Audit Guide
Audit Guide
Audit Guide
,
_
FullLoad kW Calculated
kW Measured
@
x 100,
Where: Calculated kW @ Full Load =
,
_
,
_
,
_
calculated
measured
kW
kW
41
25
X 100 = 60%
82
84
86
90
92
94
96
98
0 25 50 75 100
40 hp
20 hp
88
% Motor Load
M
o
t
o
r
E
f
f
i
c
i
e
n
c
y
(
%
)
Efficiency vs Motor Loading for 1800 rpm,
Open Drip Proof Motors
10 hp
100 hp
10 hp
5 hp
Bonneville Power Administration
18
Fans and Pumps
2 General Notes:
C Actual efficiency can easily vary from 50 percent to 80 percent for optimum operation
of a particular pump.
N When modifying or replacing pumps and fans, or adjusting their rpm, be sure that
they can operate under all conditions anticipated for the given system. System
pressure or head should not exceed the maximum pressure or head the fan or pump
can sustain. Surge points should be avoided. (Surge points occur when a fan or
pump can operate at two different flows at the same pressure).
1 For additional information, please refer to the following web sites:
http://www.oit.doe.gov/bestpractices/, http://www.ecw.org
$ Look for or Ask?:
Are pumps or fans installed that are not sized correctly for the task?
Pump or fan efficiency is very dependent upon flow and pressure, and the pump or
fans operating characteristics. For a given rpm there is one optimal operating point
of flow and pressure. As the pressure changes, flow changes and operating
efficiency is also affected. If system conditions have changed since the initial
selection of the pump or fan, they may be operating at a higher rpm than is required,
therefore wasting energy. An oversized pump or fan often works continuously
against a throttle or damper causing even greater inefficiencies.
Reduce pump or fan speed using a sheave adjustment or motor replacement.
It may be possible to tune the speed of a fan or pump so it can operate more
efficiently in a given system. If the fan or pump is belt driven the sheaves can be
modified in order to change the rpm. A motor that operates at a different rpm
may also be installed, particularly if it is oversized. Installing a two-speed motor
could also be an option.
Trim or replace pump impellers.
A pumps operating characteristics can be adjusted by re-sizing the impeller. On
a given system, it may be possible to achieve greater efficiency with a different
pump impeller.
Replace fan or pump with a more energy efficient model.
It may not be possible to achieve an acceptable efficiency on a system with a
given pump or fan. New equipment may be the best option.
Does the facility have a cooling tower(s)?
Install solid state VSD control on the cooling tower fans.
J The cooling tower fans typically run at a constant speed (60 Hz) or a two-
speed motor may drive them. Depending upon the ambient weather
conditions (Wet Bulb Temperature) at the tower location and the cooling
loads placed on the tower, the installation of VSDs on the cooling tower
fan motors can produce significant energy savings. Air is forced or drawn
Yes
Yes
Bonneville Power Administration
19
through the tower in order to cool the incoming water. The Wet Bulb
Temperature is an indication of the amount of moisture in the air that flows
through the tower. The VSDs will vary the fan speed to maintain the set-
point temperature of the cooling water leaving the tower. During periods
when the cooling demands are at a minimum, such as 2
nd
or 3
rd
shifts, the
tower fans run at minimum speed and consume less energy.
The tower fans can be turned off during periods when the ambient air
conditions will sufficiently cool the water without the aide of the fans. The
energy consumption is significantly reduced to just the cost of circulating
the water through the tower.
In addition, the following energy savings opportunities should be evaluated for
each Cooling Tower:
Replace the tower fill material with cellular film fill to improve the heat
transfer efficiency.
Install non-clogging, non-corroding spray nozzles to improve water
distribution through the tower.
Install energy efficient airfoil fans.
Install energy efficient motors on the cooling tower fans and pumps.
J Cooling tower optimization reduces the cost to provide colder water for cooling.
By reducing the temperature of the cooling water, the efficiency of the equipment
or process being cooled is improved.
Are pumps or fans being throttled in order to control the flow rate?
One of the most common and inefficient methods to control a fan or pump is to
restrict its flow. As the pressure is increased the flow is reduced. However, work
required to deliver the reduced flow is greater than would otherwise be required.
The following recommendations apply best to systems with variable flow (such as a
boiler feed-water pump or an induced draft fan.). If flow is constant at a reduced
level see recommendations for incorrectly sized pumps or fans.
Replace throttle control on pump with on-off control.
On-off control works when a pump is maintaining a reservoir level instead of
a constant flow. The pump can be set to operate only at optimum efficiency,
fill the reservoir, and then shut off.
L This measure could create excessive cycling.
Replace throttle control on pump or fan with solid state VSD control.
C VSDs can provide significant energy savings. Quick savings estimates
vary greatly with conditions, however VSDs frequently pay off in a year
or two if they replace a throttle control that operates at 60-70 percent of
full flow or less most of the time. The impact on the fan or pumping
system due to variations in speed should be evaluated when
considering this measure.
N Be careful when applying VSDs to turbine pumps. Damaging
vibrational harmonics may develop at certain operating frequencies.
Be sure to avoid vibration frequencies in the VSD control profile.
Yes
Bonneville Power Administration
20
C Use the following table and Motor Power vs. Motor Speed graph for a first
estimate of energy savings with reduced flow for VSDs controlling fans or
pumps on systems where pressure is allowed to drop with reduced flow.
Potential Energy Savings from Reducing the Speed of Centrifugal
Machines
Percent of Full Flow Percent Energy
Saved
100% 0%
90% 19%
80% 36%
60%
50%
64%
75%
40% 84%
J Example: If the speed (rpm) of a 50 hp motor driving a pump or fan can be
reduced from 1800 rpm to 900 rpm (50 percent), and still provide the
necessary flow and pressure for the task at hand, the horsepower required is
reduced from 50 hp to 13 hp resulting in a power reduction of 75 percent.
Replace throttle control on fan discharge with inlet vane control.
Inlet vanes are a good option for applications like dust collection systems
where the air volume (cubic feet per minute (CFM) of air flow) required
changes, while the air velocity and associated pressure drop must remain
relatively constant. By pre-spinning inlet air, inert guide vanes can reduce
airflow without affecting the pressure the fan must overcome. They are not as
efficient as VSDs in applications where system pressure can be allowed to
drop with reductions in airflow.
Motor Power vs Motor Speed
0
25
50
75
100
125
0 25 50 75 100 125
% of Design Speed
%
o
f
D
e
s
i
g
n
B
H
P
Bonneville Power Administration
21
L At extreme reductions in airflow (less than 30 percent) an inlet vane
acts like a throttle and its efficiency drops off significantly.
Is bypass control being utilized to vary the flow out of the Pump?
Although less common, bypass control can be an extremely inefficient method for
controlling flow. In the best case, pump energy use is constant regardless of
delivery to an end use. In the worst case, energy use increases with reduced delivery
to the end use. As less flow is required at the end use, the excess is diverted to the
bypass circuit and re-circulated. The diverted fluid does not add any value to the
finished product. The pump discharge remains at high capacity, as do the pumping
costs during periods of low demand, which makes this control very costly.
Replace throttle control on pump or fan with solid state VSD control.
C VSDs can provide significant energy savings. Quick savings estimates
vary greatly with conditions, however VSDs frequently pay off in a year
or two if they replace a throttle control that operates at 60-70 percent of
full flow or less most of the time. The impact on the fan or pumping
system due to variations in speed should be evaluated when
considering this measure.
