Elnet Comm
Elnet Comm
1
54
109-110 THD for Volts Line 3 R
1
55
111-112 THD for Current Line 1 R
1
56
113-114 THD for Current Line 2 R
1
57
115-116 THD for Current Line 3 R
1
58
117-118 Active Rate (1,2,3) R 59
119-120 Active Energy Line 1 (W-Import) R 60
121-122 Active Energy Line 2 (W-Import) R 61
123-124 Active Energy Line 3 (W-Import) R 62
125-126 Reactive Energy Line 1 (VAR-Import) R 63
127-128 Reactive Energy Line 2 (VAR-Import) R 64
129-130 Reactive Energy Line 3 (VAR-Import) R 65
131-132 Apparant Energy Line 1 (VA-Import) R 66
133-134 Apparant Energy Line 2 (VA-Import) R 67
135-136 Apparant Energy Line 3 (VA-Import) R 68
137-138 Active Energy Line 1 Rate 1 (Imp) R 69
139-140 Active Energy Line 2 Rate 1 (Imp) R 70
141-142 Active Energy Line 3 Rate 1 (Imp) R 71
143-144 Active Energy Line 1 Rate 2 (Imp) R 72
145-146 Active Energy Line 2 Rate 2 (Imp) R 73
147-148 Active Energy Line 3 Rate 2 (Imp) R 74
9
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
149-150 Active Energy Line 1 Rate 3 (Imp) R 75
151-152 Active Energy Line 2 Rate 3 (Imp) R 76
153-154 Active Energy Line 3 Rate 3 (Imp) R 77
155-156 Active Energy Line 1+2+3 Rate 1 (I) R 78
157-158 Active Energy Line 1+2+3 Rate 2 (I) R 79
159-160 Active Energy Line 1+2+3 Rate 3 (I) R 80
161-162 Apparant Energy Line 1 Rate 1 (I) R 81
163-164 Apparant Energy Line 2 Rate 1 (I) R 82
165-166 Apparant Energy Line 3 Rate 1 (I) R 83
167-168 Apparant Energy Line 1 Rate 2 (I) R 84
169-170 Apparant Energy Line 2 Rate 2 (I) R 85
171-172 Apparant Energy Line 3 Rate 2 (I) R 86
173-174 Apparant Energy Line 1 Rate 3 (I) R 87
175-176 Apparant Energy Line 2 Rate 3 (I) R 88
177-178 Apparant Energy Line 3 Rate 3 (I) R 89
179-180 Apparant Energy 1+2+3 Rate 1 (I) R 90
181-182 Apparant Energy 1+2+3 Rate 2 (I) R 91
183-184 Apparant Energy 1+2+3 Rate 3 (I) R 92
185-186 Voltage Transformer Ratio R/W 93
187-188 Epeom Revision R 94
189-190 Demo Mode R/W* 95
191-192 Configuration PassWord R/W 96
193-194 Min. Current To Accumulate Energy R/W 97
195-196 MuliMeter ID R 98
10
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
197-198 User Function Mode (Technical) R/W 99
201-202 Demand KW Max (Watt) R 101
203-204 Demand PF (KW) R 102
205-206 Demand Date (KW) R 103
207-208 Demand KVA (Watt) R 104
209-210 Demand PF (KVA) R 105
211-212 Demand Date (KVA) R 106
213-214 Demand Current (A) L1 R/W* 107
215-216 Demand Current (A) L2 R/W* 108
217-218 Demand Current (A) L3 R/W* 109
219-220 Demand Current (A) L1+L2+L3 R/W* 110
221-222 Demand Current (A) L1 Date R 111
223-224 Demand Current (A) L2 Date R 112
225-226 Demand Current (A) L3 Date R 113
227-228 Demand Current (A) L1+2+3 Date R 114
233-234 Clear All Current Demand W 117
235-236 Current Demand KW Max R 118
241-242 PFC Power Factor R/W 121
243-244 PFC On Time R/W 122
245-246 PFC Off Time R/W 123
247-248 PFC Avarege Time (Minute) R/W 124
249-250 PFC Stages R/W 125
11
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
251-252 PFC Mode Of Operation R/W 126
253-254 PFC THD (Volt) R/W 127
255-256 PFC Capacitor #1 (KVAR) R/W 128
257-258 PFC Capacitor #2 (KVAR) R/W 129
259-260 PFC Capacitor #3 (KVAR) R/W 130
261-262 PFC Capacitor #4 (KVAR) R/W 131
263-264 PFC Capacitor #5 (KVAR) R/W 132
265-266 PFC Capacitor #6 (KVAR) R/W 133
267-268 PFC THD (Current) R/W 134
271-272 PFC PF Avarrage Time R/W 136
273-274 PFC Comb. Stayble Time R/W 137
275-276 PFC Hysteresis R/W 138
277-278 PFC % Voltage (VT) For OK R/W 139
279-280 PFC % Current (CT) To Stop R/W 140
281-282 PFC Capacitor #1 Status R 141
283-284 PFC Capacitor #2 Status R 142
285-286 PFC Capacitor #3 Status R 143
287-288 PFC Capacitor #4 Status R 144
289-290 PFC Capacitor #5 Status R 145
291-292 PFC Capacitor #6 Status R 146
293-294 Pulse Value (KW-IMP) Relay 1 R/W 147
295-296 Pulse Value (KW-EXP) Relay 2 R/W 148
297-298 Pulse Value (KQ-IMP) Relay 3 R/W 149
12
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
299-300 Pulse Duration (Seconds) R/W 150
301-302 Clock : Seconds R/W* 151
303-304 Clock : Minutes R/W* 152
305-306 Clock : Hours R/W* 153
307-308 Clock : Week Day (1-7) R/W* 154
309-310 Clock : Day R/W* 155
311-312 Clock : Month R/W* 156
313-314 Clock : Year (20xx) R/W* 157
315-316 Run Time (Seconds With Current) R/W* 158
317-318 Day Time (Win Format) R 159
319-320 Force Cpu To response in MC R/W 160
321-322 Type Of Din 1 R/W* 161
323-324 Type Of Din 2 R/W* 162
325-326 Type Of Din 3 R/W* 163
327-328 Type Of Din 4 R/W* 164
333-334
K.Factor Current Line 1 R 167
335-336
K.Factor Current Line 2 R 168
337-338
K.Factor Current Line 3 R 169
339-340 K.Factor Current Line 1+2+3 R 170
341-342 Din 1 Energy Total Rate 1 R 171
343-344 Din 2 Energy Total Rate 1 R 172
345-346 Din 3 Energy Total Rate 1 R 173
13
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
347-348 Din 4 Energy Total Rate 1 R 174
349-350 Din 1 Energy Total Rate 2 R 175
351-352 Din 2 Energy Total Rate 2 R 176
353-354 Din 3 Energy Total Rate 2 R 177
