Vav Unitiom

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

Installation/ Operator Maintenance VariT rane Single-Duct and Fan-Powered Units

All VariTrane VAV Models with pneumatic, electronic, DDC controls and diffusers.

June 2006

VAV-SVN01E-EN

2006 American Standard All rights reserved

VAV-SVN01E-EN

Contents

Service Model Number Description .................. 4 14 General Information ............................................... 15


Literature Contents Receiving and Handling Warnings and Cautions Explanations

Unit Information ............................................. 16 17


Single-Duct Units Dual-Duct Units Fan-Powered and Low-Height Units

Unit Installation .............................................. 18 31


Hanging Bracket Locations Unit Weights Water Coil Connections Unit Accessibility Clearances Actuator Mounting

Unit Setup ...................................................... 32 46


Flow Sensor P vs. Airflow Delivery Maximum Fan Motor Amperage (SCR) Motor Speed Control Adjustment Procedure Electrically Commutated Motor (ECM) ECM CFMTables

Wiring Diagrams ............................................. 47 54 Maintenance .......................................................... 55


Motors Fan Wheel Filter Water Coil Fan Motor Replacement

Installation of Diffusers .......................................... 56


T -Bar Ceiling Concealed Spline Ceiling Drywall/Plaster Ceiling
VAV-SVN01E-EN

Service Model Number Description

WARNING
Fiberglass Wool!
WARNING: ALL INSULATED UNITS (except closed-cell foam insulation) CONTAIN FIBERGLASS WOOL! Read this literature prior to installation for proper instruction. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

Single-Duct Units
Digit 1, 2Unit Type VC VariTrane single-duct Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 04 4" inlet (225 cfm) 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 8" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) 24 24" x 16" inlet (8000 cfm) Digit 7 , 8Not Used 00 N/A Digit 9Not Used 0 N/A Digit 10, 11Design Sequence H0 Fourth (factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC/electric PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC Cooling only DD02 DDC N.C. on/off water valve control DD03 DDC Prop hot water valve control DD04 DDC On/off electric heat DD05 DDC Pulse-width modulation electric heat DD07 DDC N.O. on/off water valve control DD11 LonTalk DDC Controller Cooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlleron/off electric heat control DD15 LonTalk DDC Controller w/ pulse-width modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM Customer-supplied actuator & controller FM01 FM Trane actuator w/ cusomersupplied control VMA1 FM Johnson controls VMA-1410 VMA2 FM Johnson controls VMA-1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100 w/Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI05 Analog With optional on/off reheat EI28 Analog With optional on/off reheat with dual-minimum cfm EI29 Analog With optional on/off reheat with constant-volume cfm PC00 PN N.C.Trane pneumatic actuator PC04 PN N.C. with optional on/off HW, DA Stat PC05 PN N.C. with optional on/off electric, RA Stat PN00 PN N.O.Trane pneumatic actuator, RA Stat PN04 PN N.O. PVR, DA Stat PN05 PN N.O. PVR, RA Stat PN11 PN N.O. dual-minimum cfm, DA Stat PN32 PN Water Valve, N.O. constant volume, DA Stat PN34 PN Electric heat, N.O. constant volume, DA Stat

Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell
VAV-SVN01E-EN

Service Model Number Description

Single-Duct Units (con't.)


Digit 17Not Used 0 N/A Digit 18Not Used 0 N/A Digit 19Outlet Plenum (Connection is Slip & Drive) 0 None A 1 Outlet RH B 1 Outlet END C 1 Outlet LH D 2 Outlets, 1 RH, 1 END E 2 Outlets, 1 LH, 1 END F 2 Outlets, 1 RH, 1 LH H 3 Outlets, 1 LH, 1 RH, 1 END J 4 Outlets, 1 LH, 1 RH, 2 END Digit 23Transformer 0 None 1 120/24 volt (50 VA) 2 208/24 volt (50 VA) 3 240/24 volt (50 VA) 4 277/24 volt (50 VA) 5 480/24 volt (50 VA) 6 347/24 Volt (50 VA) 7 575/24 Volt (50 VA) 8 380/24 Volt (50 VA) Digit 27 , 28, 29Electric Heat kW 000 None 050 0.5 kW 010 1.0 kW 015 1.5 kW

460

46.0 kW

Note: For VCEF units with transformers the VA depends on the staging, control, and contactor type (ranges are 40 VA to 75 VA)
Digit 24Disconnect Switch 0 None W With

Notes: 0.5 to 8.0 kW kW increments 8.0 to 18.0 kW 1 kW increments 18.0 to 46.0 kW 2 kW increments
Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal 3 3 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Not Used 0 N/A

Note: See unit drawings for outlet sizes/ damper information.


Digit 20Not Used 0 N/A Digit 21Water Coil 0 None 1 1-Row 2 2-Row Digit 22Electrical Connections (VCCF , VCWF can be flipped in the field to achieve opposite-hand connection) L Left (Airflow hitting you in the face) R Right (Airflow hitting you in the face) 0 Opposite side connection coil and control

Note:

VCCF , VCWF Toggle Disconnect VCEF Door Interlocking Power Disconnect

Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1

VAV-SVN01E-EN

Service Model Number Description

Dual-Duct Units
Digit 1, 2, 3Unit Type VDD VariTrane dual-duct Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 6" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) Digit 7 , 8Secondary Air Valve 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 8" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) Digit 9Not Used 0 N/A Digit 10, 11Design Sequence C0 Third (factory assigned) Digit 12, 13, 14, 15Controls ENON No Controls, Field-installed DDC/Electric PNON No Controls, Field-installed Pneumatic DD00 Trane elec actuator only DD01 DDC Cooling only DD08 DDC Constant-volume discharge DD11 LonTalk DDC Controller Cooling only DD18 LonTalk DDC Controller Constant Volume Discharge FM00 FM Customer-supplied actuator & controller FM01 FM Trane actuator w/ customer-supplied controller PC03 PN N.C. heating/ N.O. cooling w/ PVRs, DA stat PN08 PN N.O. heating/ N.O. cool act. only, RA stat PN09 PN N.O. htg/clg vlvs w/ PVRs, DA stat PN10 PN N.O. htg/clg w/ PVRs (cv disch), DA stat. Digit 19Outlet Plenum (Connection is slip & drive) 0 none A 1 outletRH B 1 outletEND C 1 outletLH D 2 outlets1 RH, 1 END E 2 outlets1 LH, 1 END F 2 outlets1 RH, 1 LH G 2 outlets - END H 3 outlets1 LH, 1 RH, 1 END J 4 outlets1 LH, 1 RH, 2 END

Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Not Used 0 N/A Digit 18Not Used 0 N/A

Note: See unit drawings for outlet sizes/ damper information.


Digit 20Not Used 0 N/A Digit 21Not Used 0 N/A Digit 22Not Used 0 N/A Digit 23Transformer 0 None 1 120/24 volt (50 VA) 2 208/24 volt (50 VA) 3 240/24 volt (50 VA) 4 277/24 volt (50VA) 5 480/24 volt (50 VA) 6 347/24 volt (50 VA) 7 575/24 volt (50 VA) Digit 24Disconnect Switch 0 None W WithToggle Digit 25Power Fuse 0 None W With

VAV-SVN01E-EN

Service Model Number Description

Fan-Powered Parallel Units


Digit 1, 2Unit Type VP VariTrane fan-powered parallel Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 05 5" inlet (350 max cfm) 06 6" inlet (500 max cfm) 08 8" inlet (900 max cfm) 10 10" inlet (1400 max cfm) 12 12" inlet (2000 max cfm) 14 14" inlet (3000 max cfm) 16 16" inlet (4000 max cfm) Digit 7 , 8Secondary Air Valve 00 N/A Digit 9Fan P 02SQ fan (500 nominal cfm) Q 03SQ fan (1100 nominal cfm) R 04SQ fan (1350 nominal cfm) S 05SQ fan (1550 nominal cfm) T 06SQ fan (1850 nominal cfm) U 07SQ fan (2000 nominal cfm) Digit 10, 11Design Sequence J0 Design Sequence (Factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC or analog ENCL ENON with controls enclosure PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC cooling only DD02 DDC N.C. on/off water control DD03 DDC prop hot water control DD04 DDC on/off electric heat control DD05 DDC pulse-width modulation electric heat control DD07 DDC N.O. on/off hot water control DD11 LonTalk DDC Controller Cooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlon/off electric heat control DD15 LonTalk DDC Controller w/ pulse-width modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM customer actuator & control FM01 FMTrane actuator w/ customersupplied controller VMA2 FM Johnson Controls VMA-1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100 w/Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI05 Analog fan-powered parallel with optional on/off reheat PN00 PN N.O.Trane pneumatic actuator, R.A. stat PN05 PN N.O. PVR, R.A. stat Digit 20Attenuator 0 None W With Digit 21Water Coil 0 None 1 1-RowPlenum inlet installed RH 2 2-RowPlenum inlet installed RH 3 1-RowDischarge installed, LH 4 1-RowDischarge installed, RH 5 2-RowDischarge installed, LH 6 2-RowDischarge installed, RH Digit 22Electrical Connections L Left R Right

Electrical Connections Note: Airflow hitting you in the face.


Digit 23T ransformer 0 N/A (provided as standard) Digit 24Disconnect Switch 0 None W With

Notes: N.C. = Normally-closed N.O = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM) Digit 18Motor Voltage 1 115/60/1 2 277/60/1 3 347/60/1 4 208/60/1 5 230/50/1 Digit 19Outlet Connection 1 Flanged 2 Slip & Drive

Note:

VPCF , VPWF Toggle Disconnect VPEF Door Interlocking Power Disconnect

Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1 Digit 27 , 28, 29Electric Heat Voltage 000 None 050 0.5 kW 010 1.0 kW 015 1.5 kW 260 26.0 kW

Electric Heat Voltage Notes: 0.5 to 8.0 kW kW increments 8.0 to 18.0 kW 1 kW increments 18.0 to 46.0 kW2 kW increments
7

VAV-SVN01E-EN

Service Model Number Description

Fan-Powered Parallel Units (con't)


Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal 3 3 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Airflow Switch 0 None W With

VAV-SVN01E-EN

Service Model Number Description

Fan-Powered Series Units


Digit 1, 2Unit Type VS VariTrane fan-powered series Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 04 4" inlet (225 max cfm) 05 5" inlet (350 max cfm) 06 6" inlet (500 max cfm) 08 8" inlet (900 max cfm) 10 10" inlet (1400 max cfm) 12 12" inlet (2000 max cfm) 14 14" inlet (3000 max cfm) 16 16" inlet (4000 max cfm) Digit 7 , 8Secondary Air Valve 00 N/A Digit 9Fan P 02SQ fan (700 nominal cfm) Q 03SQ fan (1200 nominal cfm) R 04SQ fan (1550 nominal cfm) S 05SQ fan (1900 nominal cfm) T 06SQ fan (2600 nominal cfm) U 07SQ fan (3000 nominal cfm) DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlleron/off electric heat control DD15 LonTalk DDC Controller w/ pulse-width modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM customer actuator & control FM01 FMTrane actuator w/ customersupplied controller VMA2 FM Johnson controls VMA-1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100 w/Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI71 Analog fan-powered series with optional on/off reheat PN00 PN N.O.Trane pneumatic actuator, R.A. stat PN51 PN N.O. PVR, duct pressure switch, R.A. stat PN52 PN N.O. PVR, dual pressure main, R.A. stat Digit 18Motor Voltage 1 115/60/1 2 277/60/1 3 347/60/1 4 208/60/1 5 230/50/1 Digit 19Outlet Connection 1 Flanged 2 Slip & Drive Digit 20Attenuator 0 None W With Digit 21Water Coil 0 None 3 1-RowDischarge installed, LH 4 1-RowDischarge installed, RH 5 2-RowDischarge installed, LH 6 2-RowDischarge installed, RH Digit 22Electrical Connections L Left R Right