N Be careful when applying VSDs to turbine pumps. Damaging
vibrational harmonics may develop at certain operating frequencies.
Be sure to avoid vibration frequencies in the VSD control profile.
L This method of modulation control may cause cavitation in the pump.
Yes
Bonneville Power Administration
22
Compressed Air Systems
2 General Notes
Many air compressors include capacity and pressure gages, including pressure drop
across the oil separator and dryer.
Look for high-pressure drops through equipment and lines.
Look for intentional pressure reductions, such as with valves and pressure
regulators.
7 Record gage readings of percent capacity and pressure for the air compressors and
air dryers. Record nameplate data for the air dryers, air compressors, and drive
motors.
1 For additional information, please refer to the following web sites:
http://www.knowpressure.org/html/where.html, http://www.cagi.org/glossary1.htm,
and http://www.ecw.org
Common compressed air terms are shown below:
Term Meaning
CFM Cubic Feet per Minute of Air Flow
ICFM Air flow at inlet flange
ACFM Actual air flow delivered after
compressor losses
ACFM-FAD Air flow before filter (Free Air Delivery)
SCFM
Equivalent air flow at Standard
Conditions
(2 different standards use this same
term )
Psi Pressure in pounds per square inch
Psig Psi gauge, referred to atmospheric
pressure
Psia Psi absolute, which is 14.7 as sea
level
Standard Conditions
- CAGI (Compressed Air & Gas
Institute):
- ASME
14.7 psia, 60F, 0% rh (relative
humidity)
14.7 psia, 68F, 36% rh
Typical dryer dew points: Refrigerated Dryers +35F to +38F, Desiccant Dryers -
40F
C Each CFM of compressed air at 100 psig requires: 1/3 to 1/5 hp, ~ 1/4 to 1/7 kW, ~
$10 to $20 per year
C Estimate 3 to 5 CFM per HP
Bonneville Power Administration
23
$ Look for or Ask?:
Are large compressors serving minimal system needs during off-hours such as
maintaining the minimum pressure requirements for a Dry Fire Suppression System?
Install a smaller air compressor dedicated to serve minimal after hour needs,
and isolate from main plant air system.
It is common to leave a large compressor on continuously ~ 7 days a week
to serve a small use such as pressurizing a dry fire suppression system. The
compressor may operate for long periods at an extremely inefficient part
load condition. System leaks also consume air and energy continuously. It
is generally cost effective to install a separate dedicated compressor for
such a need and separate it from the main compressed air system to avoid
losing air and energy to system leaks during non-production times.
Does the facility have Centrifugal Screw Compressors that operate at less than full
load capacity for more than 70 percent of the Time?
Is throttle control used to modulate the compressor output capacity?
Replace throttle control with Load-Unload controls.
L It is not energy efficient for a throttle-controlled screw compressor to
operate below 70-80 percent capacity. Throttling is not desirable if
extended low load periods are expected.
C A throttle-controlled compressor consumes approximately 70 percent of
its full load power when delivering no air. (See the following Throttling
Controls graph)
Throttle Control
How does it work? Throttling modulation works by starving the compressor of
air. The mechanism itself is usually a butterfly valve or a slide valve that is
installed upstream of the compressor inlet. When the system pressure
sensor perceives that the pressure is decreasing (because plant air demand
has exceeded the storage capacity), the valve opens and the compressor
begins to build pressure. When the system pressure sensor perceives that
the pressure is increasing (because plant air demand has decreased below
the storage capacity), the valve starts to close. This creates a partial vacuum
at the compressor inlet. Consequently, the air entering the compressor is
less dense and less air mass enters the compression chamber between the
screws. This reduces the mass flow rate (cfm) of air delivered to the system.
L Energy Use: This method of control is often not efficient. Because the
compressor constantly works against system pressure at the discharge port,
the motor never really gets a chance to unload. As the compressor capacity
drops below 70 percent, the compressor efficiency declines rapidly, therefore
consuming considerable energy while producing minimal air.
Yes
Yes
Yes
Bonneville Power Administration
24
L The Throttling Controls graph above indicates that the compressor can
operate continuously at any point between 0 percent and 100 percent
capacity.
This graph also indicates that 70 percent of full load power is consumed when
the compressor is providing no air, and 85 percent of full load power is
consumed when the compressor is operating at 50 percent capacity.
Applications: Throttling is desirable when over-all plant demand is high or
erratic, when receiver size is small, or when the acceptable range for system
pressure is small. Modulation-only control is a low-risk option because of
mechanical simplicity, small pressure variation, and cycling is avoided.
Consequently, it is a common control strategy.
Load-Unload Control
How does it work? Load-Unload controls on screw compressors allow the
compressor to operate at only two points: fully loaded at 100 percent capacity,
maximum efficiency and unloaded at 0 percent capacity. This control strategy
is similar to On-Off control except that the motor and compressor never
completely shut off. When the system pressure falls below its maximum
pressure set-point (usually 100 120 psig), the compressor runs at full power
and maximum efficiency with the inlet valve 100 percent open until the system
pressure increases to maximum pressure. Then the inlet valve is fully closed
and an unloading valve at the compressor discharge opens and the air leaving
the compressor is vented to a lower pressure.
The most efficient controls use a small oil pump and vent the air all the way to
atmospheric pressure (~0 psig). Some manufacturers maintain a pressure of
~ 30 psig to circulate oil through the compressor while it is unloaded. In either
case, a check valve installed at the discharge prevents the back flow of air at
system pressure when the compressor is unloaded. In the unloaded
condition, the compressor does little work, because it is starved of air at the
inlet and is working against a minimum pressure at the outlet (0 or 30 psig).
J Load-unload control allows a compressor to operate either at full output and
maximum efficiency or unloaded.
Bonneville Power Administration
25
J This control strategy is similar to on-off control except the motor and compressor
never completely turn off. Because the compressor does not turn off, the motor is
not damaged. However, load-unload control requires larger receiver capacity
and a significant variation in system pressure to create an acceptable cycle time.
C An unloaded screw compressor consumes approximately 17 percent to 25
percent of the energy required for the compressor to operate at full capacity, if
discharge pressure is reduced to near atmospheric pressure. The energy
savings will be less if the compressor discharge pressure drops to an
intermediate pressure, such as 30-40 psig, which is usually required to
maintain oil circulation.
L Some processes are too sensitive to allow the variation in pressure necessary
to produce significant energy savings.
L The load-unload cycle can make maintenance personnel uncomfortable. It is
often set to unload at very low capacity causing the compressor to operate at
inefficient partial loads for most of the time. The compressor seldom unloads,
therefore potential energy savings are lost.
L A small amount of compressed air is released to atmosphere when the
compressor unloads. If the compressor cycles too often this air loss can be
significant.
J Energy Use: Where appropriate, this method of control has very good energy
use characteristics since it only produces air at 100 percent capacity and idles
with low energy use at other times. There will be a small loss of energy each
time the outlet blows down, because any compressed air preceding the check
valve will be vented to attain a lower pressure. The simplest way to estimate
energy use is to ignore these losses and those that may accrue as the intake
valve opens and closes. This may sound too simplistic, but the volume of air lost
will usually be less than 2 ft per cycle with most oil separators.
J The Load-Unload Controls graph above indicates that the compressor
operates at two points, full output (100 percent capacity and maximum
efficiency) or unloaded (0 percent capacity). This graph is for a compressor
that is completely vented to atmospheric pressure. A partially vented
compressor at 0 percent capacity will normally be near 25 percent of full load
power.