355-356 Din 4 Energy Total Rate 2 R 178
357-358 Din 1 Energy Total Rate 3 R 179
359-360 Din 2 Energy Total Rate 3 R 180
361-362 Din 3 Energy Total Rate 3 R 181
363-364 Din 4 Energy Total Rate 3 R 182
365-366 Din 1 Energy Total Rate 1+2+3 R 183
367-368 Din 2 Energy Total Rate 1+2+3 R 184
369-370 Din 3 Energy Total Rate 1+2+3 R 185
371-372 Din 4 Energy Total Rate 1+2+3 R 186
379-380 Temprature Sensor R/W* 190
381-382 Digital In 1 - Status R 191
383-384 Digital In 2 - Status R 192
385-386 Digital In 3 - Status R 193
387-388 Digital In 4 - Status R 194
395-396 Web Authentication (User=admin) R/W 198
397-398 Fast Trend Cycle Time (Seconds) R/W 199
399-400 History - Date W 200
401-402 History Day W 201
14
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
403-404 History Month W 202
405-406 History - Year W 203
407-408 History-Active Energy Line 1 Rate 1 R 204
409-410 History-Active Energy Line 2 Rate 1 R 205
411-412 History-Active Energy Line 3 Rate 1 R 206
413-414 History-Active Energy Line 1 Rate 2 R 207
415-416 History-Active Energy Line 2 Rate 2 R 208
417-418 History-Active Energy Line 3 Rate 2 R 209
419-420 History-Active Energy Line 1 Rate 3 R 210
421-422 History-Active Energy Line 2 Rate 3 R 211
423-424 History-Active Energy Line 3 Rate 3 R 212
425-426 History-ReActive Energy Ln 1Rate 1 R 213
427-428 History-ReActive Energy Ln 2Rate 1 R 214
429-430 History-ReActive Energy Ln 3Rate 1 R 215
431-432 History-ReActive Energy Ln 1Rate 2 R 216
433-434 History-ReActive Energy Ln 2Rate 2 R 217
435-436 History-ReActive Energy Ln 3Rate 2 R 218
437-438 History-ReActive Energy Ln 1Rate 3 R 219
439-440 History-ReActive Energy Ln 2Rate 3 R 220
441-442 History-ReActive Energy Ln 3Rate 3 R 221
443-444 History-Din 1 Energy Rate 1 R 222
445-446 History-Din 2 Energy Rate 1 R 223
447-448 History-Din 3 Energy Rate 1 R 224
449-450 History-Din 4 Energy Rate 1 R 225
15
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
451-452 History-Din 1 Energy Rate 2 R 226
453-454 History-Din 2 Energy Rate 2 R 227
455-456 History-Din 3 Energy Rate 2 R 228
457-458 History-Din 4 Energy Rate 2 R 229
459-460 History-Din 1 Energy Rate 3 R 230
461-462 History-Din 2 Energy Rate 3 R 231
463-464 History-Din 3 Energy Rate 3 R 232
465-466 History-Din 4 Energy Rate 3 R 233
491-492 History Reading Date R 246
493-494 Debug Counter 1 R/W 247
495-496 Debug Counter 2 R/W 248
497-498 Debug Counter 3 R/W 249
499-500 Debug Counter 4 R/W 250
501-502 Technical Calibration Value 1 R 251
503-504 Technical Calibration Value 2 R 252
505-506 Technical Calibration Value 3 R 253
507-508 Technical Calibration Value 4 R 254
509-510 Float Format (0,1,2) R/W 255
511-512 Compatibility Mode(0,130,170) R/W 256
513-514 Technical Current Calibration R/W 257
519-520 Start Time1 For Period Alarm R/W 260
521-522 Stop Time1 For Period Alarm R/W 261
16
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
523-524 High Power (KW) (Period) R/W 262
525-526 Low Power (KW) (Period) R/W 263
527-528 Time Table For Period Alarm High R/W 264
529-530 Time Table For Period Alarm Low R/W 265
531-532 Start2 Time For Period Alarm R/W 266
533-534 Stop2 Time For Period Alarm R/W 267
537-538 ReActive Energy Line 1 Rate 1 (Imp) R 269
539-540 ReActive Energy Line 2 Rate 1 (Imp) R 270
541-542 ReActive Energy Line 3 Rate 1 (Imp) R 271
543-544 ReActive Energy Line 1 Rate 2 (Imp) R 272
545-546 ReActive Energy Line 2 Rate 2 (Imp) R 273
547-548 ReActive Energy Line 3 Rate 2 (Imp) R 274
549-550 ReActive Energy Line 1 Rate 3 (Imp) R 275
551-552 ReActive Energy Line 2 Rate 3 (Imp) R 276
553-554 ReActive Energy Line 3 Rate 3 (Imp) R 277
555-556 ReActive E. Line 1+2+3 Rate 1 (I) R 278
557-558 ReActive E. Line 1+2+3 Rate 2 (I) R 279
559-560 ReActive E. Line 1+2+3 Rate 3 (I) R 280
561-562 Virtual Pulse Value (KW) P-Total R/W 281
563-564 Virtual Pulse Counter R/W 282
565-566 Fix Value (Debug) 123.4 R 283
567-568 Float Order (0=LM),(1=ML) R/W 284
569-570 ReActive E.Total In Capacitor Mode R 285
17
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
571-572 ReActive E.Total In Non Capacitor Mode R 286
579-580 Delay (MS) for response time (RS485) R/W 290
581-582 Current Line 1 Opposite Error R 291
583-584 Current Line 2 Opposite Error R 292
585-586 Current Line 3 Opposite Error R 293
587-588 Voltage Seq. Error R 294
601-602 1
st
Harmonics for Volts Line 1 R
1
1
301
603-604 2
nd
Harmonics for Volts Line 1 R
1
1
302
1
1
661-662 31
st
Harmonics for Volts Line 1 R
1
1
331
663-664 32
nd
Harmonics for Volts Line 1 R
1
1
332
665-666 1
st
Harmonics for Volts Line 2 R
1
1
333
667-668 2
nd
Harmonics for Volts Line 2 R
1
1
334
1
1
725-726 31
st
Harmonics for Volts Line 2 R
1
1
363
727-728 32
nd
Harmonics for Volts Line 2 R
1
1
364
729-730 1
st
Harmonic for Volts Line 3 R
1
1
365
731-732 2
nd
Harmonics for Volts Line 3 R
1
1
366
789-790 31
st
Harmonics for Vots Line 3 R
1
1
395
18
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