Water Coil and Electrical Connections Note: Airflow hitting you in the face.
Digit 23T ransformer 0 N/A (provided as standard) Digit 24Disconnect Switch 0 None W With

Fan Note: See fan curves for specific airflows


Digit 10, 11Design Sequence J0 Design Sequence (Factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC or analog ENCL ENON with control enclosure PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC cooling only DD02 DDC N.C. on/off water control DD03 DDC prop hot water control DD04 DDC on/off electric heat control DD05 DDC pulse-width modulation electric heat control DD07 DDC N.O. on/off hot water control DD11 LonTalk DDC Controller Cooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control
VAV-SVN01E-EN

Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM)

Note:

VSCF , VSWF Toggle Disconnect VSEF Door Interlocking Power Disconnect

Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1

Service Model Number Description

Fan-Powered Series Units (con't)


Digit 27 , 28, 29Electric Heat Kilowatts 000 None 050 0.5 kW 010 1.0 kW 015 1.5 kW

240 24.0 kW Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal 3 3 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Airflow Switch 0 None W With

10

VAV-SVN01E-EN

Service Model Number Description

Fan-Powered Low-Height Parallel Units


Digit 1, 2Unit Type LP VariTrane fan-powered lowheight parallel Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 05 5" inlet (350 maximum cfm) 06 6" inlet (500 maximum cfm) 08 8" inlet (900 maximum cfm) RT 8" x 14" inlet (1800 maximum cfm) Digit 7 , 8Secondary Air Valve 00 N/A Digit 9Fan V 08SQ 500 nominal cfm W 09SQ 900 nominal cfm X 10SQ 1800 nominal cfm Digit 10, 11Design Sequence K0 Sixth (factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC/ electric PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC cooling only DD02 DDC N.C. on/off water valve control DD03 DDC prop hot water valve control DD04 DDC on/off electric heat control DD05 DDC pulse-width modulation control DD07 DDC N.O. on/off water valve control DD11 LonTalk DDC ControllerCooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlleron/off electric heat control DD15 LonTalk DDC Controller w/ pulsewidth modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM customer actuator & control FM01 FMTrane actuator w/ customersupplied controller VMA2 FM Johnson Controls VMA1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100 w/Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI05 Analog fan-powered parallel with optional on/off reheat PN00 PN N.O.Trane pneumatic actuator, R.A. stat PN05 PN N.O. PVR, R.A. stat Digit 18Motor Voltage 1 115/60/1 2 277/60/1 3 347/60/1 5 230/50/1 Digit 19Outlet Connection 1 Flanged 2 Slip & Drive Digit 20Not Used 0 N/A Digit 21Water Coil 0 None 1 1-RowPlenum inlet installed 2 2-RowPlenum inlet installed 3 1-RowDischarge installed, LH 4 1-RowDischarge installed, RH 5 2-RowDischarge installed, LH 6 2-RowDischarge installed, RH Digit 22Electrical Connections L Left (airflow hitting you in the face) Digit 23T ransformer 0 N/A (provided as standard) Digit 24Disconnect Switch 0 None W With

Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM)

Note:

LPCF , LPWF Toggle Disconnect LPEF Door Interlocking Power Disconnect

Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3

VAV-SVN01E-EN

11

Service Model Number Description

Fan-Powered Low-Height Parallel Units (con't)


Digit 27 , 28, 29Electric Heat Voltage 000 None 005 0.5 kW 010 1.0 kW 015 1.5 kW 020 2.0 kW 025 2.5 kW 030 3.0 kW 035 3.5 kW 040 4.0 kW 045 4.5 kW 050 5.0 kW 055 5.5 kW 060 6.0 kW 065 6.5 kW 070 7 .0 kW 075 7 .5 kW 080 8.0 kW 090 9.0 kW 100 10.0 kW 1 10 11.0 kW 120 12.0 kW 130 13.0 kW 140 14.0 kW Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Airflow Switch 0 None W With

12

VAV-SVN01E-EN

Service Model Number Description

Fan-Powered Low-Height Series Units


Digit 1, 2Unit Type LS VariTrane low-height series fanpowered Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 8" inlet (900 cfm) RT (8" x 14" inlet (1800 cfm) Digit 7 , 8Secondary Air Valve 00 N/A Digit 9Fan V 08SQ 500 nominal cfm W 09SQ 900 nominal cfm X 10SQ 1800 nominal cfm Digit 10, 11Design Sequence K0 Sixth (factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC/ electric PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC cooling only DD02 DDC N.C. on/off water valve control DD03 DDC prop hot water valve control DD04 DDC on/off electric heat control DD05 DDC pulse-width modulation control DD07 DDC N.O. on/off water valve control DD11 LonTalk DDC Controller Cooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlleron/off electric heat control DD15 LonTalk DDC Controller w/ pulse-width modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM customer actuator & control FM01 FMTrane actuator w/ customersupplied controller VMA2 FM Johnson controls VMA-1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI71 Analog Series fan-powered on/off reheat PN00 PN N.O.Trane pneumatic actuator, R.A. stat PN51 PN N.O. PVR, duct pressure switch, R.A. stat PN52 PN N.O. PVR, dual pressure main, R.A. stat Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM) Digit 18Motor Voltage 1 115/60/1 2 277/60/1 3 347/60/1 5 230/50/1 Digit 19Outlet Connection 1 Flanged 2 Slip & Drive Digit 20Not Used 0 N/A Digit 21Water Coil 0 None 3 1-RowDischarge installed, LH 4 1-RowDischarge installed, RH 5 2-RowDIscharge installed, LH 6 2-RowDischarge installed, RH Digit 22Electrical Connections L Left (airflow hitting you in the face) R Right (airflow hitting you in the face) Digit 23T ransformer 0 N/A (provided as standard) Digit 24Disconnect Switch 0 None W With

Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell

Note:

LSCF , LSWF Toggle Disconnect LSEF Door Interlocking Power Disconnect

Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3

VAV-SVN01E-EN

13

Service Model Number Description

Fan-Powered Low-Height Series Units (con't)


Digit 27 , 28, 29Electric Heat Voltage 000 None 005 0.5 kW 010 1.0 kW 015 1.5 kW 020 2.0 kW 025 2.5 kW 030 3.0 kW 035 3.5 kW 040 4.0 kW 045 4.5 kW 050 5.0 kW 055 5.5 kW 060 6.0 kW 065 6.5 kW 070 7 .0 kW 075 7 .5 kW 080 8.0 kW 090 9.0 kW 100 10.0 kW 1 10 11.0 kW 120 12.0 kW 130 13.0 kW 140 14.0 kW 150 15.0 kW 160 16.0 kW 170 17 .0 kW 180 18.0 kW Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal Digit 31Contactors 0 None 1 24-Volt magnetic 2 24-Volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Air Flow Switch 0 None W With

14

VAV-SVN01E-EN

General Information
Verify that all options have been included, such as filters, controls, heating coils, water valves, etc. Also check that the unit voltages agree with the building parameters. Manually rotate the fan (if applicable) to assure that there are no obstructions within the housing. Claims for in-transit damage must be filed immediately with the delivery carrier. For hot water re-heat units, check the coil fins and make sure that coils are not damaged. Locate and verify that the correct zone sensors are with the order.These will be marked with an orange Accessories Enclosed label. Store in a secure location until needed. Accessories lost at the jobsite are NOT covered by Tranes warranty. If a discrepancy occurs between what was ordered and what is received, contact you localTrane representative immediately. Read the appropriate section in this manual for installation procedures prior to actual starting of equipment. Upon receiving the equipment, please inspect each unit and components for external or internal damage. Refer to the bill of lading to insure all equipment and accessories have been received. Contact your localTrane sales representative and notify the trucking company immediately of any short ship or damaged equipment.

Literature Contents This manual describes the installation of VariTrane VAV units with recommended wiring, piping, and mounting of Single-Duct, Dual-Duct, Fan-Powered, Low-Height terminal units and diffusers. Receiving and Handling VariTrane Units are shipped completely assembled with the exceptions of optional attenuators for fan-powered units and accessories. Upon receiving the equipment, complete the following: Locate the nameplate and refer to the model and sales order number and check that the correct units have been delivered. Inspect the control enclosures and air valve casing for dents or punctures.

NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. not avoided, could result in death or serious injury.

WARNING Indicates a potentially hazardous situation which, if

CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION Indicates a situation that may result in equipment or
property-damage-only accidents.
VAV-SVN01E-EN 15

Unit Information

Single-Duct Units The basic unit consists of a sheet metal casing with an air valve, which is used to modulate the air being delivered into the occupied zone.The unit is designed to modulate either cooling or heating air between the temperatures of 40F and 140F . Air enters the air valve through the round or rectangular inlet and exits into the sheet metal casing to be distributed to the zone either through integral round outlets in the casing or through rectangular duct attached to the discharge of the unit. The basic unit can also be ordered with factory-mounted electric or hot water heating coils attached to the discharge. (See Figure 1.) These re-heat units are used primarily to reheat air-to-zone temperature when the load in the occupied space is low. Primary air is modulated through the VariTrane air valve by rotating the damper blade. All air valves have a round/rectangular inlet for easy fit-up with incoming ductwork.

Figure 1 Typical Single-Duct Units

Dual-Duct Units Dual-duct units provide two air valves: one as heating primary air and the other as cooling primary air. Both discharge into the common outlet, which leads to the zone being controlled. (See Figure 2.) The units are provided with a slip and drive rectangular duct connection or can be ordered with integral outlet plenum. Sequencing of the hot and cold air valve is dependent upon job requirements. One typical control is the valves working in conjunction with each other to respond to zone temperature. When the cooling valve becomes fully closed or reaches a specified minimum, then the heating valve will begin to modulate or vice versa.The typical result is that air flowing to the zone varies from the maximum down to a minimum and back up to a maximum as the load varies and as the controls would cause one air valve to close and the other to open.

VCCF

VCWF

Another typical application is when the unit provides a constant volume to the zone. When the zone sensor is tied directly to the heating valve, it will modulate the heating valve according to the zone temperature. When the heating valve is fully closed or there is a call for cooling in the zone, the cooling valve will be at constant supply. As the space becomes too cool, the heating valve will modulate open, decreasing the cooling valve flow.The typical result is that the air flowing into the zone stays at a constant flow whether the unit is heating or cooling.

VCEF

Figure 2 Typical Dual-Duct Unit

VDDF

16

VAV-SVN01E-EN

Unit Information

Fan-Powered and Fan-Powered Low-Height Units VariTrane fan-powered and low-height fan-powered units can be either parallel or series, with or without re-heat. (See Figure 3.) The fan on a series unit runs continuously whenever the main air handler unit is in operation.There are various options for starting the fan.The fan can be started three ways: 1) remotely, 2) by a duct pressure switch, or 3) by a combination of both.The particular fan control method may vary from unit to unit, depending upon job needs. Typically, the heater is off while the air valve modulates primary air and responds to zone temperature. If zone temperature decreases to the point where a decrease in primary air will not maintain the desired temperature, the re-heat will be activated to increase the temperature of the discharge air. On a parallel unit, the VariTrane air valve delivers primary cooling air to the unit outlet. When the space temperature decreases beyond air valve control, the fan is turned on as the first stage of heat.The fan delivers plenum air from above the occupied space to the unit outlet, which is mixed with primary air and delivered to the occupied space.

