design approach to maximize quality, efficiency, and value of the final built product Flexible design that acknowledges future uses and expansion Integration among construction, structural, mechanical, & lighting/electrical disciplines for superior project delivery BIM based design for better analysis and engineering of systems
Lighting/Electrical Systems | 3 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Design Concept Elementary schools are the first institutions where children receive their academic learning. Using light to demonstrate playfulness throughout the building will align to childrens fascinations. People are naturally drawn to more complex objects and brighter light. Through the incorporation of shapes, hidden light sources, and varying light intensities, this design will invoke curiosity and stimulate deeper thinking outside the classroom to complement their education. By creating visually interesting and comfortable spaces, it will encourage children to attend classes. By students increase in attendance, it will help develop critical thinking skills and further boost grades which could potentially help Reading receive more aid from the government, thus helping the community grow. Typical Classroom Classrooms today are the prominent areas where students minds are molded to be productive members of society. Through the incorporation of radiant cooling drop panels simulating dropped ceilings, flat surfaces were provided to reflect light. Pendant fixtures centered underneath the panel were selected to uniformly illuminate the classroom to IES recommendations. Horizontal Illuminance Avg/Min LPD Target 30 FC 2.5 1.4 Design 27.82 FC 2.44:1 0.83
A distance of 8.5 AFF, 1.5 below the radiant cooling panels, was chosen to negate hot spots, see Figure 1 for mounting details. For more information regarding constructability refer to the constructions report drawings, CM-003. An efficient semi-indirect pendant was chosen to provide indirect lighting. Indirect lighting provides more uniform ambient light in the classroom, no casted shadows, and no glare sources to create a more comfortable learning environment for the students.
Figure 2: Example of Typical Classroom RCP. 1 denotes Non Dimmed Zone, 2 denotes Dimmed Zone Figure 1: Mounting Details
Lighting/Electrical Systems | 4 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community The fixture selected implements T5HOs due to their high luminous efficacy, long lamp life, ability to dim, and efficiency of delivering lumens to the work plane. Additionally, programmed rapid start ballasts connected to both lights were chosen to reduce the number of ballasts and preserve the cathodes which will improve the lumen maintenance as the fixtures will be controlled with an occupancy sensor (See Controls). Some of the pendants found in the classroom will be on emergency circuits to provide the necessary illumination to allow students to safely evacuate the school. Daylighting An important feature of the classroom is the ability to incorporate natural daylight into the learning environment. A highly transmissive window (75%) with a SHGC of 0.29 was selected to maintain a view to the exterior and maximize the amount of free light to come into the space. Having the ability to dim the lights with increasing daylight penetration allows for more uniform lighting, and energy savings. This contributes to decreasing the life cycle cost of the building and creating a more comfortable learning environment. Direct sunlight is not typically desirable as it increases the temperature of the rooms which increases the mechanical load and creates glare source. The effects from daylight can be disruptive to the learning environment. Incorporation of overhangs on the south faade decreases the amount of direct sunlight that reaches the windows during part of the heating season, see Figures 3 and 4. Additionally, the overhangs extend 3 beyond the windows to block low angle sun from penetrating underneath the overhang during early mornings or late afternoons.