791-792 32
nd
Harmonics for Volts Line 3 R
1
1
396
793-794 1
st
Harmonics for Current Line 1 R
1
1
397
795-796 2
nd
Harmonics for Current Line 1 R
1
1
398
1
1
853-854 31
st
Harmonics for Current Line 1 R
1
1
427
855-856 32
nd
Harmonics for Current Line 1 R
1
1
428
857-858 1
st
Harmonics for Current Line 2 R
1
1
429
859-860 2
nd
Harmonics for Current Line 2 R
1
1
430
1
1
917-918 31
st
Harmonics for Current line 2 R
1
1
459
919-920 32
nd
Harmonicsfor Current Line 2 R
1
1
460
921-922 1
st
Harmonics for Current Line 3 R
1
1
461
923-924 2
nd
Harmonics for Current Line 3 R
1
1
462
1
1
981-982 31
st
Harmonics for Current Line 3 R
1
1
491
983-984 32
nd
Harmonics for Current Line 3 R
1
1
492
1001-2 User Alarm #1 R 501
1003-4 User Alarm #2 R 502
1005-6 User Alarm #3 R 503
1253-4 User Alarm #127 R 627
19
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
1255-6 User Alarm #128 R 628
1261-62 Demand Watt L1 R 631
1263-64 Demand Watt L2 R 632
1265-66 Demand Watt L3 R 633
1267-68 Demand VAR L1 R 634
1269-70 Demand VAR L2 R 635
1271-72 Demand VAR L3 R 636
1273-74 Demand VA L1 R 637
1275-76 Demand VA L2 R 638
1277-78 Demand VA L3 R 639
1279-80 Demand Watt L1+L2+L3 R 640
1281-82 Demand VAR L1+L2+L3 R 641
1283-84 Demand VA L1+L2+L3 R 642
1285-86 Demand Current (A) L1 R 643
1287-88 Demand Current (A) L2 R 644
1289-90 Demand Current (A) L3 R 645
1291-92 Demand Current (A) L1+L2+L3 R 646
1299-00 Long Wave Write Now !! W 650
1301-02 Long Wave Event (Before) - Seconds R/W 651
1303-04 Long Wave Event (Total) - Seconds R/W 652
20
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
1305-06 Current L1 High - Write Long Wave Event R/W 653
1307-08 Current L1 Hysteresis (Long Wave Event) R/W 654
1315-16 PQ V.Nominal R/W
658
1317-18 PQ Enable (Active) R/W
659
1319-20 Active Energy Line 1 (Export) R
660
1321-22 Active Energy Line 2 (Export) R
661
1323-24 Active Energy Line 3 (Export) R
662
1325-26 Reactive Energy Line 1 (Export) R
663
1327-28 Reactive Energy Line 2 (Export) R
664
1329-30 Reactive Energy Line 3 (Export) R
665
1331-32 Apparant Energy Line 1 (Export) R
666
1333-34 Apparant Energy Line 2 (Export) R
667
1335-36 Apparant Energy Line 3 (Export) R
668
1337-38 Active Energy Line 1 Rate 1 (Exp) R
669
1339-40 Active Energy Line 2 Rate 1 (Exp) R
670
1341-42 Active Energy Line 3 Rate 1 (Exp) R
671
1343-44 Active Energy Line 1 Rate 2 (Exp) R
672
1345-46 Active Energy Line 2 Rate 2 (Exp) R
673
1347-48 Active Energy Line 3 Rate 2 (Exp) R
674
1349-50 Active Energy Line 1 Rate 3 (Exp) R
675
1351-52 Active Energy Line 2 Rate 3 (Exp) R
676
1353-54 Active Energy Line 3 Rate 3 (Exp) R
677
1355-56 Active Energy Line 1+2+3 Rate 1 (E) R
678
21
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
1357-58 Active Energy Line 1+2+3 Rate 2 (E) R
679
1359-60 Active Energy Line 1+2+3 Rate 3 (E) R
680
1361-62 Apparant Energy Line 1 Rate 1 (E) R
681
1363-64 Apparant Energy Line 2 Rate 1 (E) R
682
1365-66 Apparant Energy Line 3 Rate 1 (E) R
683
1367-68 Apparant Energy Line 1 Rate 2 (E) R
684
1369-70 Apparant Energy Line 2 Rate 2 (E) R
685
1371-72 Apparant Energy Line 3 Rate 2 (E) R
686
1373-74 Apparant Energy Line 1 Rate 3 (E) R
687
1375-76 Apparant Energy Line 2 Rate 3 (E) R
688
1377-78 Apparant Energy Line 3 Rate 3 (E) R
689
1379-80 Apparant Energy 1+2+3 Rate 1 (E) R
690
1381-82 Apparant Energy 1+2+3 Rate 2 (E) R
691
1383-84 Apparant Energy 1+2+3 Rate 3 (E) R
692
1385-86 Active Energy (Export) R
693
1387-88 Reactive Energy (Export) R
694
1389-90 Apparant Energy (Export) R
695
1401-2 EN50160 SetUp Value #1 R/W 701
1519-20 EN50160 SetUp Value #60 R/W 760
1521-22 EN50160 Alarm 1(Phase Bit 1,2,3) R 761
22
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
1599-00 EN50160 Alarm 40(Phase Bit 1,2,3) R 800
1601-2 EN50160 Daily Cnt Alrm #1 (L1) R 801
1603-4 EN50160 Daily Cnt Alrm #1 (L2)
R
802
1605-6 EN50160 Daily Cnt Alrm #1 (L3)
R
803
1607-8 EN50160 Daily Cnt Alrm #2 (L1)
R
804
1609-10 EN50160 Daily Cnt Alrm #2 (L2)
R
805
1611-12 EN50160 Daily Cnt Alrm #2 (L3)
R
806
1835-6 EN50160 Daily Cnt Alrm #40 (L1)
R
918
1837-8 EN50160 Daily Cnt Alrm #40 (L2)
R
919
1839-40 EN50160 Daily Cnt Alrm #40 (L3)
R
920
2001-2 EN50160 Daily MaxVal Alrm #1 (L1) R 1001
2003-4 EN50160 Daily MaxVal Alrm #1 (L2)
R
1002
2005-6 EN50160 Daily MaxVal Alrm #1 (L3)
R
1003
2007-8 EN50160 Daily MaxVal Alrm #2 (L1)
R
1004
2009-10 EN50160 Daily MaxVal Alrm #2 (L2)
R
1005
2011-12 EN50160 Daily MaxVal Alrm #2 (L3)
R
1006
2235-6 EN50160 Daily MaxVal Alrm#40(L1)
R
1118
23
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
2237-8 EN50160 Daily MaxVal Alrm#40(L2)
R
1119
2239-40 EN50160 Daily MaxVal Alrm#40(L3)
R
1120
2401-2 EN50160 Daily Time Alrm #1 (L1) R 1201
2403-4 EN50160 Daily Time Alrm #1 (L2)
R
1202
2405-6 EN50160 Daily Time Alrm #1 (L3)
R
1203
2407-8 EN50160 Daily Time Alrm #2 (L1)
R
1204
2409-10 EN50160 Daily Time Alrm #2 (L2)
R
1205
2411-12 EN50160 Daily Time Alrm #2 (L3)
R
1206