VariTrane fan-powered unit fan sizes 02SQ05SQ and 08SQ10SQ were performance tested at .12 in. w.g. and sizes 06SQ and 07SQ were tested at .15 in. w.g. Units are not designed to operate unducted and below these tested static pressures.

Note: Fan-powered units are available with rectangular discharge connection only. The optional heater is mounted on the discharge of the unit. Hot water coils are connected to either the plenum inlet or on the discharge on parallel units, and to the discharge of series units. Figure 3 Typical Fan-Powered Units

VSCF

VPCF

Note: Either the fan, the air valve, or both can deliver airflow into the occupied space. In order to prevent primary airflow from exiting through the fan when the fan is not running on a parallel unit, a back draft damper is provided. When the fan is not running, the efficiency of this system is the same as a standard singleduct VAV unit.
Typically, the control systems applied to parallel units cause the air valve to close to zero or a minimum flow before the fan is activated. After the fan is activated, the optional heat will be activated upon further reduction in zone temperature.Therefore, minimal primary air is mixed with the heated air.

VSEF

VPEF

VSWF

VPWF

VAV-SVN01E-EN

17

Unit Installation

Due to their weight, the VAV terminal units should be suspended from the uppermost ceiling, independent of the false ceiling grid. Suspension devices are to be supplied by the installer. Units must be installed level and upright. Failure to level the unit properly may prevent proper operation of the controls and/or terminal unit. Units are not designed to be installed vertically. Consequently, this will also void the UL ratings and any warranty on the unit. Single-Duct Depending upon the size and weight of the single-duct unit, it may be capable of being supported by the ductwork that is connected to it. No hanger brackets are provided on these units since the unit should be supported by means of a hanger strap.The hanger strap should be secured directly to the unit casing as shown in Figure 4. For cooling only single-duct units or single-duct units with hot water coil, the unt may be rotated 180 for opposite side connections. For units with electric heat, the unit must be ordered from the factory designating either right- or left-hand connections.

Dual-Duct Dual-duct units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. See Figure 5.

Figure 5

Dual-Duct Hanger Bracket Locations


A C

AIR VALVE
COOLING

AIR VALVE
HEATING

Figure 4

TOP VIEW

Single-Duct Hanging Recommendations


Inlet Size
5" thru 10" 12" thru 16"

A
23.154" (588 mm) 25.154" (639 mm)

B
25.25" (641 mm) 37.25" (946 mm)

C
1.376" (35 mm) 1.376" (35 mm)

18

VAV-SVN01E-EN

Unit Installation

Fan-Powered (Standard and LowHeight) Fan-powered units should be supported by either hanger straps or by using a threaded rod in conjunction with the hanger brackets that are provided on the unit. Care should be exercised to insure that the hanging straps do not block the side access panel. See Figures 613.

Figure 6

Parallel Hanger Bracket Locations Sizes


C Water Coil TOP VIEW Parallel Cooling & Hot Water Airflow Plenum Inlet

B Flow Ring Tubing Primary Airflow F


Air Valve

Optional Attenuator Field Installed E

Airflow Discharge Outlet A B D E C F FAN SIZE 26.75" (679 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm) 02SQ 03SQ, 04SQ, 05SQ 29.75" (756 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm) 36.75" (933 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm) 06SQ, 07SQ C

Airflow Plenum Inlet Optional Attenuator Field Installed F TOP VIEW Parallel Electric Heat
Air Valve

Flow Ring Tubing

Primary Airflow

Terminal Box

Heater Airflow Discharge Outlet


43.546 (1106 mm)

VAV-SVN01E-EN

19

Unit Installation

Figure 7

Series Hanger Bracket Locations


Flow Ring Tubing
Air Valve

A C

Optional Attenuator Field Installed Airflow Plenum Inlet E


2.

TOP VIEW Series Cooling & Hot Water D


1.

Fan Inlet w/o Attenuator

1. 2.

All attenuators are the same length and width. Sizes 01 and 02 units are smaller than attenuators.

Water Coil 1.625" (41 mm)

FAN SIZE 02SQ 03SQ, 04SQ 05SQ 06SQ, 07SQ

A 18.75" (476 mm) 20.75" (527 mm) 27.25" (692 mm) 27.25" (692 mm)

B 26.75" (679 mm) 26.75" (679 mm) 26.75" (679 mm) 26.75" (679 mm)

C 3.25" (83 mm) 3.25" (83 mm) 3.25" (83 mm) 3.25" (83 mm)

D 41.154" (1041 mm) 41.154" (1041 mm) 41.154" (1041 mm) 41.154" (1041 mm)

E 35.154 (740 mm) 41.154" (1041 mm) 41.154" (1041 mm) 41.154" (1041 mm)

F (Elec. Heat Only) 20.132" (511 mm) 23.875 (606 mm) 29.875" (759 mm) 29.875" (759 mm)

Flow Ring Tubing


Air Valve

A C

TOP VIEW Series Electric Heat

Optional Attenuator Field Installed Airflow Plenum Inlet

G Fan Inlet w/o Attenuator

19.00" (483 mm)

Electric Heater

C B

20

VAV-SVN01E-EN

Unit Installation

Figure 8

Low-Height Parallel 08SQ/09SQ w/ Hot Water or Electric Heat


31.65" (804 mm)

13.00" (330 mm)


Primary Airflow

23.90" (607 mm)

Airflow Plenum Inlet

Optional Attenuator Field Installed

19.86" (504 mm)

24.30" (617 mm)

Airflow Discharge Outlet

3.35" (85 mm) 13.80" (350 mm) 4.00" (102 mm)

TOP VIEW

23.10" (587 mm)

31.65" (804 mm)

13.00" (330 mm)


Primary Airflow

23.90" (607 mm)

Airflow Plenum Inlet

Optional Attenuator Field Installed

19.86" (504 mm)

24.30" (617 mm)

Terminal Box

Heater

3.35" (85 mm)


Airflow Discharge Outlet

TOP VIEW

3.00" (76 mm)

23.10" (587 mm)

13.80" (350 mm)

4.00" (102 mm)

VAV-SVN01E-EN

21

Unit Installation

Figure 9

Low-Height Parallel10SQ
1.625" (41 mm) 38.95" (989 mm)

Flow Ring Tubing

Primary Airflow Plenum Inlet 5.625" (143 mm)

Air Valve

38.75" (984 mm)

Optional Heater

Terminal Box

5.625" (143 mm)

Airflow Discharge Outlet 41.137" (1045 mm)

TOP VIEW

22

VAV-SVN01E-EN

Unit Installation

Figure 10

Low-Height Series 08SQ/09SQ w/ Hot Water or Electric Heat


31.65" (804 mm)

4.00" (102 mm)

10.13" (257 mm) Primary Airflow

12.85" (326 mm)

Airflow Plenum Inlet

Optional Attenuator Field Installed


Air Valve

19.86" (504 mm)

3.35" (85 mm)

34.30" (871 mm)

31.65" (804 mm)

3.35" (85 mm) Water Coil TOP VIEW 4.00" (102 mm)

10.13" (257 mm) Primary Airflow

12.85" (326 mm)

Airflow Plenum Inlet

Optional Attenuator Field Installed Air Valve Airflow 20.00" (508 mm) 27.00" (686 mm) 3.35" (85 mm)

19.86" (504 mm)

34.30" (871 mm)

3.35" (85 mm) Optional Electric Heater TOP VIEW

Airflow 20.00" (508 mm) 27.00" (686 mm)

VAV-SVN01E-EN

23

Unit Installation

Figure 11

Low-Height Series 10SQ w/ Hot Water or Electric Heat


19.45" (494 mm) 31.65" (804 mm)
Optional Attenuator Field Installed Primary Airflow

10.12" (257 mm)

19.45" (494 mm) 31.65" (804 mm)


Optional Attenuator Field Installed

19.86" (504 mm)

Airflow Plenum Inlet

Airflow Plenum Inlet

3.35" (85 mm)

19.86" (504 mm)

30.30" (770 mm)

3.35" (85 mm)


TOP VIEW

Airflow Discharge Outlet

3.50" (89 mm)

42.00" (1067 mm)

3.50" (89 mm)

19.45" (494 mm) 31.65" (804 mm)


Optional Attenuator Field Installed

10.12" (257 mm)

19.45" (494 mm) 31.65" (804 mm)


Optional Attenuator Field Installed

Primary Airflow

19.86" (504 mm)

Airflow Plenum Inlet

Airflow Plenum Inlet

3.35" (85 mm)

19.86" (504 mm)

30.30" (770 mm)

Terminal Box

Plenum Area

3.35" (85 mm)


TOP VIEW

Optional Heater

1.92" (49 mm) 3.50" (89 mm)

Airflow Discharge Outlet

42.00" (1067 mm)

3.50" (89 mm)

24

VAV-SVN01E-EN

Unit Installation

Figure 12

Attenuator InstallationParallel Units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

OPTIONAL ATTENUATOR FIELD INSTALLED

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

VAV-SVN01E-EN

25

Unit Installation

Figure 13

Attenuator InstallationSeries Units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

OPTIONAL ATTENUATOR FIELD INSTALLED

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

26

VAV-SVN01E-EN

Unit Installation

Figure 14

Attenuator InstallationLow-Height Parallel Units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

OPTIONAL ATTENUATOR FIELD INSTALLED

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

VAV-SVN01E-EN

27

Unit Installation

Figure 15

Attenuator InstallationLow-Height Series Units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

OPTIONAL ATTENUATOR FIELD INSTALLED

MOUNTING BRACKET

OPTIONAL ATTENUATOR FIELD INSTALLED

OPTIONAL ATTENUATOR FIELD INSTALLED MOUNTING BRACKET

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

28

VAV-SVN01E-EN

Unit Installation

Chart 1 Unit Weights Single-Duct Units


Unit Size
4 5 6 8 10 12 14 16 24

VCCF (lbs/kg)
16/7 16/7 16/7 16/7 22/10 27/12 32/15 35/16 52/24

VCCF w/ Dual Wall (lbs/kg)


19/9 19/9 19/9 20/9 27/12 34/15 41/19 46/21 63/29

VCEF (lbs/kg)
38/17 38/17 38/17 38/17 46/21 52/24 60/27 69/31 84/38

VCEF w/ Dual Wall (lbs/kg)


48/22 48/22 48/22 49/22 60/27 68/31 80/36 91/41 106/48

VCWF 1-Row (lbs/kg)


21/10 21/10 21/10 21/10 29/13 37/17 44/20 49/22 70/32

VCWF 2-Row (lbs/kg)


22/10 22/10 22/10 24/11 32/15 40/18 48/22 54/24 77/35

VCWF 1-Row w/ Dual Wall (lbs/kg)


24/11 24/11 24/11 25/11 34/15 43/20 53/24 60/27 81/37

VCWF 2-Row w/ Dual Wall (lbs/kg)


25/11 25/11 25/11 28/13 37/17 47/21 57/26 65/29 88/40

Dual-Duct Units
Unit Size
0505 0506 0606 0508 0608 0510 0808 0610 0810 1010 0612 0812

VDDF (lbs/kg)
54/24 54/24 54/24 55/25 55/25 56/25 56/25 56/25 57/26 61/28 57/26 58/26

VDDF w/ Dual Wall (lbs/kg)


