Calculation of Load Drop Compensation Settings: Substation: Moruya North Inputs Outputs

This document contains information about calculating load drop compensation settings for the Moruya North substation. It lists the inputs of full and light load voltages, currents, and power factor and outputs the recommended settings for resistance, reactance, and float voltage at no load to maintain voltage levels. It also contains a second calculation showing that with resistance of 1.08 ohms, the load drop compensation would provide a 5% boost to the voltage at full load.

Uploaded by

anuji
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views2 pages

Calculation of Load Drop Compensation Settings: Substation: Moruya North Inputs Outputs

This document contains information about calculating load drop compensation settings for the Moruya North substation. It lists the inputs of full and light load voltages, currents, and power factor and outputs the recommended settings for resistance, reactance, and float voltage at no load to maintain voltage levels. It also contains a second calculation showing that with resistance of 1.08 ohms, the load drop compensation would provide a 5% boost to the voltage at full load.

Uploaded by

anuji
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Calculation of Load Drop Compensation Settings

Substation: Moruya North

Inputs Outputs
Full Load Voltage 1.05 p.u.
Light Load Voltage 1.03 p.u. Float voltage @ no load 111.9 volts
Full Load 22 MW = 33.58 kV
Light Load 5 MW
Power Factor 0.95 Settings
CT primary 600 A for R only 1.08 ohms
CT secondary 5 A X only -5.15 ohms
CT phase Yellow R=X 1.36 ohms
VT primary 33000 volts Note : These settings are not actual dial settings
VT secondary 110 volts
VT connections Y-R

2351413.xls 03/22/2008
Calculation of % Boost for Known LDC settings

Substation: Moruya North

Inputs Outputs
Resistance (R) 1.08 ohms
Reactance (X) ohms Voltage boost @ full load
Float Voltage @ no load 111.9 volts (above nominal) 5.0 %
Full Load 22 MW
Light Load 5 MW Volts @ Light load 1.025 p.u.
Power Factor 0.95
CT primary 600 A
CT secondary 5 A
CT phase Yellow
VT primary 33000 volts
VT secondary 110 volts
VT connections Y-R

_ Boost 2351413.xls 03/22/2008