Bonneville Power Administration
26
Applications: Load-Unload control is most appropriate when conditions will not
cause unloading too often, though it can operate with more unloading cycles
than on-off controls can. An on-off controlled compressor would not be suited
to restart every 2 minutes, for example, but a load-unload controlled
compressor and motor could handle the cycling.
A plant with a large air storage capacity and equipment without
exacting pressure requirements is ideally suited for load-unload
control. Many lumber mills fit this category because they have
extensive piping networks that act as receiver tanks and if
necessary, space is usually available to install larger receiver
tanks.
Is Turn Valve control used?
Replace Turn Valve control with Load-Unload controls.
Turn Valve Control
How does it work? Turn valves or spiral valves are composed of a spirally
threaded shaft and discrete ports placed along the compression chamber
wall. The shaft lies parallel to the rotors. When the system pressure falls
below its maximum pressure set-point (usually 100 120 psig), the valves
are closed and the compressor runs at full capacity until the maximum
pressure is maintained. The turn valves allow the compressor to modulate
between full capacity and zero capacity. This modulating control is achieved
by gradually rotating the spiral shaft. As the shaft is rotated, the ports in the
shaft allow some of the air being compressed in the rotors to escape and
return to the compressor inlet, which is at atmospheric pressure (~0 psig).
The air that does not escape through these ports is discharged at system
pressure.
L Energy Use: This method is more efficient than throttling. However, since the
compressor works against system pressure at all times, this is still a relatively
energy-intensive modulation control strategy.
L The Turn Valve Controls graph above indicates that the compressor can
operate continuously at any point between 0 percent and 100 percent
capacity. This graph shows good performance at high loads, but about
Yes
Bonneville Power Administration
27
57 percent of full load power is still consumed when the compressor is
producing no air.
Applications: Turn valves are an effective control strategy when over-all plant
demand is high or erratic, when receiver size must be small, or when the
acceptable range for system pressure is small. Turn Valve modulation is a
low-risk option and consequently, a common control strategy. Though more
efficient than throttling, turn valve control is not desirable if extended low load
periods are expected.
Is Poppet Valve control used?
Replace Poppet Valve control with Load-Unload controls.
Poppet Valve Control
How does it work? Poppet valves operate using the same principle as the turn
valve: Opening discrete ports in the compression chamber walls reduces the
volumetric compression ratio. Instead of using a single rotating shaft, four or
five pneumatic valves open and close to expose the ports and allow the
compressed air to escape to the inlet, which is at atmospheric pressure.
L Energy Use: The energy use for Poppet Valves is similar to Turn Valve
control. The thermodynamics are the same only the mechanics of
implementation vary. Poppet Valves are more efficient than throttling but the
compressor still works against system pressure. Consequently, Poppet
Valves are a relatively energy-intensive control strategy.
L The Poppet Valve Controls graph above shows good performance at high
loads, but about 60 percent of the full load power is still consumed when the
compressor is not producing any air.
Applications: Applications for Poppet Valve control are the same as those for
Turn Valve modulation controls.
Yes
Bonneville Power Administration
28
The following is a discussion of additional control methods that might be
applicable.
On-Off Control
How does it work? The compressor runs at 100 percent capacity until the
system pressure reaches the maximum set point pressure. Then both the
compressor and motor completely shut off. A check valve prevents the flow
of air back through the compressor. When the compressor shuts off, an
unloading valve opens so that air in the discharge port is released to
atmospheric pressure. This reduction in discharge pressure makes it easier
for the compressor to restart.
On-off control allows a compressor to operate at full output and maximum
efficiency and then turn off. However, on-off control requires larger receiver
capacity and a significant variation in system pressure. On-off control is not
usually used in an industrial setting except as a secondary control on a
compressor that may operate at low to zero capacity for an extended period of
time.
L Some processes are too sensitive to allow the variation in pressure
required for on-off control.
L Beware of installing on-off control as a sole control on large motors. The
constant on-off cycle can reduce the life of the air compressor and motor.
L On-off control may not be an option with many compressors.
J Energy Use: This control strategy is actually the most efficient mode. Since
a compressor operating in this mode only produces air while running at 100
percent capacity and never idles, performance approaches the "ideal," as
shown in the On-Off Controls graph below. There will be modest losses
because any compressed air that is upstream of the system pressure check
valve will be lost once the compressor is shut down. For example, a system
that runs 6 minutes per cycle will likely have losses of less than 3 percent.
Applications: This type of control strategy works best when the user is confident
that there will be long periods of either very high or very low use, and when the
maximum and minimum pressures are not close together. Large receivers
Bonneville Power Administration
29
are required for efficient operation. A small plant with an occasionally used
sandblaster would be an appropriate application for this control strategy.
Bonneville Power Administration
30
Low- Unload Control
How does it work? Low-Unload control is a combination of Load-Unload
control and modulation. The modulation may be a throttling valve, a turn valve
or a poppet valve. This control strategy is designed to allow the compressor
to modulate during periods of high demand and unload if demand drops below
a certain percentage of full load capacity. The unloading point is usually set at
4050 percent capacity and may be permanently pre-set by the manufacturer
or it may be manually adjustable.
The compressor runs at 100 percent capacity and gradually increases the
system pressure, but before the maximum pressure is reached, the inlet control
starts to modulate and the capacity begins to reduce. This modulation continues
until it either balances compressed air demand with supply, or until the capacity
falls to the unloading point (40-50 percent capacity), whichever comes first. If the
unloading point is reached, the compressor drops to an unloaded idle condition,
as described in the Load-Unload section, and waits until the system pressure
drops to the minimum allowed. At this point, the modulating valve fully opens, the
blow-down valve closes, and the compressor returns to full capacity.
L A low-unload controlled screw compressor is no more efficient than a
standard throttle controlled compressor until it unloads. Unfortunately
they are often set to unload at low flows, sometimes as low as 40 percent
of capacity. Because of this, they only unload during periods of minimum
demand, such as breaks or non-production periods. During normal
production periods, the compressor capacity is throttle-controlled and
potential energy savings are lost.
C The unloaded compressor consumes approximately 17 percent to 25
percent of full load power when the air is discharged at atmospheric
pressure.
J Energy Use: The energy efficiency of low-unload controls falls between that
of load-unload control and modulation-only control. Since the operating mode
varies depending on the magnitude and regularity of the plant air demand,
receiver size, pressure range, and unload point, it is not easy to make a
simple mathematical model. However, as an example the following simplified
form can be used. Assuming inlet throttling modulation is used, the unload
point is set at 50 percent, the compressor completely unloads to atmospheric
pressure, and unloading losses are ignored, energy use can be approximated
as shown in the Throttle + Low-Unload Controls graph below:
Bonneville Power Administration
31
Note: In cases where the unload point is adjustable, it is recommended that
the unload point be increased as high as possible, 80 percent capacity
for example, until the cycle time is as short as deemed acceptable for
operation. A minimum unloaded time of 30 seconds under normal
plant demand conditions is suggested. The energy savings can be
seen graphically by looking at the Throttle + Low-Unload Controls
graph above. If the unloading point is moved to the right (increased),
from 50 percent to 80 percent, the total area under the curve is
reduced; therefore, additional energy savings is possible.
L Note: Since spiral/turn/poppet valves are already efficient in the
higher capacity region, available savings from increasing the
unloading point are less significant for compressors with this
type of control. This can be seen by referring to the Turn
Valve + Low-Unload Controls graph above, if the unloading
point is moved from 40 percent to 80 percent, the area under
the curve is not significantly reduced.