68/31 68/31 68/31 68/31 69/31 69/31 70/32 70/32 70/32 74/34 70/32 71/32

Unit Size
1012 1212 0814 1014 1214 1414 0816 1016 1216 1416 1616

VDDF (lbs/kg)
59/27 60/27 78/35 79/36 80/36 81/37 79/36 80/36 81/37 82/37 83/38

VDDF w/ Dual Wall (lbs/kg)


72/33 84/38 102/46 103/47 104/47 105/48 103/47 104/47 105/48 105/48 106/48

Parallel Fan-Powered Units


Unit Size
0502SQ 0602SQ 0603SQ 0802SQ 0803SQ 0804SQ 1002SQ 1003SQ 1004SQ 1005SQ 1006SQ 1007SQ 1203SQ 1204SQ 1205SQ 1206SQ 1207SQ 1404SQ 1405SQ 1406SQ 1407SQ 1606SQ 1607SQ VAV-SVN01E-EN

VPCF w/ Dual Wall (lbs/kg) (lbs/kg)


81/37 80/36 83/38 81/37 83/38 84/38 82/37 84/38 85/39 98/44 114/52 122/55 85/39 86/39 99/45 115/52 123/56 87/39 100/45 116/53 124/56 117/53 125/57 115/52 114/52 117/53 115/52 117/53 118/54 116/53 118/54 119/54 132/60 148/67 156/71 119/54 120/54 133/60 149/68 157/71 121/55 134/61 150/68 158/72 151/68 159/72

VPCF

VPEF (lbs/kg)
110/550 109/49 112/51 110/50 112/51 113/51 111/50 113/51 114/52 128/58 144/65 152/69 114/52 115/52 129/59 145/66 153/69 116/53 130/59 146/66 154/70 147/67 155/70

VPEF w/ Dual Wall (lbs/kg)


144/65 143/65 146/66 144/65 146/66 147/67 145/66 147/67 148/67 162/73 178/81 186/84 148/67 149/68 163/74 179/81 187/85 150/68 164/74 180/82 188/85 181/82 189/86

VPWF 1-Row (lbs/kg)


92/42 91/41 105/48 92/42 105/48 106/48 93/42 106/48 107/49 120/54 127/58 135/61 107/49 108/49 121/55 128/58 136/62 109/49 122/55 129/59 137/62 130/59 138/63

VPWF 2-Row (lbs/kg)


95/43 94/43 108/49 95/43 108/49 109/49 96/44 109/49 110/50 123/56 130/59 138/63 110/50 111/50 124/56 131/59 139/63 112/51 125/57 132/60 140/64 133/60 141/64

VPWF 1-Row w/ Dual Wall (lbs/kg)


126/57 125/57 139/63 126/57 139/63 140/64 127/58 140/64 141/64 154/70 161/73 169/77 141/64 142/64 155/70 162/73 170/77 143/65 156/71 163/74 171/78 164/74 172/78

VPWF 2-Row w/ Dual Wall (lbs/kg)


129/59 128/58 142/64 129/59 142/64 143/65 130/59 143/65 144/65 157/71 164/74 172/78 144/65 145/66 158/72 165/75 173/78 146/66 159/72 166/75 174/79 167/76 175/79

VPxF Attenuator (lbs/kg)


46/21 46/21 48/22 46/21 48/22 48/22 46/21 48/22 48/22 48/22 54/24 54/24 48/22 48/22 48/22 54/24 54/24 48/22 48/22 54/24 54/24 54/24 54/24 29

Unit Installation

Chart 1 Unit Weights (Con't.) Series Fan-Powered Unit VSCF VSCF w/ VSEF
Size
0402SQ 0502SQ 0602SQ 0603SQ 0604SQ 0802SQ 0803SQ 0804SQ 1002SQ 1003SQ 1004SQ 1005SQ 1006SQ 1007SQ 1203SQ 1204SQ 1205SQ 1206SQ 1207SQ 1404SQ 1405SQ 1406SQ 1407SQ 1606SQ 1607SQ

VSEF w/
Dual Wall (lbs/kg)
119/54 119/54 118/54 129/59 140/64 120/54 130/59 141/64 122/55 133/60 144/65 145/66 164/74 177/80 135/61 145/66 147/67 165/75 178/81 146/66 149/68 166/75 179/81 167/76 180/82

VSWF
1-Row (lbs/kg)
85/39 85/39 84/38 88/40 99/45 86/39 89/40 100/45 88/40 92/42 103/47 104/47 119/54 132/60 94/43 104/47 106/48 120/54 133/60 105/48 108/49 121/55 134/61 122/55 135/61

VSWF
2-Row (lbs/kg)
87/39 87/39 86/39 92/42 103/47 88/40 93/42 104/47 90/41 96/44 107/49 108/49 124/56 137/62 98/44 108/49 110/50 125/57 13863 109/49 112/51 126/57 139/63 127/58 140/64

VSWF 1-Row VSWF 2-Row


w/ Dual Wall (lbs/kg)
100/45 100/45 99/45 112/51 123/56 101/46 113/51 124/56 103/47 116/53 127/58 128/58 148/67 161/73 118/54 128/58 130/59 149/68 162/73 129/59 132/60 150/68 163/74 151/68 164/74

VSxF
Attenuator (lbs/kg)
46/21 46/21 46/21 48/22 48/22 46/21 48/22 48/22 46/21 48/22 48/22 48/22 54/24 54/24 48/22 48/22 48/22 54/24 54/24 48/22 48/22 54/24 54/24 54/24 54/24

Dual Wall (lbs/kg) (lbs/kg)


78/35 78/35 77/35 76/34 87/39 79/36 77/35 88/40 81/37 80/36 91/41 92/42 104/47 117/53 82/37 92/42 94/43 105/48 118/54 93/42 96/44 106/48 119/54 107/49 120/54 93/42 93/42 92/42 100/45 111/50 94/43 101/46 112/51 96/44 104/47 115/52 116/53 133/60 146/66 106/48 116/53 118/54 134/61 147/67 117/53 120/54 135/61 148/67 136/62 149/68

(lbs/kg)
104/47 104/47 103/47 105/48 116/53 105/48 106/48 117/53 107/49 109/49 120/54 121/55 135/61 148/67 111/50 121/55 123/56 136/62 149/68 122/55 125/57 137/62 150/68 138/63 151/68

w/ Dual Wall (lbs/kg)


102/46 102/46 101/46 116/53 127/58 103/47 117/53 128/58 105/48 120/54 131/59 132/60 153/69 166/75 122/55 132/60 134/61 154/70 167/76 133/60 136/62 155/70 168/76 156/71 169/77

Low-Height Parallel Units Unit LPCF LPCF w/


Size
0508SQ 0608SQ 0609SQ 0808SQ 0809SQ 0810SQ 14RT09SQ 14RT10SQ

LPEF
(lbs/kg)
84/38 83/38 88/40 84/38 89/40 105/48 98/44 112/51

LPEF w/
Dual Wall (lbs/kg)
104/47 103/47 108/49 104/47 109/49 125/57 118/54 132/60

LPWF
1-Row (lbs/kg)
78/35 77/35 82/37 78/35 83/38 99/45 92/42 106/48

LPWF
2-Row (lbs/kg)
81/37 80/36 85/39 81/37 86/39 102/46 95/43 109/49

LPWF 1-Row
w/ Dual Wall (lbs/kg)
98/44 97/44 102/46 98/44 103/47 119/54 112/51 126/57

LPWF 2-Row
w/ DualWall (lbs/kg)
101/46 100/45 105/48 101/46 106/48 122/55 115/52 129/59

LPxF
Attenuator (lbs/kg)
10/5 10/5 10/5 10/5 10/5 10/5 10/5 10/5

Dual Wall (lbs/kg) (lbs/kg)


69/31 68/31 73/33 69/31 74/34 90/41 83/38 97/44 89/40 88/40 93/42 89/40 94/43 110/50 103/47 117/53

Low-Height Series Units


Unit Size
0508SQ 0608SQ 0609SQ 0808SQ 0809SQ 0810SQ 14RT09SQ 14RT10SQ 30

LSCF w/ Dual Wall (lbs/kg) (lbs/kg)


71/32 70/32 80/36 71/32 81/37 95/43 90/41 105/48 86/39 85/39 95/43 86/39 96/44 120/54 105/48 130/59

LSCF

LSEF (lbs/kg)
86/39 85/39 95/43 86/39 96/44 120/54 105/48 130/59

LSEF w/ Dual Wall (lbs/kg)


101/45 100/45 110/50 101/46 111/50 145/66 120/54 155/70

LSWF 1-Row (lbs/kg)


80/36 79/36 89/40 80/36 90/41 111/50 99/45 121/55

LSWF 2-Row (lbs/kg)


82/37 81/37 91/41 82/37 92/42 115/52 101/46 125/57

LSWF 1-Row w/ Dual Wall (lbs/kg)


95/43 94/43 104/47 95/43 105/48 136/62 114/52 146/66

LSWF 2-Row w/ Dual Wall (lbs/kg)


97/44 96/44 106/48 97/44 107/49 140/64 116/53 150/68

LSxF Attenuator (lbs/kg)


10/5 10/5 10/5 10/5 10/5 20/9 10/5 20/9 VAV-SVN01E-EN

Unit Installation

Duct Connections All VariTrane units should be provided with a minimum of 1.5-duct diameters of straight duct prior to the inlet of the unit. It is recommended that at least 48 inches of straight duct be provided from the discharge of the units prior to any take-offs or transitions. This is a requirement for electric heat fanpowered units used in applications with 100% downward discharge.

Care should be taken to properly support the water coil piping connections while connecting the adjoining pipe. It is recommended that piping to the water coil should be done after fieldmounted controls, external insulation, and ductwork connections have been completed. Do not connect water valve or pipe extensions to the water coil connections unless supported. Unit Accessibility Single-duct and dual-duct units provided with hot water reheat have an access panel located on the side of the water coil. All other single-duct and dual-duct units are provided without access, as all functioning components are external to the unit. Fan-powered terminals are provided with a sliding side access. Low-height terminal units have a removable bottom panel. Clearances For proper service, it is recommended that at least 36 of side clearance be provided to service and access singleduct and dual-duct terminals units. Fan-powered VAV units have a plenum inlet that must be clear of obstructions. Allow at least 36 of clearance in front of the side access and plenum opening. Low-height fan-powered terminals require the same plenum clearance requirement that applies to the standard fan-powered units. However the access to the internal components is located on the bottom of the unit. It is also recommended that 6 of clearance be provided to the top and bottom of all the units.

Actuator Mounting Trane offers a factory-mounted actuator with a 90-second drive time.The actuator drives 1 degree per second. A field-installed actuator may be used if desired.The actuator shaft has a -inch diameter and is designed to travel clockwise to close the damper and counter-clockwise to open the damper. There is an indicator on the end of the actuator shaft that can be used to determine the position of the damper.

Note: In order to maintain the UL rating for VariTrane electric coils, there must be four feet of straight unlined ductwork downstream of the reheat coil prior to any diffuser takeoffs.
After all connections are made, check that the entire ductwork system is airtight. In some high-pressure systems, duct sealer may be necessary. Provide insulation around the entire inlet collar (all the way to the unit casing). Use caution not to damage the flow tubes when making ductwork connections or insulating. Cut slits in the insulation for the flow tubes and secure with duct tape. If the unit is to be installed in a location with high humidity, external insulation around the heating coil should be installed as required. Water Coil Connections Water coil piping connections will be 3/8 or 7/8 OD. If necessary, you can change the coil connection from left-handed to righthanded (and vice-versa) by disconnecting the coil from the unit and rotating the coil like a steering wheel 180. The inlet piping should always be connected to the bottom connection of the coil regardless of handedness.

