External Static Pressure Calculation: Hvac 16/27 M.M 4 June 2014 MA/CAL/16
External Static Pressure Calculation: Hvac 16/27 M.M 4 June 2014 MA/CAL/16
External Static Pressure Calculation: Hvac 16/27 M.M 4 June 2014 MA/CAL/16
AHU-UB_07
Qty.(2)
Al-Hazm Mall
HVAC
Project
Designed by
Project No.
M.M
Date
CFM
SIZE (MM)
LENGTH
B
FT.
DIA.
FT.
FT.
Sheet
16/27
Circ:
MA/CAL/16
4 June 2014
DUCT
SECTION
Al-Hazm Mall
FITTINGS
Br
R
FT.
FT.
of
27
/File
TOTAL
EQUIV.
AIR
FRICTION
EQUIV.
VELOCITY
DROP/100 FT
FRICTION
DROP
LGTH. (FT.)
LGTH. (FT.)
fpm
IN W.G.
IN W.G.
AC SUPPLY DUCT
1
9,600
1200
550
871.8
4.5
14.8
15.0
15.0
29.8
1448
0.07
0.021
9,600
1200
550
871.8 11.0
36.1
15.0
15.0
51.1
1448
0.07
0.036
9,600
1200
550
871.8
9.4
30.8
30.0
60.8
1448
0.07
0.042
8,340
1050
500
778.9
0.9
3.0
7,072
900
550
763.4
0.3
1.0
5,072
800
500
686.7
1.3
4,438
700
500
644.5
3,804
600
400
3,170
600
10
1,902
11
12
30.0
30.0
5.0
35.0
38.0
1575
0.09
0.035
10.0
40.0
41.0
1391
0.08
0.031
4.1
5.0
5.0
9.1
1233
0.07
0.006
1.5
4.9
5.0
5.0
9.9
1224
0.07
0.007
532.8
1.5
4.8
5.0
5.0
9.8
1535
0.14
0.014
400
532.8
1.4
4.5
10.0
25.0
29.5
1280
0.10
0.030
450
350
433
1.5
4.9
5.0
5.0
9.9
1163
0.11
0.011
1,268
400
350
408.8
1.3
4.1
5.0
5.0
9.1
869
0.07
0.006
634
350
350
382.6
1.2
4.0
0.0
4.0
496
0.25
0.010
30.0
15.0
0.249
AC RETURN DUCT
12
9,600
1200
550
871.8
4.5
14.8
13
9,600
1200
550
871.8
6.6
21.7
14
9,100
1200
550
871.8
4.0
13.1
15
9,100
1200
550
871.8
7.6
24.9
15.0
15.0
5.0
15.0
15.0
15.0
29.8
1448
0.07
0.021
20.0
41.7
1448
0.07
0.029
15.0
28.1
1372
0.06
0.018
15.0
39.9
1372
0.06
0.025
0.093
Abbreviations:
E = Elbow Equivalenght Length
15 Ft.
0.249
30 Ft.
VOLUME DAMPER ( x 3 )
0.375
15 Ft.
0.150
5 Ft.
0.093
0.150
SOUND ATTENUATOR
0.250
SUB-TOTAL
1.267
ADD 10%
TOTAL FRICTION DROP IN WG
0.127
1.394