Application: Low-Unload is a good compromise between Modulation and
Load-Unload. It does not outperform either of the other two modes if the
operating conditions match the requirements of modulation or load-unloading.
Bonneville Power Administration
32
Low-unload control excels when load conditions vary over the course of a day.
An example of an appropriate application of low-unload control would be a
plant where there is a steady high load during first shift, intermittent demand
on second, and holding pressure for a fire system at night. In this case, the
compressor would mostly modulate during first shift, modulate and unload
during second shift, and load-unload at night. Since this type of situation is
common in industrial facilities, this control strategy is frequently the preferred
choice.
Variable Speed Drive (VSD) Control
How does it work? A compressor system with a variable speed drive (VSD)
controls the compressor output by changing the rotational rate (rpm) of the
screws. When air demand is high, the screws rotate faster and therefore
displace more air per minute than when demand is low and rotation is slower.
Typically a minimum speed is set based upon the minimum internal pressure
required to provide proper sealing of the compression chamber. This may
require modulation or unloading control to be incorporated with the VSD
control to drop capacity without further slowing the screws.
J Energy Use: VSD control offers modulation down to low loads while still
maintaining efficiency.
Like low-unload controls, there are two different operating modes. During
periods of high demand, the VSD controls the modulation. If the load drops
below the minimum level that can be compensated for with the VSD, the drive
will stop reducing speed and the capacity will be further reduced with a
butterfly, slide, turn, or poppet valve arrangement.
Note: VSD + Throttle Controls graph shows VSD control down 40%
capacity and Throttle Control down zero to 40% capacity.
J Applications: VSDs can be the most expensive of all of the control options
and are not typically offered by compressor manufacturers as a standard
configuration. When combined with modulation, however, VSDs have the
Bonneville Power Administration
33
singular advantage of offering relatively high efficiency across the full capacity
range with the convenience of full modulating control. VSDs would be
appropriate when extended low demand periods are expected and a range of
supply pressures is unacceptable.
The Combined Part Load Performance graph compares the performance of all
of the control methods discussed.
$ Look for or Ask? (continued)
Does the facility have more than one compressor feeding into a common header?
Are these compressors operating at less than full output (cfm) capacity?
When more than one compressor is operating, all but one should operate at full
capacity and efficiency. A final trim compressor can match output to system
requirements. In the best case, the trim compressor can have more sophisticated
controls for greater efficiency at part load operation.
Manually sequence multiple compressors.
Set existing controls to load compressors sequentially so that unneeded
compressors can be turned off manually.
Install automatic compressor sequencing controls.
Sequence compressors to avoid operating several compressors at part
load and poor efficiently. The largest savings come from the sequencer
turning unneeded compressors off. The energy savings usually offset the
cost of installing additional receiver capacity.
Are compressors operating at zero capacity for extended periods of time?
Manually shut of air compressor.
If an air compressor is left on over the weekend or through the night, it can
be turned off manually.
L This measure is only as reliable as the operator(s).
Install shut-off timers on air compressors.
Shut-off timers can be set to de-energize a compressor if it operates at zero
capacity for a set period of time. This can work particularly well if air may
Yes
Yes
Bonneville Power Administration
34
be needed for short periods such as during night clean-up. The compressor
will shut off at the end of the production shift and only start up again when
needed.
Is the discharge pressure of the compressors higher than 110 psig?
If compressors are operating in a range higher than 90 to 110 psi, determine if this
higher pressure is required. Common end uses frequently require no more than 80
psi. It is also common to operate from 100 to 110 psi to overcome any potential line
losses. It is possible to have end use air requirements greater than 110 psig, but
verify them. Even 90 to 110 psi can be higher than required to ensure adequate air
delivery to the end use. It wastes energy to compress air to a higher pressure
unnecessarily. Higher system pressures also cause unregulated air uses to expend
more air. (Any end use that does not include a regulator to keep air pressure from
exceeding required pressure is an unregulated air use. System air leaks are an
unregulated use common to all compressed air systems)
C The power required to compress air increases by about 0.5 percent for each psi
increase in system discharge pressure.
Reduce pressure delivered by air compressor to the minimum required by the
system.
Determine required end use pressures on equipment, then group them
by requirements. This will help establish the actual discharge pressure
required.
Install looped piping system.
A looped piping system balances pressure throughout the plant. End uses
are served from both directions, with line losses at different points balancing
out in the two paths. With a balanced system compressor discharge
pressures can often be reduced.
Install larger pipes.
Larger pipes reduce the pressure loss in the distribution lines while providing
additional surge capacity to reduce pressure fluctuations. Both effects help
reduce system pressure, which reduces the energy consumption.
Is high pressure air being used for tasks that do not require high pressure air?
Compressed air may be used for inappropriate applications such as part drying or
aeration. A low- pressure blower or fan may be a better choice. Power is wasted to
compress the air to higher pressures than needed.
Meet end use requirements with lower pressure air delivery sources such as
a blower, fan, or a smaller horsepower air compressor.
Does the compressed air system have significant air leaks?
Most leaks are difficult to pinpoint and quantify on a leak-by-leak basis. Some leaks
are easy to find because of their location, sound, and air volume. Some leaks are
intentional; such as an open compressed air line directed to cool a hot bearing.
Leaks are easiest to find when the plant is quiet - plant is not in production
operation such as during lunch.
To quantify total air leaks in a plant: take note of air compressor loading
and/or air delivery during breaks or other times when there is no air use.
Yes
Yes
Yes
Bonneville Power Administration
35
Ultrasonic tools provide the most reliable method to locate air leaks.
Common leak locations: valve packing, pneumatic cylinders, and hoses,
quick release hose fittings for hand equipment, hand equipment itself.
C Air leaks exceeding 35 percent of the air used are excessive in any plant
(plant load can be determined by subtracting cfm leak load found during the
break period from the compressor cfm recorded during plant operation.)
C The table below gives estimates of the annual costs for air leaks. Values are
based upon a 1000 ACFM screw compressor operating at 100 psig with a
compressor efficiency of 1 hp/ 5 cfm or 20 percent .The compressor motor
has an efficiency of 90 percent. Intake air is at 70F, 14.7 psia. Compressor
operates 12 hrs/day x 5 days/wk x 50 weeks/yr = 3000 hrs/yr. Cost of
electricity is $.05/kWhr. This equates to an annual cost of approximately
$25/cfm of leaks.
Opening
Diameter
1/64 1/32 1/16 1/8 1/4 1/2
Air escaping at
each leak
.50
CFM
1.5
CFM
6.5 CFM 26 CFM 104
CFM
415
CFM
Annual kWh 249
kWh
746
kWh
3,233
kWh
12,931
kWh
51,723
kWh
206,393
kWh
Annual cost $12 $37 $162 $647 $2,586 $10,320
(Savings with reduced airflow depends on the air compressors part load
efficiency)
J Example: For a compressed air system operating at 100 psig, one air leak
1/8in diameter will loose 26 ft
3
of air per minute. The power loss due to this
air leak is:
kWh/yr = ( ) , / 931 , 12
3000
) 90 )(. (
746 .
5
1
26 yr kWh
yr
hrs
x
eff Bhp
Kw
x
cfm
Bhp
x cfm
1
]
1
The annual cost = yr
kWh
x
yr
kWh
/ 647 $
05 $. 931 , 12
,
_
,
_
Repair air leaks
By reducing the air leaks, the compressors can operate at a lower discharge
pressure. In the best cases, reducing the air leaks can allow compressors to
be shut off.