CAUTION
Equipment Damage
Note: When installing or replacing the actuator tighten the actuator set screw per the manufacturers instructions. Failure to follow the manufacturers specifications may result in unit malfunction.

Note:The minimum clearance for controls and heater controls should be 36 for all models except units with 575volt electric heaters, which require 48 of clearance. NEC and/or local codes override all clearance requirements.

VAV-SVN01E-EN

31

Unit Setup

Chart 2 Flow Sensor Delta P vs. Airflow Delivery


10

Flow Sensor Differential Pressure (inches water)

6 1 4 5

8"

10"

8" x 12" 12" 14"

16"

16" x 24"

0.1

0.01 10 100 Airflow (CFM) 1,000 10,000

Chart 3 Fan Motor Amperage Maximum PSC Fan Motor Amperage (FLA)
Fan Size
Parallel/Series 02SQ Parallel/Series 03SQ Parallel/Series 04SQ Parallel/Series 05SQ Parallel/Series 06SQ Parallel/Series 07SQ Low-height Parallel/Series 08SQ Low-height Parallel/Series 09SQ Series Low-height 10SQ Parallel Low-Height 10SQ

Maximum ECM Fan Motor Amperage (FLA)


277 VAV
0.7 1.6 2.0 2.4 3.8 4.7 2.5 2.5 5.0 3.5

HP VAC
1/8 1/3 1/3 1/2 1/2 1 1/3 1/3 2 x 1/8 2 x 1/8

115 VAC
1.6 4.3 5.5 6.7 5.5 5.5 11.0 9.4

347 VAC
.7 1.4 1.8 2.2 3.3 3.8 1.8 1.8 3.5 3.0

208
4.6 6.6

Fan Size

HP VAC

115 VAC
4.5 6.5 10.1 9.5 2.0 6.7 7.5

277 VAV
2.4 3.5 5.4 5.1 1.1 3.6 4.0

Parallel/Series 03SQ 1/3 Parallel/Series 04SQ 1/2 Parallel/Series 05SQ 1 Parallel/Series 06SQ 1 Low-height Parallel/Series 08SQ 1/2 Low-height Parallel/Series 09SQ 1/2 Low-height Series 10SQ 2 x 1/2

32

VAV-SVN01E-EN

Unit Setup

(SCR) Motor Speed Control Adjustment Procedure. In order to make units more convenient and efficient to balance, an SCR (silicone control rectifier) is provided as standard on all fan-powered units. The SCR is located on the side of the fan control box. To adjust the speed of the motor, the external knob must be rotated either clockwise or counterclockwise depending on the desired speed adjustment. There is an internal potentiometer (Figure 14) setting on the SCR controller that can be accessed by removing the control box cover. This internal potentiometer is set at the factory to the specific motor voltage. It may be necessary to adjust this in the field depending on the buildings power factor.

Figure 17 Internal Potentiometer

Electrically Commutated Motor (ECM) Trane offers an energy efficient ECM motor as a motor option. Balancing of an ECM motor is accomplished through electronic control adjustments on the ECM control board (see Figure 15). Potentiometer settings for a multitude of CFM settings are given in Charts 415. Other potentiometer settings can be determined either by interpolating from these tables or by using the following equation: CFMsetting = CFMmin + {(Potentiometer Setting) x [(CFMmax CFMmin)/100]} There is an LED on the ECM control board, which will blink one time for every 100 CFM of motor setting. For example, the LED on a unit set for 790 CFM will blink 7 times. The LED on a unit set for 800 CFM will blink 8 times.

120 v 208 v 277 v

Max

347 v
DO NOT SET THIS POTENTIOMETER BELOW THE VOLTAGE OF THE FAN MOTOR.

NOTE: Do not set this potentiometer below the voltage of the fan motor.

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

NOTE:This feature only verifies that the CFM is set properly. This feature does not indicate at what speed the motor is actually running.
The ECM must be load tested. In other words, the fan must be connected to properly test the ECM.

Figure 18 ECM Control Board

Figure 16 SCR

VAV-SVN01E-EN

33

Unit Setup

Chart 4 VPxF 03SQ ECM CFM Table

VPxF 03SQ
Motor Min CFM: 160 Motor Max CFM: 1085
CFM
160 170 179 188 198 207 216 226 235 244 254 263 272 282 291 300 310 319 328 338 347 356 366 375 385 394 403 413 422 431 441 450 459 469 478 487 497 506 515 525 534 543 553 562 571 581 590 599 609 618

L/sec
76 80 84 89 93 98 102 107 111 115 120 124 129 133 137 142 146 151 155 159 164 168 173 177 181 186 190 195 199 204 208 212 217 221 226 230 234 239 243 248 252 256 261 265 270 274 278 283 287 292

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
627 637 646 655 665 674 683 693 702 711 721 730 739 749 758 767 777 786 795 805 814 823 833 842 852 861 870 880 889 898 908 917 926 936 945 954 964 973 982 992 1001 1010 1020 1029 1038 1048 1057 1066 1076 1085

% L/sec
296 300 305 309 314 318 323 327 331 336 340 345 349 353 358 362 367 371 375 380 384 389 393 397 402 406 411 415 419 424 428 433 437 442 446 450 455 459 464 468 472 477 481 486 490 494 499 503 508 512

TENS Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

UNITS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

34

VAV-SVN01E-EN

Unit Setup

Chart 5 VPxF 04SQ ECM CFM Table

VPxF 04SQ
Motor Min CFM: 220 Motor Max CFM: 1510
CFM
220 233 246 259 272 285 298 311 324 337 350 363 376 389 402 415 429 442 455 468 481 494 507 520 533 546 559 572 585 598 611 624 637 650 663 676 689 702 715 728 741 754 767 780 793 806 819 832 845 859

L/sec
104 110 116 122 128 135 141 147 153 159 165 171 178 184 190 196 202 208 215 221 227 233 239 245 251 258 264 270 276 282 288 294 301 307 313 319 325 331 338 344 350 356 362 368 374 381 387 393 399 405

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
872 885 898 911 924 937 950 963 976 989 1002 1015 1028 1041 1054 1067 1080 1093 1106 1119 1132 1145 1158 1171 1184 1197 1210 1223 1236 1249 1262 1275 1288 1302 1315 1328 1341 1354 1367 1380 1393 1406 1419 1432 1445 1458 1471 1484 1497 1510

L/sec
411 417 424 430 436 442 448 454 461 467 473 479 485 491 497 504 510 516 522 528 534 540 547 553 559 565 571 577 584 590 596 602 608 614 620 627 633 639 645 651 657 663 670 676 682 688 694 700 706 713

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

35

Unit Setup

Chart 6 VPxF 05SQ ECM CFM Table

VPxF 05SQ
Motor Min CFM: 280 Motor Max CFM: 1850
CFM
280 296 312 327 343 359 375 391 407 423 438 454 470 486 502 518 534 549 565 581 597 613 629 645 661 676 692 708 724 740 756 772 787 803 819 835 851 867 883 898 914 930 946 962 978 994 1009 1025 1041 1057

% L/sec
132 140 147 155 162 170 177 184 192 199 207 214 222 229 237 244 252 259 267 274 282 289 297 304 312 319 327 334 342 349 357 364 372 379 387 394 402 409 417 424 431 439 446 454 461 469 476 484 491 499

Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
1073 1089 1105 1120 1136 1152 1168 1184 1200 1216 1231 1247 1263 1279 1295 1311 1327 1342 1358 1374 1390 1406 1422 1438 1454 1469 1485 1501 1517 1533 1549 1565 1580 1596 1612 1628 1644 1660 1676 1691 1707 1723 1739 1755 1771 1787 1802 1818 1834 1850

L/Sec
506 514 521 529 536 544 551 559 566 574 581 589 596 604 611 619 626 634 641 649 656 664 671 678 686 693 701 708 716 723 731 738 746 753 761 768 776 783 791 798 806 813 821 828 836 843 851 858 866 873

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

36

VAV-SVN01E-EN

Unit Setup

Chart 7 VPxF 06SQ ECM CFM Table

VPxF 06SQ
Motor Min CFM: 530 Motor Max CFM: 2100
CFM
530 546 562 577 593 609 625 641 657 673 688 704 720 736 752 768 784 799 815 831 847 863 879 895 911 926 942 958 974 990 1006 1022 1037 1053 1069 1085 1101 1117 1133 1148 1164 1180 1196 1212 1228 1244 1259 1275 1291 1307

% L/sec
250 258 265 273 280 287 295 302 310 317 325 332 340 347 355 362 370 377 385 392 400 407 415 422 430 437 445 452 460 467 475 482 490 497 505 512 520 527 535 542 549 557 564 572 579 587 594 602 609 617

TENS Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

UNITS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
1323 1339 1355 1370 1386 1402 1418 1434 1450 1466 1481 1497 1513 1529 1545 1561 1577 1592 1608 1624 1640 1656 1672 1688 1704 1719 1735 1751 1767 1783 1799 1815 1830 1846 1862 1878 1894 1910 1926 1941 1957 1973 1989 2005 2021 2037 2052 2068 2084 2100

L/sec
624 632 639 647 654 662 669 677 684 692 699 707 714 722 729 737 744 752 759 767 774 782 789 796 804 811 819 826 834 841 849 856 864 871 879 886 894 901 909 916 924 931 939 946 954 961 969 976 984 991

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

`UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

37

Unit Setup

Chart 8 VSxF 03SQ ECM CFM Table

VSxF 03SQ
Motor Min CFM: 200 Motor Max CFM: 1100
CFM
200 209 218 227 236 246 255 264 273 282 291 300 309 318 327 336 346 355 364 373 382 391 400 409 418 427 436 446 455 464 473 482 491 500 509 518 527 536 546 555 564 573 582 591 600 609 618 627 636 646

L/sec
94 99 103 107 112 116 120 124 129 133 137 142 146 150 154 159 163 167 172 176 180 185 189 193 197 202 206 210 215 219 223 227 232 236 240 245 249 253 257 262 266 270 275 279 283 287 292 296 300 305

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFN
655 664 673 682 691 700 709 718 727 736 745 755 764 773 782 791 800 809 818 827 836 845 855 864 873 882 891 900 909 918 927 936 945 955 964 973 982 991 1000 1009 1018 1027 1036 1045 1055 1064 1073 1082 1091 1100

% L/sec
309 313 318 322 326 330 335 339 343 348 352 356 360 365 369 373 378 382 386 390 395 399 403 408 412 416 420 425 429 433 438 442 446 451 455 459 463 468 472 476 481 485 489 493 498 502 506 511 515 519

TENS Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

UNITS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

38

VAV-SVN01E-EN

Unit Setup

Chart 9 VSxF 04SQ ECM CFM Table

VSxF 04SQ
Motor Min CFM: 275 Motor Max CFM: 1500
CFM
275 288 300 312 325 337 350 362 374 387 399 411 424 436 449 461 473 486 498 510 523 535 548 560 572 585 597 609 622 634 646 659 671 684 696 708 721 733 745 758 770 783 795 807 820 832 844 857 869 882

% L/sec
130 136 142 147 153 159 165 171 177 183 188 194 200 206 212 218 223 229 235 241 247 253 258 264 270 276 282 288 293 299 305 311 317 323 328 334 340 346 352 358 363 369 375 381 387 393 399 404 410 416

