All VariTrane VAV Models with pneumatic, electronic, DDC controls and diffusers.
June 2006
VAV-SVN01E-EN
VAV-SVN01E-EN
Contents
WARNING
Fiberglass Wool!
WARNING: ALL INSULATED UNITS (except closed-cell foam insulation) CONTAIN FIBERGLASS WOOL! Read this literature prior to installation for proper instruction. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
Single-Duct Units
Digit 1, 2Unit Type VC VariTrane single-duct Digit 3Reheat C Cooling Only E Electric Heat W Hot Water Heat Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 04 4" inlet (225 cfm) 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 8" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) 24 24" x 16" inlet (8000 cfm) Digit 7 , 8Not Used 00 N/A Digit 9Not Used 0 N/A Digit 10, 11Design Sequence H0 Fourth (factory assigned) Digit 12, 13, 14, 15Controls ENON No controls, field-installed DDC/electric PNON No controls, field-installed pneumatic DD00 Trane elec actuator only DD01 DDC Cooling only DD02 DDC N.C. on/off water valve control DD03 DDC Prop hot water valve control DD04 DDC On/off electric heat DD05 DDC Pulse-width modulation electric heat DD07 DDC N.O. on/off water valve control DD11 LonTalk DDC Controller Cooling only DD12 LonTalk DDC Controller w/ N.C. on/off hot water control DD13 LonTalk DDC Controller w/ proportional hot water control DD14 LonTalk DDC Controlleron/off electric heat control DD15 LonTalk DDC Controller w/ pulse-width modulation electric heat control DD17 LonTalk DDC Controller w/ N.O. on/off hot water control FM00 FM Customer-supplied actuator & controller FM01 FM Trane actuator w/ cusomersupplied control VMA1 FM Johnson controls VMA-1410 VMA2 FM Johnson controls VMA-1420 PWR1 FM Seimens 540-100 w/ GDE131.1P actuator PWR4 FM Seimens 540-100 w/Trane actuator PWR5 FM Seimens 540-100 w/ GDE131.1U actuator AT01 FM Automated Logic U341V+ AT02 FM Automated Logic U141V+ EI05 Analog With optional on/off reheat EI28 Analog With optional on/off reheat with dual-minimum cfm EI29 Analog With optional on/off reheat with constant-volume cfm PC00 PN N.C.Trane pneumatic actuator PC04 PN N.C. with optional on/off HW, DA Stat PC05 PN N.C. with optional on/off electric, RA Stat PN00 PN N.O.Trane pneumatic actuator, RA Stat PN04 PN N.O. PVR, DA Stat PN05 PN N.O. PVR, RA Stat PN11 PN N.O. dual-minimum cfm, DA Stat PN32 PN Water Valve, N.O. constant volume, DA Stat PN34 PN Electric heat, N.O. constant volume, DA Stat
Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell
VAV-SVN01E-EN
460
46.0 kW
Note: For VCEF units with transformers the VA depends on the staging, control, and contactor type (ranges are 40 VA to 75 VA)
Digit 24Disconnect Switch 0 None W With
Notes: 0.5 to 8.0 kW kW increments 8.0 to 18.0 kW 1 kW increments 18.0 to 46.0 kW 2 kW increments
Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal 3 3 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Not Used 0 N/A
Note:
Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1
VAV-SVN01E-EN
Dual-Duct Units
Digit 1, 2, 3Unit Type VDD VariTrane dual-duct Digit 4Development Sequence F Sixth Digit 5, 6Primary Air Valve 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 6" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) Digit 7 , 8Secondary Air Valve 05 5" inlet (350 cfm) 06 6" inlet (500 cfm) 08 8" inlet (900 cfm) 10 10" inlet (1400 cfm) 12 12" inlet (2000 cfm) 14 14" inlet (3000 cfm) 16 16" inlet (4000 cfm) Digit 9Not Used 0 N/A Digit 10, 11Design Sequence C0 Third (factory assigned) Digit 12, 13, 14, 15Controls ENON No Controls, Field-installed DDC/Electric PNON No Controls, Field-installed Pneumatic DD00 Trane elec actuator only DD01 DDC Cooling only DD08 DDC Constant-volume discharge DD11 LonTalk DDC Controller Cooling only DD18 LonTalk DDC Controller Constant Volume Discharge FM00 FM Customer-supplied actuator & controller FM01 FM Trane actuator w/ customer-supplied controller PC03 PN N.C. heating/ N.O. cooling w/ PVRs, DA stat PN08 PN N.O. heating/ N.O. cool act. only, RA stat PN09 PN N.O. htg/clg vlvs w/ PVRs, DA stat PN10 PN N.O. htg/clg w/ PVRs (cv disch), DA stat. Digit 19Outlet Plenum (Connection is slip & drive) 0 none A 1 outletRH B 1 outletEND C 1 outletLH D 2 outlets1 RH, 1 END E 2 outlets1 LH, 1 END F 2 outlets1 RH, 1 LH G 2 outlets - END H 3 outlets1 LH, 1 RH, 1 END J 4 outlets1 LH, 1 RH, 2 END
Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Not Used 0 N/A Digit 18Not Used 0 N/A
VAV-SVN01E-EN
Notes: N.C. = Normally-closed N.O = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM) Digit 18Motor Voltage 1 115/60/1 2 277/60/1 3 347/60/1 4 208/60/1 5 230/50/1 Digit 19Outlet Connection 1 Flanged 2 Slip & Drive
Note:
Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1 Digit 27 , 28, 29Electric Heat Voltage 000 None 050 0.5 kW 010 1.0 kW 015 1.5 kW 260 26.0 kW
Electric Heat Voltage Notes: 0.5 to 8.0 kW kW increments 8.0 to 18.0 kW 1 kW increments 18.0 to 46.0 kW2 kW increments
7
VAV-SVN01E-EN
VAV-SVN01E-EN
Water Coil and Electrical Connections Note: Airflow hitting you in the face.
Digit 23T ransformer 0 N/A (provided as standard) Digit 24Disconnect Switch 0 None W With
Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM)
Note:
Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3 K 120/60/1
240 24.0 kW Digit 30Electric Heat Stages 0 None 1 1 Stage 2 2 Stages Equal 3 3 Stages Equal Digit 31Contactors 0 None 1 24-volt magnetic 2 24-volt mercury 3 PE with magnetic 4 PE with mercury Digit 32Airflow Switch 0 None W With
10
VAV-SVN01E-EN
Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell Digit 17Motor Type D PSC Motor E High-efficiency motor (ECM)
Note:
Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3
VAV-SVN01E-EN
11
12
VAV-SVN01E-EN
Notes: N.C. = Normally-closed N.O. = Normally-opened DA Stat = Direct-acting pneumatic t-stat (by others) RA Stat = Reverse-acting pneumatic t-stat (by others) PN = Pneumatic FM = Factory installation of customersupplied controller PVR = Pneumatic Volume Regulator
Digit 16Insulation A 1/2" Matte-faced B 1" Matte-faced C 1/2" Foil-faced D 1" Foil-faced F 1" Double-wall G 3/8" Closed-cell
Note:
Digit 25Power Fuse 0 None W With Digit 26Electric Heat Voltage 0 None A 208/60/1 B 208/60/3 C 240/60/1 D 277/60/1 E 480/60/1 F 480/60/3 G 347/60/1 H 575/60/3 J 380/50/3
VAV-SVN01E-EN
13
14
VAV-SVN01E-EN
General Information