* If the leak reduction does not allow one compressor to be shut off,
consider a control strategy for efficient part load operation to realize
significant savings.
Yes
Bonneville Power Administration
36
Does the facility have rotary vane air compressors?
The capacity of rotary vane compressors is commonly controlled by blowing off
excess air to atmosphere. In such cases there is no reduction in power with reduced
airflow.
Replace rotary vane compressors with energy efficient centrifugal screw
compressors that are computer controlled to allow sequencing and
unloading.
Does the facility have desiccant air dryers?
Desiccant air dryers can produce very dry air, however, they use more energy than
refrigerated dryers. Determine if the increased drying capacity is necessary.
Heaterless desiccant air dryers purge the most amount of air and can waste the most
energy.
C From 10 percent to 15 percent of total air produced by the air compressor can
be purged in regenerating a heaterless desiccant dryer
Replace desiccant air dryers with refrigerated air dryers.
Install a capacity controlled regenerative dryer.
If drier air is required, control the desiccant recharge cycle to stop when the
humidity drops to a set level. The amount of savings will depend on the
amount of air being used.
Install internally heated desiccant air dryers.
If drier air is required, internally heated desiccant dryers only require 3to5
percent of the total airflow for purging moisture. Isolate moisture sensitive
equipment if possible, such as pneumatic controls, which can be particularly
sensitive to moisture. It is unnecessary to dry all of the plant air to the level
required by a minority of the equipment. If the sensitive equipment is
grouped on one branch of the compressed air circuit, a desiccant dryer can
serve that line only and drying costs can be greatly reduced.
Is the compressor cooling water discharged to the sewer?
Use compressor cooling water to replace warm water for other uses, such as
cleaning or pre-heating the boiler makeup water.
This strategy can save on both energy and water costs.
N Oil contamination potential in the compressor cooling water can present
a problem to be overcome. Although more costly, a heat exchanger to
transfer heat from the air compressor cooling water to preheat the
boiler make up water might be a better option.
Is the pressure drop across auxiliary equipment such as dryers, oil separators, or
filters excessive?
Some compressors display pressure drop across these devices. Pressure drop should
not exceed 8 to 10 psig; for oil separators, 5 psig for a dryer, 0.5 to 1 psig for a
filter.
Replace filters, overhaul equipment to reduce pressure drop.
Clogged filters and fouled lines increase air velocity and pressure drop.
Yes
Yes
Yes
Bonneville Power Administration
37
Size equipment to accommodate air flow with acceptable pressure drop.
Equipment such as a refrigerated dryer causes excessive pressure drop when
airflow exceeds design.
Is compressed air the best utility for the given application?
Compressed air is often chosen for its convenience; its safety in explosive situations;
and its comparatively high energy density for hand held tools, robotics, or other
equipment. Unfortunately it can be an inefficient method of getting the work done.
Replace compressed air use with another utility. For example, replace a
pneumatic motor with an electric motor or hydraulic motor.
Replace a venturi-type vacuum generator with a vacuum pump.
Does the facility utilize any air nozzles?
Have the air nozzles been designed for maximum efficiency?
Install engineered nozzles.
These nozzles are typically used for blowing off parts of equipment, cutting
or cooling. Commercially available engineered nozzles have higher
efficiencies and use less air.
Is the Air Compressor on a Regular Maintenance Schedule? Review maintenance
logs to verify if the following is being done on a scheduled basis.
Maintain modulating controls.
Modulating controls on screw compressors can fail over time. The result is a
compressor that never operates at full load or unloads properly, reducing
both efficiency and capacity.
Lubricate compressor.
Proper lubrication extends compressor life and improves its efficiency.
Clean or replace intake filter.
A clogged intake filter reduces compressor capacity and efficiency.
Yes
Yes
Yes
Yes
Bonneville Power Administration
38
Steam Systems
2 General Notes:
C A 1/8 hole will lose 600 Mbtu/yr of steam in a 100 PSI system
C Estimate 1 percent reduction in boiler efficiency for every 40F increase in stack
temperature.
7 Please refer to the following web sites for additional information:
http://www.oit.doe.gov/bestpractices/steam/totalsteam.shtml, http://www.ecw.org
C Combustion efficiency and boiler operating targets for different fuels:
Fuel Efficiency
Target
Excess
Air
Oxygen
(O2)
Carbon
Dioxide
(CO2)
Other
Natural
Gas
80% - 83% 21% -
28%
4% - 5% 9.0% - 9.6% 400 ppm Carbon
Monoxide (CO)
Oil 84% - 87% 22% -
29%
4% - 5% 11.9% -
12.6%
1 - 2 smoke test
Coal 83% - 84% 26% -
34%
4.5% -
5.5%
13.7% -
14.6%
Wood 65% - 75% 61% -
74%
8% - 9% 11.7% -
12.6%
$ Look For or Ask ?
Is the stack temperature too high?
Optimum stack temperature is typically 50F to 100F above saturated steam
pressure at high fire in a saturated steam boiler.
A record of the stack temperature after boiler tuning offers a more accurate target
for optimum operation.
C Stack temperatures higher than these suggest poor heat transfer or too much
combustion air.
Boiler
Pressure
Recommended
Maximum
Stack
Temperature
30 psig 375 F
75 psig 420 F
100 psig 440 F
125 psig 455 F
(No more than 100 F greater than saturated
steam pressure at boiler operating pressure)
Yes
Bonneville Power Administration
39
C Stack temperatures lower than 275 F can lead to corrosive condensation
Tune the Boiler. [Reduce excess combustion air]
N Be sure not to reduce excess air below minimum required to avoid
creation of carbon monoxide.
Clean the boiler to remove water side and fireside fouling.
C Soot can usually be removed with a brush during regular maintenance.
C Scale on the water side may require extensive chemical treatment if
deposits are severe.
Preheat combustion air.
C Stack gas temperature should typically be over 400F on a well tuned
boiler for this to pay off.
Is the boiler operating at incomplete combustion?
Incomplete combustion is difficult to ascertain without a stack gas analyzer.
Excessive soot buildup, or fuel consumption for the boiler load might be an
indicator. A stack gas analyzer will allow the operator to compare O
2
and CO
2
levels to optimum levels for efficient operation.
Tune the Boiler.
Is the blow-down of the boiler water manually controlled?
As water is evaporated to steam, solids in the water remain in the solution. To keep
dissolved solids from building up to excessive levels, the boiler water is drained and
replaced with fresh water. This is called blow-down. The difference in
temperature between the replacement water and the hot boiler water represents an
energy loss. To minimize this loss, blow-down should be set to the minimum required
to keep dissolved solids at an acceptable level. The rate of continuous blow-down
depends on the quality of the feed water and the amount of condensate return.
J Reducing the blow-down will also reduce the amount of water treatment
chemicals required.
Set the blow-down based upon the amount of total dissolved solids.
Does the facility have a significant number of steam traps that are malfunctioning?
Steam traps are usually designed based upon a maximum back pressure rating. This
rating is determined by dividing the outlet pressure by the inlet pressure, absolute
(psia). If the back pressure of the present system is greater than the original design
pressure, the trap is not able to fully close, and can fail in the open position. When
these traps fail open, they blow steam into the return system, which increases the
back pressure on other traps in the system, causing them to fail. When the steam is
induced into the return piping, the vapor flows over the condensate, eventually
causing enough turbulence to create a mass or slug of condensate that fills the
pipe.