TENS Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

UNITS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
894 906 919 931 943 956 968 980 993 1005 1018 1030 1042 1055 1067 1079 1092 1104 1117 1129 1141 1154 1166 1178 1191 1203 1215 1228 1240 1253 1265 1277 1290 1302 1314 1327 1339 1352 1364 1376 1389 1401 1413 1426 1438 1451 1463 1475 1488 1500

L/sec
422 428 434 439 445 451 457 463 469 474 480 486 492 498 504 509 515 521 527 533 539 544 550 556 562 568 574 579 585 591 597 603 609 615 620 626 632 638 644 650 655 661 667 673 679 685 690 696 702 708

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

39

Unit Setup

Chart 10 VSxF 05SQ ECM CFM Table

VSxF 05SQ
Motor Min CFM: 350 Motor Max CFM: 2050
CFM
350 367 385 402 419 436 453 470 488 505 522 539 556 573 591 608 625 642 659 676 694 711 728 745 762 779 797 814 831 848 865 882 900 917 934 951 968 985 1003 1020 1037 1054 1071 1088 1106 1123 1140 1157 1174 1192

L/sec
165 173 181 190 198 206 214 222 230 238 246 254 263 271 279 287 295 303 311 319 327 335 344 352 360 368 376 384 392 400 408 416 425 433 441 449 457 465 473 481 489 498 506 514 522 530 538 546 554 562

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
1209 1226 1243 1260 1277 1295 1312 1329 1346 1363 1380 1398 1415 1432 1449 1466 1483 1501 1518 1535 1552 1569 1586 1604 1621 1638 1655 1672 1689 1707 1724 1741 1758 1775 1792 1810 1827 1844 1861 1878 1895 1913 1930 1947 1964 1981 1998 2016 2033 2050

L/sec
570 579 587 595 603 611 619 627 635 643 651 660 668 676 684 692 700 708 716 724 732 741 749 757 765 773 781 789 797 805 814 822 830 838 846 854 862 870 878 886 895 903 911 919 927 935 943 951 959 967

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

40

VAV-SVN01E-EN

Unit Setup

Chart 11 VSxF 06SQ ECM CFM Table

VSxF 06SQ
Motor Min CFM: 700 Motor Max CFM: 2500
CFM
700 718 737 755 773 791 809 827 846 864 882 900 918 937 955 973 991 1009 1027 1046 1064 1082 1100 1118 1137 1155 1173 1191 1209 1227 1246 1264 1282 1300 1318 1336 1355 1373 1391 1409 1427 1446 1464 1482 1500 1518 1536 1555 1573 1591

% L/sec
330 339 348 356 365 373 382 391 399 408 416 425 433 442 451 459 468 476 485 493 502 511 519 528 536 545 554 562 571 579 588 596 605 614 622 631 639 648 656 665 674 682 691 699 708 717 725 734 742 751

TENS Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

UNITS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
1609 1627 1646 1664 1682 1700 1718 1736 1755 1773 1791 1809 1827 1846 1864 1882 1900 1918 1936 1955 1973 1991 2009 2027 2046 2064 2082 2100 2118 2136 2155 2173 2191 2209 2227 2245 2264 2282 2300 2318 2336 2355 2373 2391 2409 2427 2445 2464 2482 2500

% L/sec
759 768 777 785 794 802 811 820 828 837 845 854 862 871 880 888 897 905 914 922 931 940 948 957 965 974 983 991 1000 1008 1017 1025 1034 1043 1051 1060 1068 1077 1085 1094 1103 1111 1120 1128 1137 1146 1154 1163 1171 1180

TENS Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

UNITS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

41

Unit Setup

Chart 12 LPxF 08SQ ECM CFM Table

LPxF 08SQ
Motor Min CFM: 100 Motor Max CFM: 460
CFM
100 103 107 111 114 118 121 125 129 132 136 140 143 147 151 154 158 162 165 169 172 176 180 183 187 191 194 198 202 205 209 212 216 220 223 227 231 234 238 242 245 249 253 256 260 263 267 271 274 278

L/sec
47 49 50 52 54 56 57 59 61 62 64 66 68 69 71 73 75 76 78 80 81 83 85 87 88 90 92 93 95 97 99 100 102 104 105 107 109 111 112 114 116 117 119 121 123 124 126 128 129 131

% % Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
282 285 289 293 296 300 303 307 311 314 318 322 325 329 333 336 340 344 347 351 354 358 362 365 369 373 376 380 384 387 391 394 398 402 405 409 413 416 420 424 427 431 435 438 442 445 449 453 456 460

L/sec
133 135 136 138 140 142 143 145 147 148 150 152 154 155 157 159 160 162 164 166 167 169 171 172 174 176 178 179 181 183 184 186 188 190 191 193 195 196 198 200 202 203 205 207 209 210 212 214 215 217

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

42

VAV-SVN01E-EN

Unit Setup

Chart 13 LPxF 09SQ ECM CFM Table

LPxF 09SQ
Motor Min CFM: 250 Motor Max CFM: 1025
CFM
250 258 265 273 281 289 297 305 312 320 328 336 344 352 359 367 375 383 391 399 406 414 422 430 438 446 453 461 469 477 485 493 500 508 516 524 532 540 547 555 563 571 579 587 594 602 610 618 626 634

% L/sec
118 122 125 129 133 136 140 144 147 151 155 159 162 166 170 173 177 181 184 188 192 196 199 203 207 210 214 218 221 225 229 232 236 240 244 247 251 255 258 262 266 269 273 277 281 284 288 292 295 299

TENS Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

UNITS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
641 649 657 665 673 680 688 696 704 712 720 727 735 743 751 759 767 774 782 790 798 806 814 821 829 837 845 853 861 868 876 884 892 900 908 915 923 931 939 947 955 962 970 978 986 994 1002 1009 1017 1025

L/sec
303 306 310 314 317 321 325 329 332 336 340 343 347 351 354 358 362 365 369 373 377 380 384 388 391 395 399 402 406 410 414 417 421 425 428 432 436 439 443 447 450 454 458 462 465 469 473 476 480 484

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

43

Unit Setup

Chart 14 LSxF 08SQ ECM CFM Table

LSxF 08SQ
Motor Min CFM: 100 Motor Max CFM: 460
CFM
100 103 107 111 114 118 121 125 129 132 136 140 143 147 151 154 158 162 165 169 172 176 180 183 187 191 194 198 202 205 209 212 216 220 223 227 231 234 238 242 245 249 253 256 260 263 267 271 274 278

L/sec
47 49 50 52 54 56 57 59 61 62 64 66 68 69 71 73 75 76 78 80 81 83 85 87 88 90 92 93 95 97 99 100 102 104 105 107 109 111 112 114 116 117 119 121 123 124 126 128 129 131

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
282 285 289 293 296 300 303 307 311 314 318 322 325 329 333 336 340 344 347 351 354 358 362 365 369 373 376 380 384 387 391 394 398 402 405 409 413 416 420 424 427 431 435 438 442 445 449 453 456 460

L/sec
133 135 136 138 140 142 143 145 147 148 150 152 154 155 157 159 160 162 164 166 167 169 171 172 174 176 178 179 181 183 184 186 188 190 191 193 195 196 198 200 202 203 205 207 209 210 212 214 215 217

% Settings
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

44

VAV-SVN01E-EN

Unit Setup

Chart 15 LSxF 09SQ ECM CFM Table

LSxF 09SQ
Motor Min CFM: 240 Motor Max CFM: 950
CFM
240 247 255 262 269 276 283 290 298 305 312 319 326 333 341 348 355 362 369 376 384 391 398 405 412 419 427 434 441 448 455 462 470 477 484 491 498 505 513 520 527 534 541 548 556 563 570 577 584 592

% L/sec
113 117 120 123 127 130 134 137 140 144 147 151 154 157 161 164 167 171 174 178 181 184 188 191 195 198 201 205 208 211 215 218 222 225 228 232 235 239 242 245 249 252 255 259 262 266 269 272 276 279

TENS Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

UNITS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
599 606 613 620 627 635 642 649 656 663 670 678 685 692 699 706 713 721 728 735 742 749 756 764 771 778 785 792 799 807 814 821 828 835 842 850 857 864 871 878 885 893 900 907 914 921 928 936 943 950

L/sec
283 286 289 293 296 299 303 306 310 313 316 320 323 327 330 333 337 340 343 347 350 354 357 360 364 367 371 374 377 381 384 387 391 394 398 401 404 408 411 415 418 421 425 428 431 435 438 442 445 448

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

VAV-SVN01E-EN

45

Unit Setup

Chart 15 LSxF 10SQ ECM CFM Table

LSxF 10SQ
Motor Min CFM: 400 Motor Max CFM: 1800
CFM
400 414 428 443 457 471 485 499 513 527 542 556 570 584 598 612 626 641 655 669 683 697 711 725 740 754 768 782 796 810 824 838 853 867 881 895 909 923 937 952 966 980 994 1008 1022 1036 1051 1065 1079 1093

L/sec
189 196 202 209 216 222 229 236 242 249 256 262 269 276 282 289 296 302 309 316 322 329 336 342 349 356 362 369 376 382 389 396 402 409 416 422 429 436 442 449 456 462 469 476 482 489 496 502 509 516

% Setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

TENS Switch
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

CFM
1107 1121 1135 1150 1164 1178 1192 1206 1220 1234 1249 1263 1277 1291 1305 1319 1333 1348 1362 1376 1390 1404 1418 1432 1447 1461 1475 1489 1503 1517 1531 1545 1560 1574 1588 1602 1616 1630 1644 1659 1673 1687 1701 1715 1729 1743 1758 1772 1786 1800

L/sec
523 529 536 543 549 556 563 569 576 583 589 596 603 609 616 623 629 636 643 649 656 663 669 676 683 689 696 703 709 716 723 729 736 743 749 756 763 769 776 783 789 796 803 809 816 823 829 836 843 850

% Setting
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

TENS Switch
5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9 9 9 0

UNITS Switch
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0

46

VAV-SVN01E-EN

Wiring Diagrams

Figure 19 Single-Duct Units (Electronic or DDC/UCM)


Line Voltage (See Nameplate)

SINGLE DUCT UNITS - ELECTRONIC OR DDC/UCM HEATER TERMINALS - TYPICAL OF SINGLE PHASE VOLTAGES
SINGLE PHASE LINE VOLTAGES 208 240 277 347 480

L1 L2 N - 480 L1 L2 - 208, 240 L1 N - 277, 347


L1 N

TB4
L1 N

STAGES 1 2 3

Contactor 1st Stage

Manual Reset Cutout

Optional Fuse

Contactor 2nd Stage

HEATER CONTACTORS Magnetic Contactors (MAGN) Mercury Contactors (MERC)

Optional Fuse (208, 240, and 480) Optional Transformer

Contactor 3rd Stage

Auto Reset Air Flow Switch Thermal Cutout

L1

N
G

Optional Door Disconnect Switch

ORG

RED

PUR

BRN

24V Input from Controller

24V Output to Controller

SINGLE DUCT UNITS - ELECTRONIC OR DDC/UCM HEATER TERMINALS - TYPICAL OF THREE PHASE VOLTAGES
Contactor 1st Stage

L1 L2 L3 - 208,480,600 Line Voltage (See Nameplate) L1 L2 L3

BLU

YEL

TB4
L1 L2 L3

THREE PHASE LINE VOLTAGES 208 480 575

STAGES 1 2 3
Contactor 2nd Stage Manual Reset Cutout

HEATER CONTACTORS Magnetic Contactors (MAGN) Mercury Contactors (MERC)

Optional Fuse

Notes: FACTORY INSTALLED 1. FIELD INSTALLED OPTIONAL 2. Actual heater wiring diagrams are supplied with each unit (3-stage shown). 3. Load carrying P.E. Switches or Contactors are supplied depending upon amp drawn. 4. Air Flow Switch, Auto Reset Thermal Cutout and Manual Reset Cutout are provided as standard. 5. Heater Line Fuses, Transformers, and Door Interlocking Disconnect are optional. 6. If transformer is not ordered, a separate 24-volt power supply is required for operation of unit controls.

