Guideline To Design Electrical Network For Building

This document provides guidelines for designing the electrical network for a building or small area. It outlines 8 steps: 1) Calculate the electrical load based on area and load type. Apply diversity and common load factors. 2) Decide the voltage grade based on total load. Loads over 2.5MVA use 33kV, 1-2.5MVA use 11kV, under 1MVA taps existing 11kV feed. 3) Select transformer size from 25kVA to 400kVA based on load. No more than 2 transformers per location. 4) Use VCB or ring main unit to control transformers. Provide metering and protection at 11kV and LT panel on transformer secondary.

Uploaded by

Himdad Tahir
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
164 views3 pages

Guideline To Design Electrical Network For Building

This document provides guidelines for designing the electrical network for a building or small area. It outlines 8 steps: 1) Calculate the electrical load based on area and load type. Apply diversity and common load factors. 2) Decide the voltage grade based on total load. Loads over 2.5MVA use 33kV, 1-2.5MVA use 11kV, under 1MVA taps existing 11kV feed. 3) Select transformer size from 25kVA to 400kVA based on load. No more than 2 transformers per location. 4) Use VCB or ring main unit to control transformers. Provide metering and protection at 11kV and LT panel on transformer secondary.

Uploaded by

Himdad Tahir
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Guideline to Design Electrical Network for Building / Small Area.

(1) Calculate Electrical Load:


Find out built up area in Sqft.of per flat per House/Dwelling unit. Multiply area in Sqft. by Load/Sqft according to following Table

Type of Load Industrial Commercial Domestic

Load/Sqft 100 Watt/Sqft 30 Watt/Sqft 15 Watt/Sqft

Apply the diversity factor and Compute the load of all dwelling units in the area.

Type of Load Industrial Commercial Domestic

Diversity Factor 0.5 0.8 0.4

Add the load of common services such as Auditorium, Street Lights, Lifts and Water Pumps etc. For simplicity purpose 0.5kW/dwelling units may be considered as common load. Compute the Total Load of the area by adding load observed at above. Apply the power factor of 0.8 to determine the load in kVA. Compute the Load in kVA= Total Load/0.8 Take transformer loading of 65% considering the network arrangement Ring Main Circuit.

(2) Decide voltage grade for Electrical Load:


If load is equal to or more than 2.50MVA, the area shall be fed through 33kV feeder. For such loads, the land space for 33/11kV Sub-station shall have to be allocated by builder / Society/ Authority. For load between 1 MVA to 2.5MVA, dedicated 11kV feeder shall be preferred. For load below 1 MVA, existing 11kV feed can be tapped through VCB or RMU.

(3) Decide Size of Transformer:


Select T.C Size of 25 KVA,63 KVA,100 KVA,200 KVA or 400 KVA according to your Load. The maximum capacity of distribution transformer acceptable is 400 kVA as a standard capacity. Only two-no of transformer at one location shall be acceptable. If there is more number of transformers HT shall be required to extend using underground cables to locate additional transformer.

(4) RMU / LT Panel:


Either VCB or Ring Main Circuit shall be used to control transformers. There cables should have metering arrangement at 11kV. The protection system at incoming supply shall be using numerical relays. On LT side of transformer, LT main feeder pillar shall be provided. The Incoming shall be protected by MCCB/SFU. The distribution pillar-box shall be connected into Ring Main Unit. The incomer of distribution pillar shall have MCCB / SFU. The outgoing shall have HRC fuses.

(5) The LT cables from T.C to LT panel / Main feeder pillar:


Decide Size of LT Cable from T.C to LT Panel as per following Table.

Transformer Size 630kVA transformers 400kVA transformers 250kVA transformers 160kVA transformers 100kVA transformers

Cable 2 no x 1C x 630 Sq mm, Al, XLPE Cable 1 no x 1C x 630 Sq mm, Al, XLPE 3 C x 400 Sq mm, Al, XLPE 3 C x 300 Sq mm, Al, XLPE 3 C x 150 Sq mm, Al, XLPE

(6) Considering various Factors & Length of Cable:


The factors for cable loading shall be taken as 70%. The factor for multiplicity of cables from same cable trench shall be 80%.

The suggested maximum length of LT cable feeder shall be 250 Mtrs. The LT cables shall be connected in ring main circuit. The load on sub-feeder pillar shall be restricted to 150kW.

(7) LT cables from main feeder pillars to distribution pillar boxes:


Load on distribution pillar LT Cable Size

Up to 50kW Up to 100kW Up to 150 kW

3 C x 150 sqmm, AL, XLPE 3 C x 300 sqmm, AL, XLPE 3 C x 400sqmm, AL, XLPE

(8) Calculate Voltage Drop and T&D Losses:


The entire system has to be designed for a voltage drop of 2.0% from 11kV Side of transformer to metering equipment at end consumer premises. The entire system has to be designed for T&D losses of service maximum 2.0% from 11kV to end consumer meter including of service cable. Ref: 1. 2. NPC Limited. Electrical code.