During the times where the overhangs do not protect against direct sunlight or when the teacher would like a darker room to create higher contrast, shades can be pulled down to decrease the contribution of daylight in the space. This provides the teacher with flexibility to control the lighting in the room to enhance the learning demonstrations. A darker shade was selected to minimize the sun as a glare source but still allow for a visual connection to the exterior. For a more in-depth analysis, refer to pages 16 to 18 of the supporting documents. Controls The ability for a teacher to control the light in the space is critical to the learning environment. The design creates flexibility for the teacher to enhance the learning environment. For more information, refer to page 24 for the wiring configuration. The first row of fixtures closest to the window will be dimmable. A closed loop proportion algorithm was selected to provide smooth transition of the dimming lights. Occupants will not notice the change in light levels as the lights will dim proportionally with increasing daylight to maintain the desired illuminance in the Figure 3: 3D Perspective South Faade Prefabricated Section Figure 4: Section South Exterior Facade
Lighting/Electrical Systems | 5 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community classroom, providing greater visual comfort. Additionally, the teacher will also have the ability to dim the fixtures at their own discretion. This will override the photocell allowing for continuous dimming throughout the classroom. The spaces are large enough to require two passive infrared occupancy sensors to turn off the lights within 15 minutes of people leaving the space. This will decrease the electricity bill for the school and increase lamp life thus improving lumen maintenance. One of the occupancy sensors is placed by the whiteboard to detect any movement within the classroom as soon as someone enters the space and the second one is located along the backwall. The lights will turn on to 50% light output upon entering the space and the occupants will have the ability to switch the lights to full output if desired. The transition of the light levels in the corridor to the classroom with ample daylight could negate the need for lights to be at maximum output thus allowing for additional energy savings. Circulation Areas Corridors in elementary schools serve multiple purposes. They are not just circulation space but areas where students can showcase their classwork that is available to be seen by other students, teachers, and the community for night time art exhibits. The acknowledgement of students work to the public encourages students to develop their creativity. The Reading School District Strategic Plan acknowledges that bullying is a major issue in their schools. Using light to illuminate the surfaces of the corridors creates a feeling that the space is bigger than it actually is. A bigger space gives the perception that visibility is increased, allowing the teaching staff to see more activity that occurs during high traffic times. The design creates a feeling of safety. The ability to allow students to feel safe in the corridors helps focus their attention to achieving learning objectives. Another advantage of using higher light levels is that the adaptation difference as the light levels are more similar to the classroom light levels, see pages 19 to 21 for verification of light levels. This will help avoid the corridors feeling dim and smaller. Horizontal Illuminance Max/Min Target 15 FC 3:1 Design (1 st Floor) 16.37 FC 2.65:1 Design (2 nd Floor) 18.19 FC 1.91:1 Design (3 rd Floor) 16.64 FC 1.68:1
At the center of the designed building is a main lobby on each floor. At these points, shapes are created within the ceiling through coves, see Figures 5-7. These are points to create visual interest as the definition of the building alters. Students will have the ability to recognize the changes and discover the source of light. The indirect lighting creates uniform ambient light which contributes to the perception of easy visibility amongst the students. The diffuse light also provides minimal shadows. The fixtures hidden through coves also allow for easy maintenance since they can be easily reached. The coves are also designed tall enough to block the light sources to not be seen from view to avoid glare sources and encourage curiosity amongst the students.
Lighting/Electrical Systems | 6 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Multi-Purpose/Gym At this Reading Elementary School, the gym serves as a cafeteria and auditorium and is lit accordingly. Horizontal Illuminance Max/Min LPD Target 50 FC 3:1 1.4 Design 47.04 FC 2.78:1 0.92
Since multiple different sporting events can occur in this gym during physical education classes or community activities, the room is lit uniformly. Basketball, kickball, wiffleball, and other activities are multi-directional aerial sports and the design illuminates the room properly to allow individuals to see each other as well as the ball in the air. The design allows spectators to see all action that occurs in the space. High-bay fluorescents are used to evenly illuminate the space. They have a direct distribution to emit light onto the floor surface. They are mounted to the underside of the truss for easier conduit runs to power the fixtures, see Figure 8. This allows for quicker installation which saves the school money on initial cost. Additionally, the design provides a cost effective, clean, visually pleasing design for occupants within the space. Since multiple aerial sports occur within the gym, there is a chance that the fixtures could be struck by an object. To avoid the fixtures or lamps breaking, an impact resistant acrylic lens was chosen to protect the lamps and fixture.