Contactor 3rd Stage Optional Transformer Auto Reset Thermal Cutout Air Flow Switch

L1 L2 L3

ORG

PUR

BRN

RED

BLU

YEL

Optional Door Disconnect Switch

24V Input from Controller

24V Output to Controller

VAV-SVN01E-EN

47

Wiring Diagrams

Figure 20 Single-Duct Units (Pneumatic Controls)


SINGLE DUCT UNITS - PNEUMATIC CONTROL HEATER TERMINAL - TYPICAL OF SINGLE PHASE VOLTAGES
SINGLE PHASE LINE VOLTAGES 208 240 277 347 480
Line Voltage (See Nameplate) L1 L2 - 208, 240 L1 L2 N - 480 L1 N - 277, 347
L1 N G L1 N

TB4

STAGES 1 2 3

Contactors

Manual Reset Cutout

Optional Fuse

PE Switch 1st Stage

HEATER CONTACTORS P.E. with Magnetic Contactors (PEMA) P.E. with Mercury Contactors (PEME)
P.E. Switch 2nd Stage

Auto Reset Thermal Cutout

Air Flow Switch

L1 N

P.E. Switch 3rd Stage

Optional Door Disconnect Switch

SINGLE DUCT UNITS - PNEUMATIC CONTROL HEATER TERMINAL - TYPICAL OF THREE PHASE VOLTAGES
THREE PHASE LINE VOLTAGES 208 480 575
Manual Reset Cutout

Line Voltage (See Nameplate)

L1 L2 L3 - 208, 600 L1 L2 L3 N - 480 L1 L2 L3


G

STAGES 1 2 3

Contactors

Optional Fuse

L1 L2 L3
TB4

HEATER CONTACTORS P.E. with Magnetic Contactors (PEMA) P.E. with Mercury Contactors (PEME)

PE Switch 1st Stage

NOTE: FACTORY INSTALLED FIELD INSTALLED OPTIONAL 2. Actual heater wiring diagram is supplied with each unit (3-stage shown). Load carrying P.E. Switches or Contactors are supplied depending upon amp drawn. Air Flow Switch, Auto Reset Thermal Cutout and Manual Reset Cutout provided as standard. Heater Line Fuses and Door Interlocking Disconnect are optional.
P.E. Switch 2nd Stage

Auto Reset Thermal Cutout

Air Flow Switch

1.

L1 L2 L3

N G N

P.E. Switch 3rd Stage

3.

Optional Door Disconnect Switch

4.

5.

48

VAV-SVN01E-EN

Wiring Diagrams

Figure 21 Fan-Powered Units (Electronic or DDC/UCM)


Line Voltage (See Nameplate)

FAN-POWERED UNITS - ELECTRONIC OR DDC/UCM HEATER TERMINALS - TYPICAL OF SINGLE PHASE VOLTAGES
SINGLE PHASE LINE VOLTAGES 208 240 277 347 480

L1 L2 N - 208, 240, 480 L1 N - 277, 347


L1 L2 N

TB4

STAGES 1 2

L1 L2 N

Contactor 1st Stage

Manual Reset Cutout

Optional Fuse

HEATER CONTACTORS Magnetic Contactors (MAGN) Mercury Contactors (MERC)


Contactor 2nd Stage Optional Air Flow Switch

Auto Reset Thermal Cutout

L1 L2 N
G

Optional Door Disconnect Switch

24V Input from Controller

115 or 277V Output to Motor

FAN-POWERED UNITS - ELECTRONIC OR DDC/UCM HEATER TERMINALS - TYPICAL OF THREE PHASE VOLTAGES
Contactor 1st Stage

WHT

PUR

BRN

BLK

OR

Line Voltage (See Nameplate)

L1 L2 L3 N - 208,480,600 L1 L2 L3 N

THREE PHASE LINE VOLTAGES 208 480 575

TB4
L1 L2 L3 N

STAGES 1 2

Manual Reset Cutout

Optional Fuse

HEATER CONTACTORS Magnetic Contactors (MAGN) Mercury Contactors (MERC)

Contactor 2nd Stage

Notes: FACTORY INSTALLED 1. FIELD INSTALLED OPTIONAL 2. Actual heater wiring diagrams are supplied with each unit (2-stage shown). 3. Load carrying P.E. Switches or Contactors are supplied depending upon amp drawn. 4. Auto Reset Thermal Cutout and Manual Reset Cutout are provided as standard. 5. Heater Line Fuses, Airflow Switch, and Door Interlocking Disconnect are optional.
24V Input from Controller 115 or 277V Output to Motor
PUR BRN WH OR BK

Optional Auto Reset Air Flow Thermal Cutout Switch

L1 L2 L3

Optional Door Disconnect Switch

VAV-SVN01E-EN

49

Wiring Diagrams

Figure 22 Fan-Powered Units (Pneumatic Controls)


FAN-POWERED UNITS - PNEUMATIC CONTROL HEATER TERMINAL - TYPICAL OF SINGLE PHASE VOLTAGES
SINGLE PHASE LINE VOLTAGES 208 240 277 347 480
Line Voltage (See Nameplate) L1 L2 N - 208, 240, 480 L1 N - 277, 347
L1 L2 N G L1 L2 N

Manual Reset Cutout

TB4

Contactors

STAGES 1 2 3

Optional Fuse

PE Switch 1st Stage

HEATER CONTACTORS P.E. with Magnetic Contactors (PEMA) P.E. with Mercury Contactors (PEME)

Auto Reset Thermal Cutout Optional Air Flow Switch

L1 L2 N G

Optional Door Disconnect Switch

115 to 277V Output to Motor

FAN-POWERED UNITS - PNEUMATIC CONTROL HEATER TERMINAL - TYPICAL OF THREE PHASE VOLTAGES

Line Voltage (See Nameplate)

WHT

BLK

L1 L2 L3 N - 208, 480, 575 L1 L2 L3 N


G

THREE PHASE LINE VOLTAGES 208 480 575

STAGES 1 2 3
PE Switch 1st Stage

Contactors

Manual Reset Cutout

Optional Fuse

L1 L2 L3 N
TB4

HEATER CONTACTORS P.E. with Magnetic Contactors (PEMA) P.E. with Mercury Contactors (PEME)

P.E. Switch 2nd Stage

NOTE:
L1 L2 L3 N G N

1.

FACTORY INSTALLED FIELD INSTALLED OPTIONAL


Optional Air Flow Switch Auto Reset Thermal Cutout

2.

Actual heater wiring diagram is supplied with each unit (1 and 2-stage shown). Load carrying P.E. Switches or Contactors are supplied depending upon amp drawn. Auto Reset Thermal Cutout and Manual Reset Cutout provided as standard. Heater Line Fuses, Door Interlocking Disconnect, and Airflow Switch are optional.

3.

Optional Door Disconnect Switch


WHT BLK

4.

5.

115 to 277V Output to Motor

50

VAV-SVN01E-EN

Wiring Diagrams

Figure 23 Fan-Powered Control Boxes


Fan-powered Control Box with Electronic or DDC Controls LINE VOLTAGE OR FROM HEATER TERMINAL Fan-powered Control Box with Pneumatic Controls Duct Pressure Switch Option LINE VOLTAGE OR FROM HEATER TERMINAL GREEN GROUND SCREW

GREEN GROUND SCREW TRANSFORMER

L1

}
L1 N

5. 6.
TRANSFORMER
24V

5.

TO VAV CONTROLLER

W-COM

W-COM

BK

FAN CONTROL BOX


W BK BR CAPACITOR BR MOTOR FAN BR CAPACITOR BR MOTOR FAN W BK

BK

DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

DUCT PRESSURE MAIN CONTROL

6.

GREEN GROUND SCREW

}
L1 N

HAZARDOUS VOLTAGE!

USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

NOTES: 1. FACTORY INSTALLED BY OTHERS OPTIONAL OR ALTERNATE CIRCUITRY


W-COM

2. 3. 4. 5.

CAPACITOR IS INSTALLED ON FAN HOUSING. FUSE IS OPTIONAL. DETERMINED BY MOTOR VOLTAGE ON ORDER. VOLTAGE FOUND ON UNIT NAMEPLATE. FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
BR CAPACITOR BR

BK

DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED EXTERNAL TO CONTROL BOX.

6.

VAV-SVN01E-EN

Y
24V

BL BR R

BK

DISCONNECT SWITCH

BK

NO

BK

DISCONNECT SWITCH

BK

2.
NC
BK BK MOTOR RELAY BR 1 R W W 24V 3 2 4 BK BK FUSE W DUCT PRESSURE SWITCH BK MOTOR RELAY BR 2 4 BK W

2.

BK BK FUSE

4.

24V R

4.

W W

TERMINAL BLOCK

MOTOR SPEED CONTROL

TERMINAL BLOCK

MOTOR SPEED CONTROL

FAN CONTROL BOX

3.

3.

WARNING

Fan-powered Control Box with Pneumatic Controls

LINE VOLTAGE OR FROM HEATER TERMINAL

5.

BK NO C BK

NO C NC BK P.E. SWITCH-2

DISCONNECT SWITCH

BK

2.
BK W BK BK

CAUTION

NC P.E. SWITCH-1

6.

NO BK C NC P.E. SWITCH W W FUSE

4.

TERMINAL BLOCK

MOTOR SPEED CONTROL

FAN CONTROL BOX


W BK MOTOR FAN

3.

51

Wiring Diagrams

Figure 24 Fan-Powered Units with ECM


Fan-powered Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located in the fan control box.)
LINE VOLTAGE OR FROM HEATER TERMINAL

Fan-powered Control Box w/ ECM with Pneumatic Controls


Duct Pressure Switch Option
LINE VOLTAGE FAN MOTOR

4.

L1

4.
BK

GR GREEN GROUND SCREW TERMINAL BLOCK DISCONNECT SWITCH 2. 3.


FUSE
2 4

Y
BK

}
W

FAN MOTOR

OR FROM HEATER TERMINAL

GR
NEUT. RED 24V RED

BK

GREEN GROUND SCREW

BK

BK

TERMINAL BLOCK

3. FUSE

2. DISCONNECT SWITCH W BK

W BK

W
1 24V 3

ECM BOARD

G R

BL

Y
5. NO BL
POWER FACTOR CORRECTION CHOKE
NEUT. RED 24V RED

BK

3.

MOTOR RELAY

Y
24V

BL

W BK

24V

SWITCH BK

TRANSFORMER

BL

ECM BOARD

TRANSFORMER POWER FACTOR CORRECTION CHOKE FAN CONTROL BOX

FAN CONTROL BOX

WARNING
HAZARDOUS VOLTAGE! DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

Fan-powered Control Box with Pneumatic Controls


LINE VOLTAGE OR FROM HEATER TERMINAL
FAN MOTOR

4.

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

GR GREEN GROUND SCREW TERMINAL BLOCK DISCONNECT SWITCH 2.


BK W BK

DUCT PRESSURE MAIN CONTROL

3.
FUSE

BK

BL
Y

5.