The condensate slug can travel throughout the piping system at the same velocity as
the steam until it encounters a sudden change in direction and this energy is
transferred into a force referred to as water hammer. It can be difficult to identify
traps that are leaking, failed open or failed closed. When properly designed and
maintained, steam traps remove the condensate from the steam and purge air and
Yes
Yes
Yes
Bonneville Power Administration
40
other non-condensable gases from the steam system which increases its thermal
efficiency.
J The most reliable method to identify traps that are malfunctioning is to use
ultrasonic tools.
Initiate a program to identify and repair traps that are malfunctioning.
Consider installing continuously discharging thermostatic steam traps.
Is the condensate return system open to atmosphere?
Hot condensate will travel in the direction of high pressure to low pressure. When
the feed tank is vented to atmosphere, as the condensate enters the feed tank, it will
flash to steam due to the sudden drop in pressure and the steam escapes through the
vent to atmosphere. The steam and associated energy is lost.
Install properly designed steam traps to reduce the amount of steam lost
through the open system.
Install pressurized condensate return system to reduce flash steam losses.
Insulate Condensate Storage Tanks.
Is an open condensate return system utilized?(condensate not returned to the boiler)
If condensate is not returned to the boiler all of the energy in the hot condensate
return is lost. Since this condensate also contains water treatment chemicals, these
chemicals have to be replaced. The energy and wastewater treatment costs will
increase.
L This loss has to be balanced against the significant cost of adding a
condensate return system. In large facilities, the installation of a condensate
return system may require extensive pumping, piping and valves.
Install a condensate return loop.
Does the boiler cycle frequently?
Boiler efficiency is reduced at partial load. Frequent cycling reduces the overall
operation efficiency and the life of a boiler. Continual cycling can be an indicator
of an oversized boiler.
Install multiple smaller boilers (modular).
Match steam load to the boiler output.
Is the efficiency and performance of the steam system being monitored manually?
Install a boiler stack gas thermometer with a maximum indicating hand.
Install a meter to measure the amount of boiler make-up water being
consumed.
Is the flow rate of the induced draft and forced draft fans being controlled by throttling
methods?
Install VSD control on boiler induced draft and forced draft fans.
H Boilers typically operate 24 hours a day, 365 days per year. Improving the
efficiency of any equipment associated with the day-to-day operation of the
boiler will produce significant energy savings.
Yes
Yes
Yes
Yes
Yes
Bonneville Power Administration
41
Are there any opportunities for heat recovery?
Install heat exchangers to use the stack gases to preheat the boiler make up
water. Waste heat from air compressors or other equipment can be used for
this application. Use high pressure condensate to create flash steam for low
pressure heating service.
Yes
Bonneville Power Administration
42
Refrigeration Systems
2 General Notes:
C Compressor energy use drops 1 - 1.5 percent for each F of head pressure drop.
C Compressor energy use drops 2 - 3 percent for each F of suction pressure
increase.
1 Please refer to the following web sites for additional information: http://www.ecw.org,
http://www.oit.doe.gov, http://www.ecw.org/products/commindu.html#502/
Simple Refrigeration Cycle
Note: The Simple Refrigeration Cycle diagram is for information only and will be
described in detail at a later time.
1
2
3
4
Low Pressure,
GAS
HIGH
Pressure,
LIQUID
Low Pressure,
LIQUID/GAS
mix
HIGH
Pressure,
GAS
C
O
M
P
R
E
S
S
O
R
CONDENSER
T
H
R
O
T
T
L
E
V
A
L
V
E
EVAPORATOR
Cooling
water
Bonneville Power Administration
43
$ Look For or Ask?
Can the operation of the existing refrigeration system be optimized by implementing
any of the following measures?
Optimize inter-stage pressure.
A two-stage system has three separate pressures maintained by high- and
low-stage compressors. Choose intermediate pressure so that each
compressor has approximately the same pressure ratio to minimize
compressor energy use.
Economized single stage system.
For applications that require extremely low temperatures such as a blast
freezer, a two- stage compressor is usually preferred. An economized
single stage system may allow operation at slightly lower suction
temperatures while providing the necessary cooling and avoiding the cost of
a two-stage system.
Install 2-speed or VSD speed control on condenser and evaporator fans.
By reducing fan speed when full capacity is not needed, the energy
consumption of the fan motors is significantly reduced.
Cycle evaporator and condenser fans.
Evaporator fans move air across refrigerant coils to condition the space.
Condenser fans remove the heat generated during compression of the
refrigerant. Evaporator fans can turn off when not needed for temperature
control or to de-stratify air in the space. Cycling fans saves fan and
compressor energy. Duty cycles can be reduced as much as 50 percent. A
timer can be used to cycle primary fans after a given amount of operation
Are refrigeration compressors being operated manually or semi-automatically?
Install computer controls to allow the compressors to operate at their highest
efficiency point.
Overlap suction pressure switches on compressors connected to a common
header to allow their operation to be sequenced.
Is it necessary to operate at lower suction pressures in order to maintain production
rates or to maintain the desired storage temperature?
Poor cooler/freezer insulation, undersized or dirty evaporators require lower suction
pressure and wastes energy.
Consolidate and re-pipe loads with similar suction requirements. Dedicate
a compressor to these loads.
Compressors operating at their maximum suction pressure are more
energy efficient.
Reset suction pressure.
Raise suction pressure to match the actual pressure required to meet the
cooling loads.
When the suction pressure drop increases, compressor work increases.
Add evaporator capacity to reduce evaporator approach temperature and
raise suction pressure.
The compressor savings resulting from operating at higher suction
pressures often offset the additional evaporator fan energy consumed.
Yes
Yes
Yes
Bonneville Power Administration
44
Are back pressure regulators (BPRs) used in order to control suction pressures to
accommodate a significant portion of the load?
BPRs control system branch pressure.
Eliminate BPRs.
BPRs control various refrigeration loads on a single system. Loads
requiring a lower suction pressure could be separated from loads
requiring a higher suction pressure.
Can the timing of heavy process or other refrigeration loads be distributed better?
Consider load shifting during periods of high energy use and or thermal
storage during periods of low energy use to reduce the total energy demand.
Are head pressures significantly higher than rated pressures?
Minimum Head Pressure
Ammonia 93 psig
R12 72 psig
R134a 72 psig
Set the system to operate at lower head pressures.(Minimize the lift)
Flash gas caused by system losses at low discharge pressure can be avoided with
a liquid pressure amplifier (LPA) pump.
LPA pump is a small horsepower pump with a magnetically driven impeller
installed at the outlet of the condenser to increase the pressure and subcool
the refrigerant before it enters the expansion valve. This allows the
compressor to operate with a lower discharge pressure.
Install a Thermosyphon cooling system to cool the compressor oil.
Oil is used to seal, cool, and lubricate screw compressors. L Liquid-refrigerant-
injection cooling uses 5-15 percent of compressor power to recompress
refrigerant.
A thermosyphon system cools the oil with a heat exchanger by transferring
the heat from the oil to the refrigerant, which causes it to change from a liquid
to a vapor. The refrigerant vapor rises to a condenser where it condenses to
a liquid and the cycle is repeated. This process requires less energy to cool
the oil than liquid refrigerant injection.
Install additional condensing capacity to reduce discharge pressure.
Additional condensing capacity will bring the liquid refrigerant temperature
closer to the wet bulb temperature, therefore increasing the heat transfer
efficiency.