The high bay fluorescent fixtures specifically implement T5HOs. They have high luminous efficacy, great optical control, and ability to dim. Using T5HOs in the gym also reduces the different number of lamp types, which creates easier service for the maintenance team. Additionally, mounting to the bottom of the structure creates a more sturdy connection as the fixture will not move or swing as the maintenance team relamps the fixture and allows for power lines to run above the bottom cord of the truss. Emergency During typical emergencies, some of the fixtures will be on emergency circuits in accordance with (site code) to meet the minimum illuminance necessary for people to exit the building within a 90 minute period. The gym is designed to act as a shelter in case of a natural disaster for people living in the surrounding area. Some of the fixtures in the gym will be connected to a separate emergency circuit in order to provide comfortable uniform light, see page 22, while people are taking refuge in this space, see Sheet E4. Figure 8: Gym Rendering Figure 5: 1st Floor Lobby Rendering Figure 6:2nd Floor Lobby Rendering
Lighting/Electrical Systems | 7 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Min Horizontal Illuminance Max/Min Avg/Min Target 4 FC 10:1 2:1 Design 5.3 FC 3:17 2:1
Daylighting Since the gym could be a potential shelter if necessary, clerestory windows are added to the north side. The area of the windows was determined to take advantage of diffused light and avoid glare. The window sizes were chosen to allow for a connection to the exterior and not cause any distractions or injury during sporting events due to visual uncertainty. The sky on the north side could still potentially be a glare source when a presentation or assembly is occurring in the gym. A darker space could be desired. Manually operated shades controlled remotely can lower to decrease the daylight penetrating into the space. Controls The first column of fixtures closest to the windows will be circuited on a dimmed zone. A closed loop constant proportion algorithm was selected to provide smooth transition of the dimming lights as more daylighting enters the space. Occupants will not notice the change in light levels as the lights will dim proportionally with increasing daylight to maintain the desired illuminance in the gym providing uniform light across the space. Additionally, the highbay fluorescents are specified with an occupancy sensor attached to each fixture allowing for a cost effective design. This infrared occupancy sensor was selected to turn off the lights within 15 minutes of people leaving the space. It will detect people entering the space quicker than an ultrasonic occupancy sensor due to the size of the gym. The implementation of a photosensor and occupancy sensor will decrease the electricity bill for the school and increase lamp life thus improving lumen maintenance. Theatrical Design As previously mentioned, the gym can serve as an assembly space or for plays as well. Ceiling mounted downlights are implemented over the stage. A row of fixtures are placed in front of the curtain for functions where the full stage is not required. Additionally, wall sconces will be placed along the walls to provide ambient light for the audience. The sconces will be mounted above the required mounting height for ADA compliancy as well as protected in a cage. Exterior Site lighting will be designed in compliance with IES recommendations as specified with the Pennsylvania Lighting Ordinance. The fixtures are specified with a full cutoff as to limit urban sky glow. As the pool is open during the night after school hours, safety is a major issue. The design permits safe traveling from the parking lot to the building. Additionally, to avoid promotion of trespassers around the facility at night, the fixtures will be dimmed down to 50% light output after 11:00 pm. The mounting height will be no greater than 20 above the finished grade as well to limit light trespass.