2635-6 EN50160 Daily Time Alrm#40(L1)
R
1318
2637-8 EN50160 Daily Time Alrm#40(L2)
R
1319
2639-40 EN50160 Daily Time Alrm#40(L3)
R
1320
2801-2 EN Yesterday Cnt Alrm #1 (L1) R 1401
2803-4 EN Yesterday Cnt Alrm #1 (L2)
R
1402
2805-6 EN Yesterday Cnt Alrm #1 (L3)
R
1403
2807-8 EN Yesterday Cnt Alrm #2 (L1)
R
1404
2809-10 EN Yesterday Cnt Alrm #2 (L2)
R
1405
2811-12 EN Yesterday Cnt Alrm #2 (L3)
R
1406
3035-6 EN Yesterday Cnt Alrm#40(L1)
R
1518
3037-8 EN Yesterday Cnt Alrm#40(L2)
R
1519
24
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
3039-40 EN Yesterday Cnt Alrm#40(L3)
R
1520
3201-2 EN Yesterday MaxVal Alrm #1 (L1) R 1601
3203-4 EN Yesterday MaxVal Alrm #1 (L2)
R
1602
3205-6 EN Yesterday MaxVal Alrm #1 (L3)
R
1603
3207-8 EN Yesterday MaxVal Alrm #2 (L1)
R
1604
3209-10 EN Yesterday MaxVal Alrm #2 (L2)
R
1605
3211-12 EN Yesterday MaxVal Alrm #2 (L3)
R
1606
3435-6 EN Yesterday MaxVal Alrm#40(L1)
R
1718
3437-8 EN Yesterday MaxVal Alrm#40(L2)
R
1719
3439-40 EN Yesterday MaxVal Alrm#40(L3)
R
1720
3601-2 EN Yesterday Time Alrm #1 (L1) R 1801
3603-4 EN Yesterday Time Alrm #1 (L2)
R
1802
3605-6 EN Yesterday Time Alrm #1 (L3)
R
1803
3607-8 EN Yesterday Time Alrm #2 (L1)
R
1804
3609-10 EN Yesterday Time Alrm #2 (L2)
R
1805
3611-12 EN Yesterday Time Alrm #2 (L3)
R
1806
3835-6 EN Yesterday Time Alrm#40(L1)
R
1918
3837-8 EN Yesterday Time Alrm#40(L2)
R
1919
3839-40 EN Yesterday Time Alrm#40(L3)
R
1920
25
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
3841-42 Summer Clock DTE #1 (Sec) R/W 1921
3843-44 Summer Clock DTE #2 (Sec) R/W 1922
3879-80 Summer Clock DTE #20 (Sec) R/W 1940
3881-82 Summer Clock #1 Minute To Add R/W 1941
3883-84 Summer Clock #2 Minute To Add R/W 1942
3919-20 Summer Clock #20 Minute To Add R/W 1960
3921-22 Summer Clock DTE #1 (Hour) R/W 1961
3923-24 Summer Clock DTE #2 (Hour) R/W 1962
3959-60 Summer Clock DTE #20 (Hour) R/W 1980
3961-62 PFC Capacitor #7 (KVAR) R/W 1981
3963-64 PFC Capacitor #8 (KVAR) R/W 1982
3965-66 PFC Capacitor #9 (KVAR) R/W 1983
3967-68 PFC Capacitor #10 (KVAR) R/W 1984
3969-70 PFC Capacitor #11 (KVAR) R/W 1985
3971-72 PFC Capacitor #12 (KVAR) R/W 1986
3973-74 PFC Capacitor #13 (KVAR) R/W 1987
3975-76 PFC Capacitor #14 (KVAR) R/W 1988
26
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
3977-78 PFC Capacitor #15 (KVAR) R/W 1989
3979-80 PFC Capacitor #16 (KVAR) R/W 1990
4001-2 Active Energy (L123)- Month 1 -KWh R 2001
4003-4 Active Energy (L123)- Month 2-KWh R 2002
4071-72 Active Energy(L123)- Month 36-KWh R 2036
4073-74 Month #1 (1-12) (For Register 2001) R 2037
4075-76 Month #2 (1-12) (For Register 2002) R 2038
4143-44 Month #36 (1-12) (For Register 2036) R 2072
4145-46 Year #1 (2001-99) (Register 2001) R 2073
4147-48 Year #2 (2001-99) (Register 2002) R 2074
4215-16 Year #36 (2001-99) (Register 2036) R 2108
4241-42 U.Alarm High Current Value R/W 2121
4243-44 U.Alarm High Voltage Value R/W 2122
4245-46 U.Alarm Low Voltage Value R/W 2123
4247-48 U.Alarm Low PF Value R/W 2124
4249-50 U.Alarm High V.THD Value R/W 2125
4251-52 U.Alarm High I.THD Value R/W 2126
27
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
4261-62 U.Alarm High Current DelayOn R/W 2131
4263-64 U.Alarm High Voltage DelayOn R/W 2132
4265-66 U.Alarm Low Voltage DelayOn R/W 2133
4267-68 U.Alarm Low PF DelayOn R/W 2134
4269-70 U.Alarm High V.THD DelayOn R/W 2135
4271-72 U.Alarm High I.THD DelayOn R/W 2136
4281-82 Demand THD Current (A) L1 R/W* 2141
4283-84 Demand THD Current (A) L2 R/W* 2142
4285-86 Demand THD Current (A) L3 R/W* 2143
4287-88 Demand THD Current (A) L1 | L2 | l3 R/W* 2144
4289-90 Demand THD Current (A) L1 - Date R 2145
4291-92 Demand THD Current (A) L2 - Date R 2146
4293-94 Demand THD Current (A) L3 - Date R 2147
4295-96 Demand THD Current (A) L123 - Date R 2148
4297-98 Demand THD Voltage (A) L1 R/W* 2149
4299-300 Demand THD Voltage (A) L2 R/W* 2150
4301-02 Demand THD Voltage (A) L3 R/W* 2151
4303-04 Demand THD Voltage (A) L1 | L2 | l3 R/W* 2152
4305-06 Demand THD Voltage (A) L1 - Date R 2153
4307-08 Demand THD Voltage (A) L2 - Date R 2154
4309-10 Demand THD Voltage (A) L3 - Date R 2155
4311-12 Demand THD Voltage (A) L123 - Date R 2156
28
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
4313-14 Clear All THD Demand W 2157
4413-14 Alarm- High Voltage L1 R/W 2207
4415-16 Alarm- High Voltage L2 R/W 2208
4417-18 Alarm- High Voltage L3 R/W 2209
4419-20 Alarm- High Voltage L1-2 R/W 2210
4421-22 Alarm- High Voltage L2-3 R/W 2211
4423-24 Alarm- High Voltage L3-1 R/W 2212
4427-28 Alarm- High Current L1 R/W 2214
4429-30 Alarm- High Current L2 R/W 2215
4431-32 Alarm- High Current L3 R/W 2216
4433-34 Alarm- High Current L0 R/W 2217
4437-38 Alarm- High PF L1 R/W 2219
4439-40 Alarm- High PF L2 R/W 2220
4441-42 Alarm- High PF L3 R/W 2221
4443-44 Alarm- High PF (L1-2-3) R/W 2222
4453-54 Alarm- High Voltage THD L1 R/W 2227
4455-56 Alarm- High Voltage THD L2 R/W 2228
4457-58 Alarm- High Voltage THD L3 R/W 2229
