This document provides a summary of the air system sizing for Floor 2 of a library project in Lahore, Pakistan. The air system serves one zone covering an area of 9,820 square feet. Key specifications of the central cooling coil include a total cooling load of 43.4 tons, a sensible cooling load of 304.2 MBH, and a required airflow of 13,036 CFM to serve the zone. Outdoor design conditions for sizing include an outdoor dry bulb temperature of 106.2°F and relative humidity of 51%.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
21 views
Load Calculations Result
This document provides a summary of the air system sizing for Floor 2 of a library project in Lahore, Pakistan. The air system serves one zone covering an area of 9,820 square feet. Key specifications of the central cooling coil include a total cooling load of 43.4 tons, a sensible cooling load of 304.2 MBH, and a required airflow of 13,036 CFM to serve the zone. Outdoor design conditions for sizing include an outdoor dry bulb temperature of 106.2°F and relative humidity of 51%.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for Floor 2
Project Name: Floor 2 Library
Prepared by: uet
05/16/2014 06:08PM
Air System Information
Air System Name .............................................. Floor 2 Equipment Class ......................................... SPLT AHU Air System Type ................................................ SZCAV
Number of zones ............................................................. 1
Floor Area ............................................................... 9820.0 ft Location ................................................ Lahore, Pakistan
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM ....................... Sum of space airflow rates Space CFM ................... Individual peak space loads
Calculation Months ......................................... Apr to Sep
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load .......................................................... 43.4 Total coil load ....................................................... 520.9 Sensible coil load ................................................. 304.2 Coil CFM at Jul 1400 ........................................... 13036 Max block CFM ................................................... 13036 Sum of peak zone CFM ...................................... 13036 Sensible heat ratio ............................................... 0.584 ft/Ton ................................................................... 226.2 BTU/(hr-ft) ............................................................. 53.0 Water flow @ 10.0 F rise ....................................... N/A
Tons MBH MBH CFM CFM CFM
Load occurs at ..................................................... Jul 1400
OA DB / WB .................................................... 106.2 / 94.9 Entering DB / WB ............................................. 80.4 / 69.6 Leaving DB / WB .............................................. 58.2 / 56.9 Coil ADP ..................................................................... 54.3 Bypass Factor .......................................................... 0.150 Resulting RH ................................................................. 51 Design supply temp. ................................................... 58.0 Zone T-stat Check .................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
F F F F % F OK F
Supply Fan Sizing Data
Actual max CFM .................................................. 13036 CFM Standard CFM ..................................................... 12704 CFM Actual max CFM/ft ................................................ 1.33 CFM/ft
Outdoor Ventilation Air Data
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static .................................................................... 0.00 in wg CFM/person .............................................................. 16.08 CFM/person