Lighting/Electrical Systems | 8 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Natatorium The Reading Community requested the designers to look into the possibility of adding a six lane, twenty-five meter wide pool accessible to the community into the design. The design constructed the pool underneath the gym as the most cost effective and integrated solution; more detail can be seen on page 5 of the construction report. The inclusion of the pool provides the community with another public space and has the ability to be used as a learning tool to teach students at a young age how to swim. A major concern with implementing the pool underneath the gym is to avoid a cave-like feeling. Clerestory windows are added along the west side to maintain a connection with the exterior for a comfortable environment, see Figures 9 and 10. Additionally, the minimum pool height as suggested by the Olympic Swimming Guidelines was designed to reduce the cost of excavation. By doing so, this creates a short, wide space. Indirect light fixtures to illuminate the ceiling from the sides of the pool were chosen to make the space feel taller and uniformly illuminate the pool with diffuse light. The light-truss is hung below the structure and does not interfere with the mechanical ducts. The use of the light truss was implemented as it can be custom tailored to any design and successfully achieves the design goals. It provides flexibility for more light sources to be added easily at a later date if desired but currently the design is in accordance with recommendations with IES for a type 3 pool, see page 23 for verification of light levels. Horizontal Illuminance Max/Min LPD Target Pool 30 FC 3:1 1.4 Design Pool 34.23 FC 1.43:1 0.53 Target Deck 10 FC 4:1 - Design Deck 24.87 FC 3:1 -
Additionally, the indirect lighting from the light-truss prevents glare sources allowing a lifeguard to easily see directly to the bottom of the pool in case of an emergency. Maintenance cost is drastically reduced as there are no fixtures over the pool. The pool will not need to be drained, decreasing the time it takes to relamp fixtures. The light-truss is ordered pre-wired and pre-aimed reducing time of installation which in turn reduces initial cost of construction.
The light-truss is specified using T5HOs. They have high luminous efficacy, and great optical control. Using T5HOs in the pool also reduce the different number of lamp types which creates easier service for the maintenance team. The indirect fixture in the light truss is protected from any objects that may strike it from activities that occur in the pool.
Figure 9: Outdoor Garden Rendering Figure 10: Pool Rendering
Lighting/Electrical Systems | 9 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Electrical Design Distribution The schools electrical system will consist of three-phase 480/277V power and three-phase 208/120V power. The incoming utility feed is assumed to be three-phase 4,160 Volt. This incoming feed enters the building from the Park Avenue side of the building running parallel with the natural gas, water, and telecommunications utilities. The service terminates in the buildings main electrical room which is centrally located in the basement level. At the unit substation which consists of a main service breaker-disconnect, a 750 kVA delta-wye transformer, secondary breaker, and secondary switchgear distribution section, the main service is stepped down from a three-phase 4,160V delta to a 480/277V wye configuration. From here the system splits into the buildings three main power branches life safety, emergency, and normal. The life safety branch will carry all loads deemed necessary for the protection of human life. The emergency branch will carry all loads that are necessary for safe and reliable operation of the school as an emergency natural disaster shelter. Supplying standby power for the life safety and emergency branches will come from four Capstone 65kW natural gas microturbines, which will be discussed later in this document. Please see the attached electrical riser diagram for a more detailed organization of the electrical system. The preliminary sizing for all equipment was based on a tabulation that can be found on page 25 of the supporting documents and also details of this equipment can be seen on pages 29-30.
Figure 11: 3D Representation of Electrical System within Building Figure 12: BIM Model of Main Electrical Room
Lighting/Electrical Systems | 10 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Equipment Layout As mentioned before, the unit substation will be located in the buildings main electrical room in the basement level. Also, this room will house the main distribution panels for each of the three power branches life safety, emergency, and normal. The automatic transfer switches for the life safety and emergency branches will be located here as well. Finally, each branch will be provided with a 480/277V lighting panel, transformer, and 208/120V double-tub receptacle panel in the main electrical room.
On floors 1, 2, and 3, the normal power branch will have a dedicated closet that will hold a 480/277V lighting panel, a 45 kVA transformer, and 208/120V double-tub receptacle panel. For these closets it was calculated to be more cost effective to transform power in the closets beside the panels as compared to housing a larger single transformer in the main electrical room. Also by doing this, it significantly lowers the available fault current to the 208/120V receptacle panels making it a safer design.
On the 1 st floor, a closet beside the kitchen and gym area will provide space for a 480/277V lighting panel and 208/120V receptacle panel for the life safety and emergency branches.
For exact locations of these spaces and equipment, please see the attached electrical drawings.
