Transformer / Reactor:: Typical Limiting Values of Sub-Station Electrical Equipment's

This document lists typical limiting values and permissible limits for testing various electrical equipment in sub-stations, including: 1. Transformers should have a minimum breakdown voltage of 600kV for oil at initial charging and 50kV during operation and maintenance. Oil moisture content should not exceed 15ppm initially and 25ppm during operation and maintenance. 2. Reactor vibration levels should not exceed 200 microns peak-to-peak and 60 microns on average. 3. Bushings should have a tan delta value below 0.007 and capacitance within 5% of specifications. Winding insulation resistance should be over 1000 megohms and tan delta below 0.007.

Uploaded by

Santhosh RM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views1 page

Transformer / Reactor:: Typical Limiting Values of Sub-Station Electrical Equipment's

This document lists typical limiting values and permissible limits for testing various electrical equipment in sub-stations, including: 1. Transformers should have a minimum breakdown voltage of 600kV for oil at initial charging and 50kV during operation and maintenance. Oil moisture content should not exceed 15ppm initially and 25ppm during operation and maintenance. 2. Reactor vibration levels should not exceed 200 microns peak-to-peak and 60 microns on average. 3. Bushings should have a tan delta value below 0.007 and capacitance within 5% of specifications. Winding insulation resistance should be over 1000 megohms and tan delta below 0.007.

Uploaded by

Santhosh RM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Typical limiting values of Sub-station electrical equipments.

1. Transformer / Reactor:
SL.
NO.
EQUIPMENT / TEST DATA PERMISSIBLE LIMITS REFERENCE
A)
Transformer oil
a) BDV
-At the time of first charging 600 kV (Gap 2.5 mm) Minimum IS 1866
-During O&M 50 kV (Gap 2.5 mm) Minimum IS 1867
b) Moisture content IS 1868
-At the time of first charging 15 PPM (Max.) IS 1869
-During O&M 25 PPM (Max.) IS 1870
c) Resistivity at 90 degree C 0.1-1012 Ohm-CM (Min.) IS 1871
d) Acidity 0.2 mg KOH/gm (Max.) IS 1872
e) IFT at 27 degree C 0.018 N/M (Min.) IS 1873
f) Tan delta at 90 degree C 0.20 (Max.) IS 1874
g) Flash point 126 Deg. C (Min.) IS 1875
B)
Vibration level for reactors 200 Microns (Peak to Peak) IS 1876
60 Microns (Average) IS 1877
C) Tan delta for bushing at 20 Deg. C 0.007* IEC 137
D) Capacitance for bushing + 5% variation IEC 138
E) IR value for winding 1000 M-Ohm By 5.0/10.0 kV Ins. Tester IEC 139
F) Tan delta for windings at 20 Deg. C 0.007* IEEE/C57.12.90.1980
G)
Contact resistance of bushing
terminal connectors
10 M. Ohm / Connector NGC.UK
Recommendations
H) Turret Neutral CT ratio errors 39 IS 2705