4469-70 Alarm- High Current THD L1 R/W 2235
4471-72 Alarm- High Current THD L2 R/W 2236
4473-74 Alarm- High Current THD L3 R/W 2237
4475-76 Alarm- High Current THD L0 R/W 2238
4479-80 Alarm- High Current TDD L1 R/W 2240
29
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
4481-82 Alarm- High Current TDD L2 R/W 2241
4483-84 Alarm- High Current TDD L3 R/W 2242
4485-86 Alarm- High Current TDD L0 R/W 2243
4489-90 Alarm- High Current KF L1 R/W 2245
4491-92 Alarm- High Current KF L2 R/W 2246
4493-94 Alarm- High Current KF L3 R/W 2247
4495-96 Alarm- High Current KF L0 R/W 2248
4613-14 Alarm- Low Voltage L1 R/W 2307
4615-16 Alarm- Low Voltage L2 R/W 2308
4617-18 Alarm- Low Voltage L3 R/W 2309
4619-20 Alarm- Low Voltage L1-2 R/W 2310
4621-22 Alarm- Low Voltage L2-3 R/W 2311
4623-24 Alarm- Low Voltage L3-1 R/W 2312
4627-28 Alarm- Low Current L1 R/W 2314
4629-30 Alarm- Low Current L2 R/W 2315
4631-32 Alarm- Low Current L3 R/W 2316
4633-34 Alarm- Low Current L0 R/W 2317
4637-38 Alarm- Low PF L1 R/W 2319
4639-40 Alarm- Low PF L2 R/W 2320
4641-42 Alarm- Low PF L3 R/W 2321
4643-44 Alarm- Low PF (L1-2-3) R/W 2322
4653-54 Alarm- Low Voltage THD L1 R/W 2327
4655-56 Alarm- Low Voltage THD L2 R/W 2328
30
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
4657-58 Alarm- Low Voltage THD L3 R/W 2329
4669-70 Alarm- Low Current THD L1 R/W 2335
4671-72 Alarm- Low Current THD L2 R/W 2336
4673-74 Alarm- Low Current THD L3 R/W 2337
4675-76 Alarm- Low Current THD L0 R/W 2338
4679-80 Alarm- Low Current TDD L1 R/W 2340
4681-82 Alarm- Low Current TDD L2 R/W 2341
4683-84 Alarm- Low Current TDD L3 R/W 2342
4685-86 Alarm- Low Current TDD L0 R/W 2343
4689-90 Alarm- Low Current KF L1 R/W 2345
4691-92 Alarm- Low Current KF L2 R/W 2346
4693-94 Alarm- Low Current KF L3 R/W 2347
4695-96 Alarm- Low Current KF L0 R/W 2348
4813-14 Alarm- Relay High Voltage L1 R/W 2407
4815-16 Alarm- Relay High Voltage L2 R/W 2408
4817-18 Alarm- Relay High Voltage L3 R/W 2409
4819-20 Alarm- Relay High Voltage L1-2 R/W 2410
4821-22 Alarm- Relay High Voltage L2-3 R/W 2411
4823-24 Alarm- Relay High Voltage L3-1 R/W 2412
4827-28 Alarm- Relay High Current L1 R/W 2414
4829-30 Alarm- Relay High Current L2 R/W 2415
4831-32 Alarm- Relay High Current L3 R/W 2416
4833-34 Alarm- Relay High Current L0 R/W 2417
31
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
4837-38 Alarm- Relay High PF L1 R/W 2419
4839-40 Alarm- Relay High PF L2 R/W 2420
4841-42 Alarm- Relay High PF L3 R/W 2421
4843-44 Alarm- Relay High PF (L1-2-3) R/W 2422
4853-54 Alarm- Relay High Voltage THD L1 R/W 2427
4855-56 Alarm- Relay High Voltage THD L2 R/W 2428
4857-58 Alarm- Relay High Voltage THD L3 R/W 2429
4869-70 Alarm- Relay High Current THD L1 R/W 2435
4871-72 Alarm- Relay High Current THD L2 R/W 2436
4873-74 Alarm- Relay High Current THD L3 R/W 2437
4875-76 Alarm- Relay High Current THD L0 R/W 2438
4879-80 Alarm- Relay High Current TDD L1 R/W 2440
4881-82 Alarm- Relay High Current TDD L2 R/W 2441
4883-84 Alarm- Relay High Current TDD L3 R/W 2442
4885-86 Alarm- Relay High Current TDD L0 R/W 2443
4889-90 Alarm- Relay High Current KF L1 R/W 2445
4891-92 Alarm- Relay High Current KF L2 R/W 2446
4893-94 Alarm- Relay High Current KF L3 R/W 2447
4895-96 Alarm- Relay High Current KF L0 R/W 2448
5013-14 Alarm- Relay Low Voltage L1 R/W 2507
5015-16 Alarm- Relay Low Voltage L2 R/W 2508
5017-18 Alarm- Relay Low Voltage L3 R/W 2509
5019-20 Alarm- Relay Low Voltage L1-2 R/W 2510
32
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
5021-22 Alarm- Relay Low Voltage L2-3 R/W 2511
5023-24 Alarm- Relay Low Voltage L3-1 R/W 2512
5027-28 Alarm- Relay Low Current L1 R/W 2514
5029-30 Alarm- Relay Low Current L2 R/W 2515
5031-32 Alarm- Relay Low Current L3 R/W 2516
5033-34 Alarm- Relay Low Current L0 R/W 2517
5037-38 Alarm- Relay Low PF L1 R/W 2519
5039-40 Alarm- Relay Low PF L2 R/W 2520
5041-42 Alarm- Relay Low PF L3 R/W 2521
5043-44 Alarm- Relay Low PF (L1-2-3) R/W 2522
5053-54 Alarm- Relay Low Voltage THD L1 R/W 2527
5055-56 Alarm- Relay Low Voltage THD L2 R/W 2528
5057-58 Alarm- Relay Low Voltage THD L3 R/W 2529
5069-70 Alarm- Relay Low Current THD L1 R/W 2535
5071-72 Alarm- Relay Low Current THD L2 R/W 2536
5073-74 Alarm- Relay Low Current THD L3 R/W 2537
5075-76 Alarm- Relay Low Current THD L0 R/W 2538
5079-80 Alarm- Relay Low Current TDD L1 R/W 2540
5081-82 Alarm- Relay Low Current TDD L2 R/W 2541
5083-84 Alarm- Relay Low Current TDD L3 R/W 2542
5085-86 Alarm- Relay Low Current TDD L0 R/W 2543
5089-90 Alarm- Relay Low Current KF L1 R/W 2545
5091-92 Alarm- Relay Low Current KF L2 R/W 2546
5093-94 Alarm- Relay Low Current KF L3 R/W 2547
33
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
5095-96 Alarm- Relay Low Current KF L0 R/W 2548
5213-14 Alarm- T.Tbl Voltage L1 R/W 2607
5215-16 Alarm- T.Tbl Voltage L2 R/W 2608
5217-18 Alarm- T.Tbl Voltage L3 R/W 2609
5219-20 Alarm- T.Tbl Voltage L1-2 R/W 2610
5221-22 Alarm- T.Tbl Voltage L2-3 R/W 2611