Cogeneration In part of a collaborative effort with the mechanical engineers, the school will be outfitted with four Capstone 65kW natural gas microturbines to reduce the amount of electricity consumed from the Reading, PA electric grid. The waste heat created from these microturbines will be utilized in mechanical processes producing an overall system efficiency of 80-90%, whereas the typical efficiency of an electric utility system is around 30%. The use of combined heat and power (CHP) from the microturbine will reduce the operating costs of the school during cogenerating hours and is much cleaner on the environment. The scale of that cost reduction is dependent on ambient running conditions, microturbine part-load efficiencies, and schedule of operation.
Also as mentioned before, the microturbines will act as the buildings source for emergency backup power. The microturbines also have the ability to run on low pressure gases. On-site, an existing underground concrete vault will house a propane storage tank to act as an emergency fuel source should the natural gas utility be compromised. The tank will store enough fuel to power the microturbines for 72 hours.
Heating Load Integration Cogeneration is viable in our school design because the school has some significant year-round heating loads used for heating the pool and supply air reheat. A more detailed breakdown of how the waste heat is utilized can be found in the Mechanical report.
Figure 15: Image of Parallel Capstone Microturbines Figure 14: Main Electrical Room Layout
Lighting/Electrical Systems | 11 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Calculating Cost Savings Microturbine Efficiency and Capacity Manufacturer catalogs claim the microturbine can get up to 85% efficient with the collection of waste heat (See the Capstone Microturbine product sheet in Mechanical Supporting Documentation for information on this product). However, this efficiency seems rather high for typical conditions. Our design team calculated our own assumed microturbine efficiency for determining energy savings:
Table: Assumed Microturbine Efficiency Process Efficiency (% of Energy Input) Notes Electric Production 29% Per Capstone Microturbine product sheet Collectable Waste Heat 36% After electric conversion, our design team estimates we will be able to recover half of the heat from the exhaust gas ( without installing a very large heat exchanger) Total 65% Assumed efficiency for energy savings calculations
Assumption of this overall microturbine efficiency results in the following cogeneration plant capacity.
Table: Elementary School Cogeneration Plant Capacity at Full Load Natural Gas Input (MBH) Electric Power Generation (kW) Collectible Waste Heat (MBH) 3068 260 1,100
Operation and Cost-Savings The team created an hourly demand load model for a typical day in every month of the year, modeling both building electric demand and heating demand. The model was made in Microsoft Excel. From that model, microturbine operation was assessed to determine a preliminary schedule and run-times for each of the four microturbines in the plant. Graphical representation of the model is sampled below, and graphs for all months are included in the Mechanical Supporting Documentation. It was estimated that $50,000 worth of energy savings per year were reasonably achievable with this system. Also, should any excess electricity be produced, it can be sold back to the utility grid. In the state of Pennsylvania, there are many grants and incentives that the district could apply for to help pay for this system. Without any government assistance, the team calculated that the units could be paid off in 10 years. More analysis of the cogeneration life-cycle costs can be found in the Mechanical and Construction reports.
Legend: Blue = Electric demand Red = Building heating demand Green = Electric generation from microturbine Purple = Waste heat from microturbine
0 50 100 150 200 250 300 0 500 1000 1500 2000 2500 3000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 E l e c t r i c
D e m a n d
( k W ) H e a t i n g
( M B h ) Hour (Hour 0 is Midnight) January Weekday Cogeneration Figure 16: Predicted School Electric and Heat Loads Matched with Microturbine Operation
Lighting/Electrical Systems | 12 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Typical Classroom Power The power layout of a typical classroom will be convenient and allow for the emerging growth of technology in the educational setting. The front teaching area will hold a SmartBoard with an integrated projector as well as standard white boards straddling both sides of the Smart Board. A duplex receptacle and data outlet will be provided at 90 AFF for this unit. Three duplex receptacles will be mounted below the teaching boards at 18 AFF for use by the instructor. Shallow depth floor boxes coordinated with the underfloor radiant heating system will provide power/data connections for the instructors desk and also the two student computers near the back of the room. A GFCI receptacle will be located 6 above the counter at the sink as required by the National Electric Code. A duplex receptacle at 18 AFF will be located at the back of the room along with a multioutlet raceway system that will act as a charging station in anticipation of the various technologies that could be brought into the classroom. All receptacles in classrooms will be specified as tamper-resistant for the safety of students.