BK NO C NC P.E. SWITCH-1 BK BK

NO C NC P.E. SWITCH-2

POWER FACTOR CORRECTION CHOKE

Y
24V

NEUT. RED

24V RED

BK

BL

TRANSFORMER

W BK

1.

FACTORY INSTALLED BY OTHERS OPTIONAL OR ALTERNATE CIRCUITRY DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED EXTERNAL TO CONTROL BOX. FUSE IS OPTIONAL. DETERMINED BY MOTOR VOLTAGE ON ORDER. VOLTAGE FOUND ON UNIT NAMEPLATE. FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

C NC P.E. SWITCH

ECM BOARD

2.

FAN CONTROL BOX

3. 4.

5.

G R

NOTES:

NO

G R

BL C TO VAV NC DUCT PRESSURE

CONTROLLER Y

52

VAV-SVN01E-EN

Wiring Diagrams

Figure 25 Fan-Powered Low-Height Units


Fan-Powered Low-Height Control Box with Electronic or DDC Controls
CAPACITOR FAN 3. 5. LINE VOLTAGE OR FROM HEATER TERMINAL CAPACITOR MOTOR BR BR CAPACITOR BR BR W BK W BK FAN MOTOR 3. FAN MOTOR 2 (SIZE 10 ONLY) 3. FAN MOTOR 2 (SIZE 10 ONLY)

Fan-Powered Low-Height Control Box with Pneumatic Controls


Duct Pressure Switch Option

}
L1 N

GREEN GROUND SCREW MOTOR SPEED CONTROL DISCONNECT BK W SWITCH 2.

5. LINE VOLTAGE OR FROM HEATER TERMINAL


L1 N

CAPACITOR BR

3. BR BR W BR W BK

GREEN GROUND SCREW W W BK

2. MOTOR SPEED CONTROL W W

BK

2.
TERMINAL BLOCK

W
2.

4. FUSE

BK

W BR W BK

DISCONNECT

TERMINAL BLOCK

SWITCH

BR
W

BK W or BR BK 2 4 MOTOR RELAY BR TRANSFORMER Y

BK

BL BR R

4. TO VAV 6. FUSE BK BK BK

BK

24V

CONTROLLER

2 24V
BL Y TRANSFORMER

4
BL

NO

BL 1 24V 3 R

C NC DUCT PRESSURE

1 24V 3
MOTOR RELAY FAN CONTROL BOX

FAN CONTROL BOX

SWITCH

WARNING
HAZARDOUS VOLTAGE! DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

Fan-Powered Low-Height Control Box with Pneumatic Controls


FAN MOTOR

3.

FAN MOTOR 2 (SIZE 10 ONLY)

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

5. LINE VOLTAGE OR FROM HEATER TERMINAL

3.
BR BK BR CAPACITOR W

BR

CAPACITOR

W BK

L1

GREEN GROUND SCREW


MOTOR SPEED CONTROL

DUCT PRESSURE MAIN CONTROL

2.
BK W TERMINAL BLOCK

6.

BK NO C NC P.E. SWITCH-1 BK BK

NO C NC P.E. SWITCH-2
4.
FUSE BK W

2.
DISCONNECT SWITCH

W BR W

BK

BK

NOTES: 1. FACTORY INSTALLED BY OTHERS OPTIONAL OR ALTERNATE CIRCUITRY DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED EXTERNAL TO CONTROL BOX. CAPACITOR IS INSTALLED ON FAN HOUSING.
FAN CONTROL BOX NO BK

C
NC P.E. SWITCH

2. 3. 4. 5.

FUSE IS OPTIONAL. DETERMINED BY MOTOR VOLTAGE ON ORDER. VOLTAGE FOUND ON UNIT NAMEPLATE. FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

6.

VAV-SVN01E-EN

53

Wiring Diagrams

Figure 26 Fan-Powered Low-Height Units with ECM


Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located in the fan control box.)
LINE VOLTAGE 4. OR FROM HEATER TERMINAL

Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls


Duct Pressure Switch Option
LINE VOLTAGE OR FROM HEATER TERMINAL

4.

FAN MOTOR

FAN MOTOR 2 (SIZE 10 ONLY)

FAN MOTOR

FAN MOTOR 2 (SIZE 10 ONLY)

GR GREEN GROUND SCREW TERMINAL BLOCK DISCONNECT SWITCH 2. 3. FUSE


1 2 4

BK
GR BK W

W BK W BK

Y
NEUT. RED 24V RED
3. FUSE

BK

BK

GREEN GROUND SCREW

W BK TERMINAL BLOCK

2. DISCONNECT SWITCH W BK Y

BL

W BK

24V

ECM BOARD

G R

5. NO BL BL
RED RED

MOTOR RELAY

NEUT.

24V

24V

Y 24V BK BL

}
FAN CONTROL BOX

NC DUCT PRESSURE SWITCH BK

TO VAV CONTROLLER

W BK

BL

ECM BOARD

TRANSFORMER

TRANSFORMER

FAN CONTROL BOX

WARNING
HAZARDOUS VOLTAGE! DISCONNECT, LOCK OUT AND TAG ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. DISCHARGE MOTOR START/RUN CAPACITORS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls

4. LINE VOLTAGE OR FROM HEATER TERMINAL

FAN MOTOR

FAN MOTOR 2 (SIZE 10 ONLY)

GR GREEN GROUND SCREW TERMINAL BLOCK DISCONNECT SWITCH 2. W BK W BK

BK

DUCT PRESSURE MAIN CONTROL

5.

BL
W

BK NO C NC P.E. SWITCH-1 BK BK

NO C NC

3. FUSE

BL
Y

NEUT.

24V RED

P.E. SWITCH-2
24V BK

Y
RED

BL

NOTES: 1. FACTORY INSTALLED BY OTHERS OPTIONAL OR ALTERNATE CIRCUITRY DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED EXTERNAL TO CONTROL BOX. FUSE IS OPTIONAL.

TRANSFORMER

W BK

NO C NC P.E. SWITCH

ECM BOARD

2.

3. 4.

FAN CONTROL BOX

DETERMINED BY MOTOR VOLTAGE ON ORDER. VOLTAGE FOUND ON UNIT NAMEPLATE. FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

5.

G R

G R

54

VAV-SVN01E-EN

Maintenance

Periodic maintenance of the VariTrane product is minimal, but necessary for efficient operation. Routine maintenance consists of inspecting/replacing the air filters of the fan-powered terminals. Motors Both the PSC (permanent split capacitor) and the ECM (Electrically Commutated Motor) require no lubrication during its normal life of operation. FanWheel: Periodically, the fan wheel should be inspected for dirt or debris and cleaned as necessary. Filter The filter on fan-powered terminals will need to be inspected/replaced routinely depending on the environmental conditions of the plenum. Water Coil Water coils should be inspected and the fins should be cleaned periodically. Water coils have been provided with an access panel as standard to assist with inspection and cleaning. Fan Motor Replacement

Figure 27 Standard Motor Removal

Figure 28 Low-Height Motor Removal

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

Standard height fan-powered series and parallel fan motors are replaceable through the filter opening and the standard sliding side access panel. To access the fan motor, the fan housing must be detached by removing the mounting bolts that hold the housing to the fan board. Removing the entire housing allows the fan motor, fan housing, and fan wheel to be re-aligned on a workbench or floor and prevent any possible fan wheel rubbing that may occur. Removing the housing will provide access to the motor shaft set screw that holds the fan wheel to the motor shaft. The low-height fan assembly was designed with an inlet ring that assists with removal of the fan motor. To access the fan motor assembly, the bottom panel must be removed. The inlet ring is held in place by six bolts and three motor mount bolts. Remove these bolts and the motor and fan wheel will come out of the fan housing.

WARNING
Rotating Components!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
VAV-SVN01E-EN 55

Installation of Diffusers

General All units must be installed upright and level as indicated by the arrow on the side of the units. Return air slots should be placed perpendicular and offset to the slot diffusers to avoid shortcircuiting of air distribution patterns. Place the unit in its approximate final position and check that it is upright and level. For single- slot units, engage the back of the diffuser over the t-bar with an edge and both ends resting on the t-bar. For double-slot units, slide the unit over the t-bar. For centernotch units, place diffuser over the t-bar, straddling it across a t-bar and resting on the units ends. If the unit has a fire damper, make sure that the damper is still fully open. Diffuser discharge must always be flush with the ceiling tiles to assure the proper airflow (Coanda effect). Diffusers require specific installation information when mounting to a desired ceiling type. Select the ceiling type that closely matches the job site application and use the following procedures. T-Bar Ceiling Finish installation of the diffuser in t-bar ceiling. (See Figure 29.) Follow these procedures before the ceiling construction is completed. 1. Position the diffuser at each end resting directly on the structural t-bar for support and the t-bar fitting into the channel provided at the unit discharge air throw. 2.A ceiling tile support flange is provided on each side of the discharge slot of the unit.Trim ceiling tile approximately 1 inches each to allow for width of discharge slot. For revealed edge ceilings, tile must be cut in a Z pattern. 3.Install ceiling tiles in usual manner with cut edges resting on the flanges of the air slot.

Figure 29 Diffuser Installation in T-Bar Ceiling

Drywall/Plaster Ceiling Finish installation of diffusers in plaster ceiling. Follow these procedures before completing the ceiling construction (Figure 31). 1. Suspend the units above the intended ceiling level and their approximate horizontal positions and finish running flexible ductwork. 2.After drywall and/or plaster is installed, cut openings to receive the diffuser air outlets. Also, allow for access openings to complete installation and service of the unit.

Concealed Spline Ceiling Follow these procedures to finish installation of control and satellite diffusers and concealed spline for suspension ceilings before completing the ceiling construction (Figure 30). Place the units in their approximate final positions. If using the trim angle diffuser, its slots must be even with the spline level. If applying the trim accessory, the bottom of the diffuser must be level with the finished ceiling. If installing the trim accessory, insert the trim into the ceiling opening from below and engage the diffuser slot to the trim t-bar structure. With bottom flange of trim accessory against the ceiling, and using the pre-drilled holes in the flange as a guide, drill holes in the flange of the diffuser. Join the diffuser and trim accessory with self-taping sheet metal.

3.Slide the trim accessory up and into the ceiling opening. Using the rim accessory as a template, drill four guide holes in the lip of the diffuser slot. Lower the unit onto the trim frame and attach with the sheet metal screws.

Note:The bottom of the throat section must be parallel to the ceilings for proper air distribution.

CAUTION
Equipment Damage!
Do not install trim frame into ceiling using screws. When diffuser is placed on the trim frames, it will pull out.

Figure 31 Diffuser with Trim Accessory Installation in Plaster Ceiling

Figure 30 Diffuser with Trim Accessory Installation in Concealed Spline Ceiling

Plaster trim frame attaches with 24 tension clips on the side of the diffuser.

56

VAV-SVN01E-EN

Maintenance/ Service Log

Date

T ag

Serial #

Service Notes

VAV-SVN01E-EN

57

Maintenance/ Service Log

Date

T ag

Serial #

Service Notes

58

VAV-SVN01E-EN

Notes

VAV-SVN01E-EN

59

Literature Order Number File Number Supersedes

VAV-SVN01E-EN SL -TD-000-VAV-SVN01E-EN-0606 SL -TD-000-VAV-SVN01D-EN-0905 Inland

Trane An American Standard Company www.trane.com For more information contact your local district office or e-mail us at [email protected]

Stocking Location

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.

You might also like