5223-24 Alarm- T.Tbl Voltage L3-1 R/W 2612
5227-28 Alarm- T.Tbl Current L1 R/W 2614
5229-30 Alarm- T.Tbl Current L2 R/W 2615
5231-32 Alarm- T.Tbl Current L3 R/W 2616
5233-34 Alarm- T.Tbl Current L0 R/W 2617
5237-38 Alarm- T.Tbl PF L1 R/W 2619
5239-40 Alarm- T.Tbl PF L2 R/W 2620
5241-42 Alarm- T.Tbl PF L3 R/W 2621
5243-44 Alarm- T.Tbl PF (L1-2-3) R/W 2622
5253-54 Alarm- T.Tbl Voltage THD L1 R/W 2627
5255-56 Alarm- T.Tbl Voltage THD L2 R/W 2628
5257-58 Alarm- T.Tbl Voltage THD L3 R/W 2629
5269-70 Alarm- T.Tbl Current THD L1 R/W 2635
5271-72 Alarm- T.Tbl Current THD L2 R/W 2636
5273-74 Alarm- T.Tbl Current THD L3 R/W 2637
5275-76 Alarm- T.Tbl Current THD L0 R/W 2638
5279-80 Alarm- T.Tbl Current TDD L1 R/W 2640
34
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
5281-82 Alarm- T.Tbl Current TDD L2 R/W 2641
5283-84 Alarm- T.Tbl Current TDD L3 R/W 2642
5285-86 Alarm- T.Tbl Current TDD L0 R/W 2643
5289-90 Alarm- T.Tbl Current KF L1 R/W 2645
5291-92 Alarm- T.Tbl Current KF L2 R/W 2646
5293-94 Alarm- T.Tbl Current KF L3 R/W 2647
5295-96 Alarm- T.Tbl Current KF L0 R/W 2648
5401-2 Alarm- T.Tbl #1 R/W 2701
5431-32 Alarm- T.Tbl #16 R/W 2716
5601-2 TOU- Uruguay (Dbl) Low - From R/W 2801
5603-4 TOU- Uruguay (Dbl) Low - To R/W 2802
5605-6 TOU- Uruguay (Dbl) Low - From R/W 2803
5607-8 TOU- Uruguay (Dbl) Low - To R/W 2804
5609-10 TOU- Uruguay (Dbl) Med - From R/W 2805
5611-12 TOU- Uruguay (Dbl) Med - To R/W 2806
5613-14 TOU- Uruguay (Dbl) Med - From R/W 2807
5615-16 TOU- Uruguay (Dbl) Med - To R/W 2808
5617-18 TOU- Uruguay (Dbl) High - From R/W 2809
5619-20 TOU- Uruguay (Dbl) High - To R/W 2810
5621-22 TOU- Uruguay (Dbl) High - From R/W 2811
35
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
5623-24 TOU- Uruguay (Dbl) High - To R/W 2812
5625-26 TOU- Uruguay (Trpl) Low - From R/W 2813
5627-28 TOU- Uruguay (Trpl) Low - To R/W 2814
5629-30 TOU- Uruguay (Trpl) Low - From R/W 2815
5631-32 TOU- Uruguay (Trpl) Low - To R/W 2816
5633-34 TOU- Uruguay (Trpl) Med - From R/W 2817
5635-36 TOU- Uruguay (Trpl) Med - To R/W 2818
5637-38 TOU- Uruguay (Trpl) Med - From R/W 2819
5639-40 TOU- Uruguay (Trpl) Med - To R/W 2820
5641-42 TOU- Uruguay (Trpl) High - From R/W 2821
5643-44 TOU- Uruguay (Trpl) High - To R/W 2822
5645-46 TOU- Uruguay (Trpl) High - From R/W 2823
5647-48 TOU- Uruguay (Trpl) High - To R/W 2824
6001-2 Relay #1 Force Start Time R/W 3001
6003-4 Relay #1 Force Stop Time R/W 3002
6005-6 Relay #1 Force Start Time R/W 3003
6007-8 Relay #1 Force Stop Time R/W 3004
6009-10 Relay #1 Force Start Time R/W 3005
6011-12 Relay #1 Force Stop Time R/W 3006
6017-18 Relay #2 Force Start Time R/W 3009
6019-20 Relay #2 Force Stop Time R/W 3010
6021-22 Relay #2 Force Start Time R/W 3011
36
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
6023-24 Relay #2 Force Stop Time R/W 3012
6025-26 Relay #2 Force Start Time R/W 3013
6027-28 Relay #2 Force Stop Time R/W 3014
6033-34 Relay #3 Force Start Time R/W 3017
6035-36 Relay #3 Force Stop Time R/W 3018
6037-38 Relay #3 Force Start Time R/W 3019
6039-40 Relay #3 Force Stop Time R/W 3020
6041-42 Relay #3 Force Start Time R/W 3021
6043-44 Relay #3 Force Stop Time R/W 3022
6049-50 Flg To Clear SST At MidNight R/W 3025
6061-62 Digital Out #1 (Status) R 3031
6063-64 Digital Out #2 (Status) R 3032
6065-66 Digital Out #3 (Status) R 3033
6067-68 Digital Out #4 (Status) R 3034
6101-2 TOU J anuary Type R/W* 3101
6103-4 TOU February Type R/W* 3102
6123-24 TOU December Type R/W* 3112
6125-26 TOU Hour Details R/W* 3113
37
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
6655-56 TOU Hour Details R/W* 3328
6799-0 Active Total Energy (KWh) R 3400
6801-2 Reactive Total Energy (KVARh) R 3401
6803-4 Apparent Total Energy (KVah) R 3402
6805-6 Active Energy Line 1 (KWh-Import) R
3403
6807-8 Active Energy Line 2 (KWh-Import) R
3404
6809-10 Active Energy Line 3 (KWh-Import) R
3405
6811-12 Reactive Energy Line 1 (KVARh-Import) R
3406
6813-14 Reactive Energy Line 2 (KVARh-Import) R
3407
6815-16 Reactive Energy Line 3 (KVARh-Import) R
3408
6817-18 Apparant Energy Line 1 (KVAh-Import) R
3409
6819-20 Apparant Energy Line 2 (KVAh-Import) R
3410
6821-22 Apparant Energy Line 3 (KVAh-Import) R
3411
6823-24 Active Energy Line 1 Rate 1 KWh (Imp) R
3412
6825-26 Active Energy Line 2 Rate 1 KWh (Imp) R
3413
6827-28 Active Energy Line 3 Rate 1 KWh (Imp) R
3414
6829-30 Active Energy Line 1 Rate 2 KWh (Imp) R
3415
6831-32 Active Energy Line 2 Rate 2 KWh (Imp) R
3416
6833-34 Active Energy Line 3 Rate 2 KWh (Imp) R
3417
6835-36 Active Energy Line 1 Rate 3 KWh (Imp) R
3418
6837-38 Active Energy Line 2 Rate 3 KWh (Imp) R
3419
6839-40 Active Energy Line 3 Rate 3 KWh (Imp) R
3420
38
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
6841-42 Active Energy Line 1+2+3 Rate 1 KWh (I) R
3421
6843-44 Active Energy Line 1+2+3 Rate 2 KWh (I) R
3422
6845-46 Active Energy Line 1+2+3 Rate 3 KWh (I) R
3423
6847-48 ReActive Energy Line 1 Rate 1 KVARh (Imp) R