Figure 17: Classroom Power Layout Figure 18: View Looking Towards Front of Classroom Figure 19: View Looking at Back of Classroom
Lighting/Electrical Systems | 13 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Emergency Power As mentioned before, the elementary school will serve as a natural disaster shelter for the surrounding community. The multi-purpose gym space will serve as the primary refuge space for local citizens. This was designed structurally, mechanically, and electrically to serve and house up to 200 people. Also, the school kitchen will be designated as part of the shelter space to help provide food to shelter occupants. All lighting and electrical loads between these spaces will be served from the emergency branch of the buildings power system. To reiterate, this branch is backed up by the buildings four 65kW microturbines so that in the case of electric utility failure, power can be generated on-site to serve these loads as well as life safety loads. In the case of the natural gas utility also failing, the cogen system will be backed up by underground storage tank containing propane. Enough fuel will be stored to run the system for a minimum of 72 hours. Fire Alarm Design The fire alarm system implemented for the school will follow the NEC 2011 and NFPA 72 standards for the design and installation of detection and signaling equipment. The system will be connected to the building network as well as the local municipality network to quickly notify fire departments of any events that should arise. See the attached fire alarm riser diagram and electrical floor plans for a detailed view of the fire alarm system.
Major Equipment Locations The main fire alarm control panel (FACP) will be located in the main electrical room in the basement level. Floors 1, 2, and 3 will be allotted a terminal cabinet (FATC) in the telecom room of each floor due to the central building location and close proximity to the building backbone data system. An annunciator panel will be located in the front entrance vestibule to provide system feedback to fire-fighting crews.
Device Locations In accordance with NFPA standards, smoke detection devices will be placed in hallways, mechanical/electrical/telecom rooms, and in the mechanical system at proper distances and coverage areas. Other devices such as manual pull stations will be placed at each stairwell and building egress point. Notification devices such as speaker/strobe combination units will be placed in each classroom and throughout the school with the sizing of such according to code.
Figure 20: BIM model of Typical Telecom Room
Lighting/Electrical Systems | 14 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Telecom Design The telecommunications system provided will follow the NEC 2011 and ANSI/TIA/EIA standards for installation and design. For a further detailed view of the telecommunications system, please see the attached telecom riser diagram and electrical floor plans.
Major Equipment Locations Floors 1, 2, and 3 will each provide a 12 x 12 room dedicated to telecommunications. These rooms were chosen because of their central location within the building and the distance limitations of the horizontal cabling. The 1 st floor telecom room will house the main distribution frame with intermediate distribution frames being located in the 2 nd and 3 rd floor rooms. Also housed in these rooms will be the fire alarm terminal cabinets as mentioned before and also the security data gathering panels (SDGP) which will feed the school security system.
Device Locations All horizontal cabling in the school shall be Category 6 (CAT6) throughout. The horizontal cabling will exit the telecom room through rigid steel conduit and then traverse to the nearest cable tray where it will travel to its respective device.
Typical Classroom Each classroom will have data outlets located in each of the three floor boxes to supply data to the student computers, instructor computer, and the instructor voice-over IP (VoIP) handset. Also a data connection will be provided for the classroom Smart Board so it may be connected to the building network as well. A wireless access point integrated into the radiant cooled dropped ceiling panels will be available in each classroom for connectivity of future wireless learning devices. Lastly, a pendant mounted four speaker surround sound system will be connected to be used locally by the instructor or by school officials on an entire building level.
Building Data outlets and wireless access points will be provided accordingly throughout the rest of the building to specific spaces. The building will also incorporate a monitored security system consisting of card readers, door contacts, cameras, motion sensors, and silent alarms, which will be integrated into the whole building network as well as being connected to the local municipality as is the fire alarm system.
