Class X Current Transformer

The document discusses sizing a Class X current transformer for use with high impedance differential protection relays. It provides a 4 step process: [1] calculate the knee point voltage, [2] calculate the transformer through fault current, [3] obtain the CT secondary winding resistance, and [4] obtain the pilot wire resistance. An example is then shown applying the sizing process to a 2500kVA transformer with a Class X CT ratio of 4000/5A and selecting a CT with a 185V knee point voltage.

Uploaded by

Vijay Pitchaiah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
50% found this document useful (4 votes)
1K views4 pages

Class X Current Transformer

The document discusses sizing a Class X current transformer for use with high impedance differential protection relays. It provides a 4 step process: [1] calculate the knee point voltage, [2] calculate the transformer through fault current, [3] obtain the CT secondary winding resistance, and [4] obtain the pilot wire resistance. An example is then shown applying the sizing process to a 2500kVA transformer with a Class X CT ratio of 4000/5A and selecting a CT with a 185V knee point voltage.

Uploaded by

Vijay Pitchaiah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Class X Current Transformer

Class X current transformer is use in conjunction with high impedance circulating current
differential protection relay, eg restricted earlh fault relay. As illustrated in 1EC60044-'1,
the class X current transformer is needed.

The following illustrates the method to size a class X current transformer.

Step l: calculating knee point voltage Vkp

Vkp = {2 x lft (Rct+Rw)}/ k
Vkp = required CT knee point voltage
lfl = max transformer through fault in ampere
Rct = CT secondary winding resistance in ohms
Rw = loop impedance of pilot wire between CT and the
K = CT transformation ratio


Class X Current Transformer
Step 2: calculate Transformer through fault lft

lft = (KVAx 1000)/(1 .732xVx lmpedance)

Where,
KVA = transformer rating in kVA
V = transformer secondary voltage
lmpedance = transformer impedance

Step 3: How to obtain Rct

To measure when CT is produce

Step 4: How to obtain Rw

This is the resistance of the pilot wire used to connect the class X CT at the transformer
star point to the relay in the LV switchboard.
Class X Current Transformer
Example:
Transformer Capacity : 2500kvA

Transformer impedance : 6%

Voltage system : 22kV/415 V
Current transformer ratio : 4000/5 A
Current transformer type : Class X
Current transformer Vkp :185 V
Current transformer Rct : 1.02 ohm
Pilot wire resistance Rw = 25 meters using 6.0mm sq cable
= 2x25x0.0032
= 0.16 ohm
Ift = (kVAx 1000) / (1.732xVximpedance)
= (2500 x 1000) / (1 .732 x 415 x 0.06)
= 57,968 round up 58,000 A
Class X Current Transformer

Vkp = {2xIft(Rct+Rw)}/k
= {2 x 58000 (1 .02+0.16) } /800
= 171.1V
Class X CT with knee point voltage of 185V is suitable to be use in this application.