Are the compressors on a regular maintenance schedule? If so, verify that the
following is being done on a scheduled basis.
Maintain evaporative condensers.
Yes
Yes
Yes
Yes
Bonneville Power Administration
45
Water evaporates as it absorbs heat from the condensing refrigerant. The heat
exchange surface must be clean and free of corrosion. Air must pass through
freely for efficient heat transfer. Water should be treated to reduce scale and
corrosion, and reduce biological growth.
Purge non-condensable gasses.
Non-condensable gasses such as air or CO
2
reduce the effective surface area of
the condenser used to condense refrigerant vapor, thereby decreasing heat
exchanger efficiency. In general, non-condensables enter the system when the
low stage suction pressure is less than atmospheric pressure. Automatic purging
controls are readily available. The system can also be purged manually when an
operator notices as increase in the discharge pressure. A refrigeration log helps
identify when operating conditions change.
Can the evaporator defrost control be optimized?
Evaporator coils must be free of ice for maximum heat transfer.
Avoid excessive defrost times - reduce defrost times.
Warm fluid (refrigerant gas or water) commonly is used to defrost
evaporators. Heat will warm the space after the ice has melted. Airflow
sensors and thermocouples can control the defrost system to stop as soon as
the ice has melted.
Use Hot gas defrost instead of electric defrost.
High-pressure refrigerant is more efficient than electric heaters.
Use water defrost instead of hot gas defrost.
Hot process water can also defrost the evaporator. Additional compressor
energy is not required. This can be more efficient and faster in a blast
freezer, for example, where the defrost can occur with water without the
product being present.
Are there any opportunities for Heat Recovery?
Utilize waste heat off of condensers.
Use waste heat to preheat process water.
Insulate Cooler/Freezer area.
Unnecessary heat gain decreases system efficiency.
Yes
Yes
Bonneville Power Administration
46
Material Handling Systems
2 General Notes:
7 The following option should be considered when exploring opportunities to save
energy with material handling fans and blowers:
For belt driven devices, the speed can be reduced by re-sheaving the motor to
determine the minimum speed allowed to move the material and avoid design and
safety problems. After this speed is determined, the actual motor rpm can be
measured with a tachometer. The proper drive mechanism can be selected.
(VSD, two-speed motor, an energy efficient motor at reduced rpm and
horsepower, etc.)
L This approach can provide energy savings at the least cost. The preferred
method is to evaluate the entire system and to size the fan and motor to efficiently
handle the present operating conditions.
1 For additional information, please refer to the following web sites:
http://www.energy.wsu.edu/industry/research.htm, http://www.ecw.org
$ Look For or Ask?
Does the facility utilize high or low pressure blowers to convey material?
The following energy savings opportunities should be evaluated:
Reduce the speed of the blower or fan to capture the energy savings and
reduce the wear and tear on the distribution piping by reducing the
velocity.
Replace Dust Collection System Material Handling fans with High
Efficiency Clean side fans.
Install high efficiency bag houses.
Replace Pneumatic chip transfer with conveyors or vibrating transfer
systems.
Does the facility have more than one baghouse and multiple distribution lines feeding
into these baghouses?
Determine if these distribution lines can be valved/knifed off when not
operating to reduce the load on the fan and baghouse.
Determine if these distribution lines should be re -routed to allow a dedicated
fan that requires less horsepower to perform the same task.
Quite often the plant distribution lines, fans, and blowers have been modified
over the years and are not operating under design conditions and could be
wasting a lot of energy.
Yes
Yes
Bonneville Power Administration
47
Hydraulic Systems
2 General Notes:
1 For additional information, please refer to the following web site:
http://www.energy.wsu.edu/industry/research.htm#hydraulic
$ Look For or Ask?
Does the manufacturing process utilize hydraulic pumps?
The following energy savings opportunities should be evaluated:
Install accumulators.
Accumulators can improve the efficiency of the hydraulic system by
maintaining system pressure and allowing the pump to unload or to do
other work. This reduces the amount of times the pumps cycle on and
off. They also compensate for changes in pressure due to leaks and
thermal expansion of the working fluid.
Install a variable speed drive on the hydraulic pump.
The variable speed drive varies the pump speed to match the hydraulic oil
needs of the system. This provides smooth response and can result in
significant energy savings.
Install variable displacement pump for variable hydraulic loads.
Install pressure compensation to unload the hydraulic pump.
Yes
Bonneville Power Administration
48
Injection Molding or Extrusion
2 General Notes:
1 For additional information, please refer to the following web sites:
http://www.energy.wsu.edu/industry/research.htm
http://www.oit.doe.gov/pdfs/bestpractices.pdf
http://www.ecw.org
$ Look For or Ask ?
Does the manufacturing process involve Extrusion or Injection Molding?
The following energy savings opportunities should be evaluated:
Install a variable-speed extruding machine.
The drive runs at the minimum speed necessary for the product being produced.
The input signal to the drive is typically a 4 to 20mA control signal that maintains
the desired set-point.
Insulate heater bands to reduce thermal losses.
Grind and reuse reject parts and trim pieces.
Is a chiller used to cool the hydraulic oil?
Cool the hydraulic oil with a closed-loop cooling tower circuit.
Yes
Yes
Bonneville Power Administration
49
Veneer Dryers
2 General Notes:
1 For additional information, please refer to the following web sites:
http://www.energy.wsu.edu/industry/research.htm
http://www.oit.doe.gov/pdfs/bestpractices.pdf
1 http://www.amca.org/
$ Look For or Ask?
Does the manufacturing process involve the use of Veneer Dryers?
The following energy savings opportunities should be evaluated:
Perform an air balance on the dryer.
Provide uniform drying, sufficient air circulation, optimize air contact with
product.
Install electronic dryer controls (VSD) to control drying time.
Install VSD fan control if there is a significant variation in species and
moisture content of the product being dried.
Plastic bearings reduce friction loss and last longer than carbon/steel
bearings.
Investigate alternate drying methods
- Infra-red
- Microwave
- Radio frequency
Preheat dryer makeup air with heat from exhaust.
Yes
Bonneville Power Administration
50
Kiln Drying
2 General Notes:
1 For additional information, please refer to the following web sites:
http://www.energy.wsu.edu/industry/research.htm
http://www.oit.doe.gov/pdfs/bestpractices.pdf
http://www.amca.org/
$ Look For or Ask?
Does the manufacturing process involve Kiln Drying?
The following energy savings opportunities should be evaluated:
Retrofit kiln fans to maintain optimum speed throughout the drying cycle
by installing VSD fan control.
Repair baffles, stack lumber and trim ends to prevent the airflow from
short circuiting the load.
Install zone temperature control to save energy and improve uniformity of
drying.
Install steam recovery.
Energy Management
The following energy savings opportunities should be considered:
Have the utility explain how the total energy consumption, demand
charges, and power factor penalties are determined for the facility.
Discuss options to reduce these charges.
Switch to a different billing schedule if applicable.
Consolidate accounts.
Install power factor correcting capacitors - individual capacitors on
motors, or automatically switching banks at the facility service entrance to
minimize power factor penalties.
Install demand controller/ load shedder to reschedule/distribute high
demand loads to reduce demand charges.
Install temporary or permanent meters to validate the billing data for
electricity and water consumption.