Security For a detailed analysis of how the aforementioned devices work within our teams security strategies, please see the teams Integration report.
Figure 21: BIM model of Typical Telecom Room
Lighting/Electrical Systems | 15 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Codes and Standards Electrical Codes ASHRAE 2007 90.1
National Electric Code 2011
NFPA 72 National Fire Alarm and Signaling Code
NFPA 101 Life Safety Code
NFPA 110 Standard for Emergency and Standby Power Systems
ANSI/TIA/EIA Standards for Building Telecommunications
Lighting Standards and References IES Lighting Handbook 10 th Edition
ASHRAE 2007 90.1
Reading School District Strategic Plan
PPG Glazing SOLARBAN 60 (2) STARPHIRE + STARPHIRE
Tips for Daylighting With Windows by the Lawrence Berkeley National Laboratory
Pennsylvania Lighting Ordinance
Lighting/Electrical Systems | 16 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lux Daylighting Analysis Typical Angled First Floor South Classroom (Daylight plus Lighting and Shades)
January 10 am January 1 pm
January 4 pm
January 1 pm
January 10 am
March 10 am
June 10 am
March 1 pm
June 1 pm
March 4 pm
June 4 pm
Lighting/Electrical Systems | 17 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lux Daylighting Analysis Typical Angled Second Floor South Classroom (Daylight plus Lighting and Shades)
January 10 am
January 1 pm
January 4 pm
March 10 am
March 1 pm
March 4 pm
June 10 am
June 1 pm
June 4 pm March10 am March 1 pm March 4 pm June 10 am June 1 pm June 4 pm
Lighting/Electrical Systems | 18 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Daylighting Analysis Energy Savings per Classroom
Example of Preliminary Solar Study for South Facing Classroom with an overhang: A 3 overhang overhang at the top of a 5 window, would protect the window from direct sun during the year highlighted in blue. The portion highlighted in green is when shades may need to be pulled down in order to not have the sun disturb the learning environment within the classroom. The white region is when the south facing faade would not receive any direct sunlight.
Lighting/Electrical Systems | 19 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Analysis First Floor AGI32 Verification of Illuminance Levels (FC)
Lighting/Electrical Systems | 20 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Analysis Second Floor AGI32 Verification of Illuminance Levels (FC)
Lighting/Electrical Systems | 21 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Analysis Third Floor AGI32 Verification of Illuminance Levels (FC)
Lighting/Electrical Systems | 22 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Analysis Gym AGI32 Verification of Illuminance Levels (FC)
Normal Lighting
Life Safety Lighting
Lighting/Electrical Systems | 23 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Lighting Analysis Pool AGI32 Verification of Illuminance Levels (FC)
Lighting/Electrical Systems | 24 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Classroom Control Wiring Diagram Wattstopper LCD-203 Dimming Controller with a LS-5C Wall-Switch.