3424
6849-50 ReActive Energy Line 2 Rate 1 KVARh (Imp) R
3425
6851-52 ReActive Energy Line 3 Rate 1 KVARh (Imp) R
3426
6853-54 ReActive Energy Line 1 Rate 2 KVARh (Imp) R
3427
6855-56 ReActive Energy Line 2 Rate 2 KVARh (Imp) R
3428
6857-58 ReActive Energy Line 3 Rate 2 KVARh (Imp) R
3429
6859-60 ReActive Energy Line 1 Rate 3 KVARh (Imp) R
3430
6861-62 ReActive Energy Line 2 Rate 3 KVARh (Imp) R
3431
6863-64 ReActive Energy Line 3 Rate 3 KVARh (Imp) R
3432
6865-66 ReActive E. Line 1+2+3 Rate 1 KVARh (I) R
3433
6867-68 ReActive E. Line 1+2+3 Rate 2 KVARh (I) R
3434
6869-70 ReActive E. Line 1+2+3 Rate 3 KVARh (I) R
3435
6879-80 Active Total Energy (Wh) -Meter B R 3440
6881-82 Reactive Total Energy (VARh) -Meter B R 3441
6883-84 Apparent Total Energy (Vah) -Meter B R 3442
6919-20 Active Energy Line 1 (W-Import) -Meter B R 3460
6921-22 Active Energy Line 2 (W-Import) -Meter B R 3461
6923-24 Active Energy Line 3 (W-Import) -Meter B R 3462
6925-26 Reactive Energy Line 1 (VAR-Import) -Meter B R 3463
6927-28 Reactive Energy Line 2 (VAR-Import) -Meter B R 3464
39
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
6929-30 Reactive Energy Line 3 (VAR-Import) -Meter B R 3465
6931-32 Apparant Energy Line 1 (VA-Import) -Meter B R 3466
6933-34 Apparant Energy Line 2 (VA-Import) -Meter B R 3467
6935-36 Apparant Energy Line 3 (VA-Import) -Meter B R 3468
6937-38 Active Energy Line 1 Rate 1 (Imp) -Meter B R 3469
6939-40 Active Energy Line 2 Rate 1 (Imp) -Meter B R 3470
6941-42 Active Energy Line 3 Rate 1 (Imp) -Meter B R 3471
6943-44 Active Energy Line 1 Rate 2 (Imp) -Meter B R 3472
6945-46 Active Energy Line 2 Rate 2 (Imp) -Meter B R 3473
6947-48 Active Energy Line 3 Rate 2 (Imp) -Meter B R 3474
6949-50 Active Energy Line 1 Rate 3 (Imp) -Meter B R 3475
6951-52 Active Energy Line 2 Rate 3 (Imp) -Meter B R 3476
6953-54 Active Energy Line 3 Rate 3 (Imp) -Meter B R 3477
7001-2 33 Harmonics for Volts Line 1 R 3501
7003-4 34 Harmonics for Volts Line 1 R
3502
7061-62 63 Harmonics for Volts Line 1 R
3531
7063-64 64
Harmonics for Volts Line 1 R
3532
7065-66 33 Harmonics for Volts Line 2 R
3533
7067-68 34 Harmonics for Volts Line 2 R 3534
7125-26 63 Harmonics for Volts Line 2 R
3563
40
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
7127-28 64 Harmonics for Volts Line 2 R
3564
7129-30 33 Harmonic for Volts Line 3 R
3565
7131-32 34 Harmonics for Volts Line 3 R
3566
7189-90 63 Harmonics for Vots Line 3 R 3595
7191-92 64 Harmonics for Volts Line 3 R
3596
7193-94 33 Harmonics for Current Line 1 R
3597
7195-96 34 Harmonics for Current Line 1 R
3598
7253-54 63 Harmonics for Current Line 1 R
3627
7255-56 64 Harmonics for Current Line 1 R 3628
7257-58 33 Harmonics for Current Line 2 R
3629
7259-60 34 Harmonics for Current Line 2 R
3630
7317-18 63 Harmonics for Current line 2 R
3659
7319-20 64 Harmonicsfor Current Line 2 R
3660
7321-22 33 Harmonics for Current Line 3 R 3661
7323-24 34 Harmonics for Current Line 3 R
3662
7381-82 63 Harmonics for Current Line 3 R
3691
7383-84 64 Harmonics for Current Line 3 R
3692
41
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
7599-00 Map Item 3900 (Reg 7799-7800) R/W
3800
7601-02 Map Item 3901 (Reg 7801-7802) R/W
3801
7797-98 Map Item 3999 (Reg 7997-7998) R/W
3899
7799-00 Maped Item 3800 (Reg 7599-7600) R/W
3900
7801-02 Maped Item 3801 (Reg 7601-7602) R/W
3901
7997-98 Maped Item 3899 (Reg 7797-7798) R/W
3999
8799-00 Alarm- High Voltage L1 R/W 4400
8801-02 Alarm- High Voltage L2 R/W
4401
8803-04 Alarm- High Voltage L3 R/W
4402
8805-06 Alarm- High Current L1 R/W
4403
8806-08 Alarm- High Current L2 R/W
4404
8809-10 Alarm- High Current L3 R/W
4405
8811-12 Alarm- High Demand Total KW R/W
4406
8813-14 Alarm- High Import Total KW R/W
4407
8815-16 Alarm- High Export Total KW R/W
4408
8817-18 Alarm- High Temprature R/W
4409
8819-20 Alarm- High kVarhC/kWh R/W
4410
8821-22 Alarm- High kVarhL/kWh R/W
4411
8839-40 Alarm- Low Voltage L1 R/W 4420
42
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
8841-42 Alarm- Low Voltage L2 R/W
4421
8843-44 Alarm- Low Voltage L3 R/W
4422
8845-46 Alarm- Low Current L1 R/W
4423
8846-48 Alarm- Low Current L2 R/W
4424
8849-50 Alarm- Low Current L3 R/W
4425
8851-52 Alarm- Low Demand Total KW R/W
4426
8853-54 Alarm- Low Import Total KW R/W
4427
8855-56 Alarm- Low Export Total KW R/W
4428
8857-58 Alarm- Low Temprature R/W
4429
8859-60 Alarm- Low kVarhC/kWh R/W
4430
8861-62 Alarm- Low kVarhL/kWh R/W
4431
8879-80 Alarm- Hysteresis Voltage L1 R/W 4440
8881-82 Alarm- Hysteresis Voltage L2 R/W
4441
8883-84 Alarm- Hysteresis Voltage L3 R/W
4442
8885-86 Alarm- Hysteresis Current L1 R/W
4443
8886-88 Alarm- Hysteresis Current L2 R/W
4444
8889-90 Alarm- Hysteresis Current L3 R/W
4445
8891-92 Alarm- Hysteresis Demand Total KW R/W
4446
8893-94 Alarm- Hysteresis Import Total KW R/W
4447
8895-96 Alarm- Hysteresis Export Total KW R/W
4448
8897-98 Alarm- Hysteresis Temprature R/W