Yes
ADJUSTABLE SPEED DRIVE ENERGY SAVINGS
CALCULATOR
~ Fan and Pump Applications ~
100.00 hp
95.00 %
95.00 %
74.60 KW
Enter Hours per year fan operates: 8760 hrs/yr
Enter Energy Charge: 0.05 $/kwh
1 Inlet Guide Vane, FC Fans 4 Outlet Damper, FC Fans
1 2 Inlet Guide Vane, BI & Airfoil Fans 5 Outlet Damper, BI & Airfoil Fans
3 Inlet Damper, General Curve 6 Eddy Current Drives 7 Measured kW
Percent of
Design Bhp Power (KW)
Percent of
Design Bhp Power (KW)
5.0% 20.00 1,500.0 14.92 5.90 4.40 4,607.15 230.36 $
5.0% 20.64 3,000.0 15.40 4.75 3.54 5,193.17 259.66 $
10.0% 21.57 16.09 5.37 4.01 10,585.98 529.30 $
10.0% 23.32 17.40 8.00 5.97 10,009.27 500.46 $
10.0% 26.44 19.72 12.89 9.62 8,852.26 442.61 $
10.0% 31.45 23.46 20.27 15.12 7,310.99 365.55 $
10.0% 38.92 29.03 30.38 22.66 5,581.51 279.08 $
10.0% 49.36 36.83 43.46 32.42 3,859.87 192.99 $
10.0% 63.33 47.25 59.75 44.57 2,342.13 117.11 $
10.0% 81.37 60.70 79.50 59.30 1,224.32 61.22 $
10.0% 104.01 77.59 102.93 76.79 702.51 35.13 $
100.0% Kwh/yr
existing
Kwh/yr
asd 60,269.16 3,013.46 $
60,269.16 KWH/yr 1,250.00 $
3,013.46 $ 2,799.82
1,549.82 $ 0.93 years
Sample Duty Cycle - LOW FAN LOADING
Sample Duty Cycles (use these as a guide if the duty cycle is not known)
Summary
Energy Savings: (Note 1)
Cost Savings:
Enter Materials Cost:
Enter Labor Cost:
Total Cost:
Simple Payback:
Sample Duty Cycle - HIGH FAN LOADING
10.0%
20.0%
30.0%
0.0%
ASD System Existing System
Power Analysis Savings Analysis
Motor Information
Facility Information
Flow Control Method and Fan Type
Refer to the Fan Types worksheet for more information
Enter Nameplate Horsepower:
Enter Nameplate Efficiency:
Enter Motor Load at Fan Design CFM:
Select Flow Control and
Fan Type Below
Power(KW) at Fan Design CFM:
Annual Energy
Savings (KWH/YR)
Annual Energy Cost
Savings
Duty Cycle
Enter
Percent of
Design
Capacity
(CFM)
60.0%
40.0%
50.0%
Enter Percent
of Time at
this Capacity
This calculator was developed by Chris Milan at the Bonneville Power Administration (BPA) and is intended to be used as an indication of the potential energy savings
and payback for ASD installations. (If you would like a copy of the ASDcalculator, please contact Chris Milan at mailto:cbmilan@bpa.gov). More extensive analysis
tools are available at: http://www.eere.energy.gov/industry.
80.0%
300,668.67 240,399.52
70.0%
100.0%
90.0%
Totals:
20
60
20
0
10
20
30
40
50
60
70
50 75 90
Percent of Design Capacity (cfm)
P
e
r
c
e
n
t
o
f
T
i
m
e
a
t
t
h
i
s
C
a
p
a
c
i
t
y
15
55
25
5
0
10
20
30
40
50
60
30 50 70 90
Percent of Design Capacity (cfm)
P
e
r
c
e
n
t
o
f
T
i
m
e
a
t
t
h
i
s
C
a
p
a
c
i
t
y
Page 1 of 1 Bonneville Power Administration, Portland, OR [Revision No. 1]
http://www.bpa.gov/Energy/N/Projects/Industrial/
ASD Fan Calculator AVAILABLE at
ADJUSTABLE SPEED DRIVE ENERGY SAVINGS CALCULATOR
~ Pump Applications ~
40.00 hp
95.00 %
80.95 %
25.43 KW
Enter Hours per year pump operates: 8760 hrs/yr
Enter Energy Charge: 0.05 $/kwh
1
Throttling Valve
4 Bypass, Recirculation Valve
1 2 Eddy Current Clutch 5
3 Mechanical (Torque Converter)
Existing
Percent of
Design Bhp
Do Not
Enter Data
Below
Existing
System
Power (kW)
Percent of
Design
(kW) for
ASD
System
ASD
System
Power (kW)
15.0% 55.21 100.0 14.04 27.45 6.98 9,276.48 463.82
55.0% 61.39 15.61 19.12 4.86 51,781.25 2,589.06
25.0% 67.19 17.08 14.32 3.64 29,439.12 1,471.96
5.0% 72.61 100.0 18.46 13.05 3.32 6,633.48 331.67
0.0% 77.65 19.74 15.30 3.89 0.00 0.00
0.0% 82.31 20.93 21.07 5.36 0.00 0.00
0.0% 86.59 22.02 30.37 7.72 0.00 0.00
0.0% 90.49 23.01 43.19 10.98 0.00 0.00
0.0% 94.01 100.0 23.90 59.53 15.14 0.00 0.00
0.0% 97.15 24.70 79.40 20.19 0.00 0.00
0.0% 99.91 25.40 102.79 26.14 0.00 0.00
100.0%
Kwh/yrexisting Kwh/yrasd
97,130.33 4,856.52 $
97,130.33 KWH/yr 500.00 $
4,856.52 $ 1,000.00 $
500.00 $ 0.21 years
Sample Duty Cycles (these can be used as a guide if the duty cycle is not known)
Sample Duty Cycle - HIGH PUMP LOADING Sample Duty Cycle - LOW PUMP LOADING
42,028.95 139,159.28
100.0%
90.0%
80.0%
Summary
Simple Payback:
Total Cost:
Labor Cost: Energy Savings: (Note 1)
Cost Savings:
Materials Cost:
Motor Information
Savings Analysis
Annual
Energy
Savings
(Kwh/yr)
Annual
Energy
Cost
Savings
($/yr)
60.0%
Totals:
40.0%
50.0%
Enter Nameplate Horsepower:
20.0%
30.0%
0.0%
ASD System Existing System
Select Flow Control
Method Below
Selection 5 allows Measured Power (kW)
readings to be used in the analysis
10.0%
Power Analysis
Enter Nameplate Efficiency:
Enter Motor Load at Pump Design GPM:
Enter Power(KW) at Pump Design GPM:
70.0%
Facility Information
Existing Pump Flow Control Method
Click to go to Pump Power Graphs for additional information
Enter
Percent of
Time at this
Capacity
Duty Cycle
Enter
Percent of
Design
Capacity
(GPM)
20
60
20
0
10
20
30
40
50
60
70
50 75 90
Percent of Design Capacity (gpm)
P
e
r
c
e
n
t
o
f
T
i
m
e
a
t
t
h
i
s
C
a
p
a
c
i
t
y
15
55
25
5
0
10
20
30
40
50
60
30 50 70 90
Percent of Design Capacity (gpm)
P
e
r
c
e
n
t
o
f
T
i
m
e
a
t
t
h
i
s
C
a
p
a
c
i
t
y
Page 1 of 2 Any questions? Please contact Chris Milan at cbmilan@bpa.gov [Revision No. 1]
ASD Pump Calculator
now Available:
http://www.bpa.gov/Energy/N/Projects/Industrial/