LS-5C Wall Switch
Lighting/Electrical Systems | 25 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Mechanical Equipment Load (kW) Receptacles - 1.0 Watts/SF Load (kW) Main Chiller 151.62 Basement 20 Secondary Chiller 63.23 First Floor 35 Central Main Supply Fan A 16.41 Second Floor 27 Central Main Supply Fan B 16.41 Third Floor 21 Central Main Return Fan A 5.22 Central Main Return Fan B 5.22 East Main Supply Fan 6.71 Load (kW) East Main Return Fan 2.24 Community Main Supply Fan 5.97 Basement 40 Community Main Return Fan 1.49 First Floor 70 Pool Main Supply Fan 5.97 Second Floor 54 Pool Main Return Fan 1.49 Third Floor 42 Lighting - 1.2 Watts/SF Load (kW) Basement 24 First Floor 42 Second Floor 32.4 Third Floor 25.2 Misc. Power/Future Growth - 2.0 Watts/SF Total Load: 715 kW Electrical Load Tabulation
Lighting/Electrical Systems | 26 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community BLP 480 15,830 22 YES BRP 208 5,240 10 YES EBLP 480 15,380 22 YES EBRP 208 5,120 10 YES ELP1 480 8,610 10 YES EDP 480 16,310 22 YES ERP1 208 2,800 10 YES LSDP 480 7,870 10 YES LP1 480 8,300 10 YES LP2 480 7,850 10 YES LP3 480 7,430 10 YES LSBLP 480 7,450 10 YES LSBRP 208 4,390 10 YES LSLP1 480 5,420 10 YES LSRP1 208 2,770 10 YES NDP 480 16,730 22 YES RP1 208 4,560 10 YES RP2 208 4,490 10 YES RP3 208 4,420 10 YES UNIT SUBSTATION 480 17,200 22 YES Bus Voltage Fault Current (A) kAI C Rating Protected SKM Electrical System Analysis Fault Current Analysis
Lighting/Electrical Systems | 27 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community SKM Electrical System Analysis Arc Flash Studies
Lighting/Electrical Systems | 28 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community SKM Electrical System Analysis Protective Device Coordination Example of coordination among protective devices upstream from the Community Main Supply Fan so if a fault should occur at this equipment, the Community Main Supply Fan MCB should trip first, then the Life Safety DP MCB, and finally the Unit Substation MCB. This coordination prevents the unnecessary loss of power to other branches and panels within the schools electrical system.
Lighting/Electrical Systems | 29 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Electrical Equipment Square D Model III Package Unit Substation
Lighting/Electrical Systems | 30 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Electrical Equipment Square D Premium 30 Energy Efficient Transformers
Lighting/Electrical Systems | 31 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Fixture Schedule
Lighting/Electrical Systems | 32 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Light Truss
Lighting/Electrical Systems | 33 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Light Truss
Lighting/Electrical Systems | 34 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Registration Number 05-2013 Lighting/Electrical Systems to build a better community Drawings Legend
Scale Date Competition Submission Drawings 2/22/12 1 ASCE Charles Pankow Foundation Architectural Engineering Student Competition Team Number 05-2013 N E10 Riser Diagrams Issue Date No. Description Date Chilled Ceiling Water Main AHU Cooling Coils Central Main Supply Fan A Central Main Return Fan A Central Main Supply Fan B Central Main Return Fan B East Main Supply Fan East Main Return Fan Elevator Community Main Supply Fan Community Main Return Fan RP3 LP3 RP2 LP2 RP1 LP1 BRP BLP Normal DP Pool Main Supply Fan Pool Main Return Fan Utility Main Disconnect 750 kVA Transformer MCB Substation Switchgear Emergency ATS Emergency DP EBLP EBRP ERP1 ELP1 LSLP1 LSBLP LSBRP LSRP1 CHP Life Safety ATS Life Safety DP Fire Alarm Terminal Cabinet (FATC) Fire Alarm Terminal Cabinet (FATC) Fire Alarm Terminal Cabinet (FATC) Fire Alarm Control Panel (FACP) Integral Backup Battery Supply 120V Emergency Notification Appliance Circuit NAC Signal Line Circuit SLC F F S 120V Emergency Notification Appliance Circuit NAC Signal Line Circuit SLC F F S 120V Emergency Notification Appliance Circuit NAC Signal Line Circuit SLC F F S 120V Emergency Notification Appliance Circuit NAC Signal Line Circuit SLC F F S Telephone Utility Data Utility Cable TV Utility HOR CT HOR CT HOR CT HOR CT Main Distribution Frame Intermediate Distribution Frame Intermediate Distribution Frame FATC SDGP FATC SDGP FATC SDGP FACP Roof Roof Roof Third Floor Second Floor First Floor Basement First Floor First Floor Basement Basement Second Floor Second Floor Third Floor Third Floor Electrical Riser Fire Alarm Riser Telecom Riser