4449
8899-00 Alarm- Hysteresis kVarhC/kWh R/W
4450
8901-02 Alarm- Hysteresis kVarhL/kWh R/W
4451
43
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
8919-20 Alarm- Delay On -Voltage L1 R/W 4460
8921-22 Alarm- Delay On -Voltage L2 R/W
4461
8923-24 Alarm- Delay On -Voltage L3 R/W
4462
8925-26 Alarm- Delay On -Current L1 R/W
4463
8926-28 Alarm- Delay On -Current L2 R/W
4464
8929-30 Alarm- Delay On -Current L3 R/W
4465
8931-32 Alarm- Delay On -Demand Total KW R/W
4466
8933-34 Alarm- Delay On -Import Total KW R/W
4467
8935-36 Alarm- Delay On -Export Total KW R/W
4468
8937-38 Alarm- Delay On -Temprature R/W
4469
8939-40 Alarm- Delay On -kVarhC/kWh R/W
4470
8941-42 Alarm- Delay On -kVarhL/kWh R/W
4471
8959-60 Alarm- Delay Off -Voltage L1 R/W 4480
8961-62 Alarm- Delay Off -Voltage L2 R/W
4481
8963-64 Alarm- Delay Off -Voltage L3 R/W
4482
8965-66 Alarm- Delay Off -Current L1 R/W
4483
8966-68 Alarm- Delay Off -Current L2 R/W
4484
8969-70 Alarm- Delay Off -Current L3 R/W
4485
8971-72 Alarm- Delay Off -Demand Total KW R/W
4486
8973-74 Alarm- Delay Off -Import Total KW R/W
4487
8975-76 Alarm- Delay Off -Export Total KW R/W
4488
8977-78 Alarm- Delay Off -Temprature R/W
4489
44
MODBUS
Register
Field Description Type GR PQ TXT LT MC LTE LTC
ITEM #
UniArt \
Bacnet AV
8979-80 Alarm- Delay Off -kVarhC/kWh R/W
4490
8981-82 Alarm- Delay Off -kVarhL/kWh R/W
4491
8999-00 Alarm- Relay -Voltage L1 R/W 4500
9001-02 Alarm- Relay -Voltage L2 R/W
4501
9003-04 Alarm- Relay -Voltage L3 R/W
4502
9005-06 Alarm- Relay -Current L1 R/W
4503
9006-08 Alarm- Relay -Current L2 R/W
4504
9009-10 Alarm- Relay -Current L3 R/W
4505
9011-12 Alarm- Relay -Demand Total KW R/W
4506
9013-14 Alarm- Relay -Import Total KW R/W
4507
9015-16 Alarm- Relay -Export Total KW R/W
4508
9017-18 Alarm- Relay -Temprature R/W
4509
9019-20 Alarm- Relay -kVarhC/kWh R/W
4500
9021-22 Alarm- Relay -kVarhL/kWh R/W
4511
Table 1-4 Registers Table
45
1.3 UniArt Alarms for ElNet Multimeter
TheElNet Energy & Powermeteris capable of working with UNIART software. When working with UNIART software user can get specific
alarms from the unit as described in Table 1-5.
Alarm # Description Phase GR LT MC PICO
1 Low Voltage (Line To N) 1
2 High Voltage (Line To N) 1
3 Low Voltage (Line To N) 2
4 High Voltage (Line To N) 2
5 Low Voltage (Line To N) 3
6 High Voltage (Line To N) 3
7 Low Voltage (Line To Line) 1-2
8 High Voltage (Line To Line) 1-2
9 Low Voltage (Line To Line) 2-3
10 High Voltage (Line To Line) 2-3
11 Low Voltage (Line To Line) 3-1
12 High Voltage (Line To Line) 3-1
13 Low Current 1
14 High Current 1
15 Low Current 2
16 High Current 2
17 Low Current 3
18 High Current 3
19 Low Current L0 (N)
20 High Current L0 (N)
21 Low Power Factor 1
22 High Power Factor 1
23 Low Power Factor 2
46
Alarm # Description Phase GR LT MC PICO
24 High Power Factor 2
25 Low Power Factor 3
26 High Power Factor 3
27 Low Power Factor 1+2+3
28 High Power Factor 1+2+3
39 High Power Period (Item 262) 1+2+3
40 Low Power Period (Item 263) 1+2+3
41 Low Voltage THD 1
42 High Voltage THD 1
43 Low Voltage THD 2
43 High Voltage THD 2
45 Low Voltage THD 3
46 High Voltage THD 3
47 Low Current THD 1
48 High Current THD 1
49 Low Current THD 2
50 High Current THD 2
51 Low Current THD 3
52 High Current THD 3
53 Low Current THD L0 (N)
54 High Current THD L0 (N)
55 Low Current TDD 1
56 High Current TDD 1
57 Low Current TDD 2
47
Alarm # Description Phase GR LT MC PICO
58 High Current TDD 2
59 Low Current TDD 3
60 High Current TDD 3
61 Low Current TDD L0 (N)
62 High Current TDD L0 (N)
63 Low Current K.Factor 1
64 High Current K.Factor 1
65 Low Current K.Factor 2
66 High Current K.Factor 2
67 Low Current K.Factor 3
68 High Current K.Factor 3
69 Low Current K.Factor L0 (N)
70 High Current K.Factor L0 (N)
81 U.Alarm High Current 1
82 U.Alarm High Current 2
83 U.Alarm High Current 3
84 U.Alarm High Voltage 1
85 U.Alarm High Voltage 2
86 U.Alarm High Voltage 3
87 U.Alarm Low Voltage 1
88 U.Alarm Low Voltage 2
89 U.Alarm Low Voltage 3
90 U.Alarm Low PF 1+2+3
91 U.Alarm High V.THD 1+2+3
48
Alarm # Description Phase GR LT MC PICO
92 U.Alarm High I.THD 1+2+3
Table 1-5 Alarm Table
49
Whats New?
01.03.2010 : Add LT Demand THD Values (2141-2157)
08.03.2010 : Add GR KFactor (167-170)
31.05.2010 : Add MC
06.06.2010 : Add Temp Sensor (190)
22.07.2010 : Add Modbus Response Delay (290)
01.09.2010 : Add TOU Registers (3101-3328)
06.06.2010 : Add Energy in KW (3400-3435)
15.06.2010 : Add Energy in KW (3400-3411) in LTE
08.09.2011 : Add Total Q For C & L Mode (285 & 286)
12.09.2011 : Add Meter B (3440 & 3477)
10.11.2011 : Add Fast Trend Cycle (GR) (199)
23.11.2011 : Add Long Wave Events (PQ) (650-654)
10.12.2011 : Update Alarm Table
09.01.2012 : Add LTC16 Capacitors 8-16 (1981-1990)
16.02.2012 : Add MC & LT ModBus Index (ReMap Items 3800-3999)
19.02.2012 : Add LT Alarms (Items 4400-4519)
20.02.2012 : Add PQ/GR ModBus Index (ReMap Items 3800-3999)