SIMATIC ET 200M Systemredundancy

Siemens AG 2011. All Rights Reserved.

Redundancy with PROFINET

Possible Configurations
Ring struktur with standard-CPU (MRP) System redundancy with S7-400H

DP/ MPI

DP

Standard-CPU (IO Controller)


PN

DP/ MPI

DP

S7-400H
PN

DP/ MPI

DP

Sync

PN

Sync Sync PN Sync

PN

Sync

PN

PN

Sync

PN

ET 200M ET 200M ET 200M ET 200M

ET 200M

ET 200M

IM153-4 PN IO Standard

IM 153-4 PN IO High Feature

Page 2

Siemens AG 2011. All Rights Reserved. Industry Sector

Redundancy with PROFINET

Control of possible errors


3 1

1. Wire break of the ring 2. Power off / failure of a single station 3. Switch over time appr. 200ms

1. 2. 3. 4.

Wire break of the ring Power off / failure of a single station CPU failure Switch over time appr. 30ms autom. synchronisation at CPU change
Siemens AG 2011. All Rights Reserved. Industry Sector

Page 3

High-available automation system SIMATIC S7-400H with PROFINET I/O System Redundancy (SR)
Goals Overview Innovations Redundant Periphery Periphery Overview PROFINET I/O PROFIBUS I/O High-available communication Safety & High availibility Applications References

Automatic switchover in the event of a fault Event-controlled synchronization of both stations makes for fast and bumpless switchover Redundant CPU picks up processing at the interruption point without loss of information and alarms. All components can be replaced during running operation (hot swapping). When replacing a CPU, it is automatically loaded with the latest programs and data.
Open ring architecture SR-Support through H-CPUs and ET 200M Guarantee of functionality in the case of an error in a CPU or a ring node or a bus error

Sync wiring Data synchronization

Failure of an IO device (ET 200M) is limited to the damaged ring node


Cable break between two devices does not affect functionality of the system Failure of a CPU does not affect functionality of the redundant system Automatic synchronization after replacement of faulty component

CPU 41x-5H
Switch

CPU 41x-5H

PROFINET

Switch

Switch

ET 200M

ET 200M

ET 200M

E 200M

Page 4

Siemens AG 2011. All Rights Reserved. Industry Sector

SIMATIC ET 200M