This document provides a summary of the air system sizing for Floor 2 of a library project in Lahore, Pakistan. The air system serves one zone covering an area of 9,820 square feet. Key specifications of the central cooling coil include a total cooling load of 43.4 tons, a sensible cooling load of 304.2 MBH, and a required airflow of 13,036 CFM to serve the zone. Outdoor design conditions for sizing include an outdoor dry bulb temperature of 106.2°F and relative humidity of 51%.

Uploaded by

M Hamza Nadeem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views

Load Calculations Result

This document provides a summary of the air system sizing for Floor 2 of a library project in Lahore, Pakistan. The air system serves one zone covering an area of 9,820 square feet. Key specifications of the central cooling coil include a total cooling load of 43.4 tons, a sensible cooling load of 304.2 MBH, and a required airflow of 13,036 CFM to serve the zone. Outdoor design conditions for sizing include an outdoor dry bulb temperature of 106.2°F and relative humidity of 51%.

Uploaded by

M Hamza Nadeem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for Floor 2

Project Name: Floor 2 Library


Prepared by: uet

05/16/2014
06:08PM

Air System Information


Air System Name .............................................. Floor 2
Equipment Class ......................................... SPLT AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ............................................................... 9820.0 ft
Location ................................................ Lahore, Pakistan

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Apr to Sep


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load .......................................................... 43.4
Total coil load ....................................................... 520.9
Sensible coil load ................................................. 304.2
Coil CFM at Jul 1400 ........................................... 13036
Max block CFM ................................................... 13036
Sum of peak zone CFM ...................................... 13036
Sensible heat ratio ............................................... 0.584
ft/Ton ................................................................... 226.2
BTU/(hr-ft) ............................................................. 53.0
Water flow @ 10.0 F rise ....................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ..................................................... Jul 1400


OA DB / WB .................................................... 106.2 / 94.9
Entering DB / WB ............................................. 80.4 / 69.6
Leaving DB / WB .............................................. 58.2 / 56.9
Coil ADP ..................................................................... 54.3
Bypass Factor .......................................................... 0.150
Resulting RH ................................................................. 51
Design supply temp. ................................................... 58.0
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM .................................................. 13036 CFM
Standard CFM ..................................................... 12704 CFM
Actual max CFM/ft ................................................ 1.33 CFM/ft

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW ............................................................. 0.00 kW
Fan static .................................................................... 0.00 in wg
CFM/person .............................................................. 16.08 CFM/person

Design airflow CFM ............................................... 1725 CFM


CFM/ft ................................................................... 0.18 CFM/ft