Relay Testing Procedure
Relay Testing Procedure
Relay Testing Procedure
VOLUME 3-8
The Appearance of the Internet Version of This manual May Differ From the Original, but the Contents Do Not
Page
Relay Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Applying Revised Relay Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 New Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Testing Equipment Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Testing Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Frequency of Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Test Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Annual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
10. Auxiliary Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 11. Time-Overcurrent and Time-Overvoltage Relays . . . . . . . . . . . . . . . . . . . . . . . . 4 12. Directional Overcurrent Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 13. Distance Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 14. Differential Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15. Static Relays 5
................................................... 5
16. Portable Relay Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 17. Circuit Burden Measurements for CT's . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 18. Exitation Curves for CT's . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 19. Grounding CT and PT Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 20. Open-Secondary Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 21. Temperature Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 22. Pressure Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Typical Exitation Curves for 69-kV Multi-ratio Bushing Type Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Forms
Page
PO&M 100 - Overcurrent relay test report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 PO&M 101 - Differential relay test report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 PO&M 102A - Distance relay test report (Westinghouse) . . . . . . . . . . . . . . . . . . . 13 PO&M 102B - Distance relay test report (General Electric) . . . . . . . . . . . . . . . . . 15 O&M 106 - Miscellaneous test sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Appendixes
Page
Appendix A - Electrical Device Numbers and Functions . . . . . . . . . . . . . . . . . . . 21 Appendix B - Definitions of Relay Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
ii
4. TESTING EQUIPMENT REQUIRED A good set of testing equipment and relay tools are important. Several manufacturers now produce portable relay test sets that will provided excellent results. If not available on the project, most of the equipment necessary can be borrowed from the Denver Office for making relay tests.
Age of Relays
Environment
Current Rating
Control Voltage
Station Service
appears excessive, since most relays are designed to operate in ambient temperatures not exceeding 40EC (104EF), a further check of the ambient temperature would be in order. Voltage and current supplied to the relay should be checked and compared with the name plate or instruction book ratings. Should evidence of overheating be found, the insulation should be checked for embrittlement and, where necessary, replaced. Removal of the connection plug in drawout relays may reveal evidence of severe fault currents or contaminated atmospheres, either of
which may indicate the advisability of a change in maintenance schedule. The condition of the relay contacts can be equally revealing. b. Mechanical adjustments and inspection should be made according to instructions shown following: (1) Check to see that all connections are tight. Several loose connections could indicate excessive vibration which should be corrected.
Static relays should be tested in accordance with manufacturer's recommendations given in relay instruction books. As there are no moving parts in static relays, there is no physical wear due to usage and no need for lubricants. Prime causes of failure in electronic components are heat, vibration, and moisture. Overheating can be caused by voltage transients, current surges, excessive power, or high ambient temperature. Vibration can loosen or break leads and connections and can crack component casings
Auxiliary CT's tend to saturate at much less secondary current and burden than large multiratio bushing type CT's. Excitation curves should be available on all CT's, especially on auxiliary CT's used in protective relaying circuits (fig. 1). Such curves can be derived by opencircuiting the primary, and driving the secondary with a 60-Hertz source while measuring voltage and current. Readings should be taken up to two times rated secondary current or to the point where voltage applied is 1500 volts. 19. GROUNDING CT AND PT CIRCUITS
The CT and PT circuits should be grounded at only one point. Relay misoperations can be caused by grounding the neutral at two points, such as one ground at the switchyard and another at the relay panel. At least once every 3 years with the primary deenergized, the known ground should be removed and the overall circuits should be checked for additional grounds and insulation breakdowns. 20. OPEN-SECONDARY CIRCUITS
Temperature relays used on bearings and for other important purposes should be checked for correct operation by placing the bulb in a pail of water with a thermometer, and gradually heating to the temperature at which the relay is set to operate. A mercury or alcohol thermometer should be used to read the temperature while the water is being stirred. Record temperature at which the relay operates on increasing temperature and at which it resets on falling temperature. Temperature relays operating from RTD's (resistance temperature detectors) should be checked by heating the detectors slowly in an enclosed air space since they should not be immersed in water or other liquid. 22. PRESSURE RELAYS
WARNING: Secondary circuits of CT's must not be open while primary current flows. Extreme care should be taken to avoid breaking the secondary circuit while primary current is flowing. If the secondary is open-circuited the primary current raises core flux density to saturation and induces a high voltage in the secondary which can endanger human life, and
Pressure relays should be checked for correct operation by comparing with an accurate pressure gage. Pressure should be increased and decreased to determine the pressure at which the relay operates and resets. The above does not apply to sudden pressure relays, which should be maintained in accordance with the manufacturer's recommendations.
11
12
13
14
15
16
17
19
Device No.
1.
2.
3.
4.
5.
6.
7.
8.
21
10.
11. 12.
13.
14.
15.
16. 17.
18.
Accelerating or Decelerating Device is a device that is used to close or to cause closing of circuits which are used to increase or decrease the speed of a machine. Starting-to-Running Transition Contactor is a device that operates to initiate or cause the automatic transfer of a machine from starting to running power connection. Electrically Operated Valve is an electrically operated, controlled, or monitored valve used in a fluid line. Distance Relay is a relay that functions when circuit admittance, impedance, or reactance increases or decreases beyond predetermined limits. Equalizer Circuit Breaker is a breaker that serves to control or to make and break equalizer or current-balancing connections for a machine field, or for regulating equipment, in a multiple-unit installation.
19.
20.
21.
22.
22
24. 25.
Reserved for future application Synchronizing or Synchronism-Check Device is a device that operates when two a-c circuits are within the desired limits of frequency, phase angle, or voltage to permit or to cause the paralleling of these two circuits. Apparatus Thermal Device is a device that functions when temperature of the shunt field or amortisseur winding of a machine, or that of a load limiting or load shifting resistor or of a liquid or other medium, exceeds a predetermined value: or if temperature of the protected apparatus, such as a power rectifier, or of any medium, decreases below a predetermined value. Undervoltage Relay is a relay that functions on a given value of undervoltage. Flame Detector is a device that monitors the presence of pilot or main flame in such apparatus as a gas turbine or a steam boiler. Isolating Contactor is a device that is used expressly for disconnecting one circuit from another for purposes of emergency operation, maintenance, or test. Annunciator Relay is a nonautomatically reset device that gives a number of separate visual indications upon functioning of protective devices, and which may also be arranged to perform a lockout function. Separate Excitation Device is a device that connects a circuit, such as shunt field of a synchronous converter, to a source of separate excitation during starting sequence, or one that energizes the excitation and ignition circuits of a power rectifier. Directional Power Relay is a device that functions on a desired value of power flow in a given direction or upon reverse power resulting from arc-back in the anode or cathode circuits of a power rectifier. Position Switch is a switch that makes or breaks contact when the main device or piece of apparatus which has no device function number reaches a given position. Master Sequence Device is a device such as a motor-operated multi-contact switch, or equivalent, or a programming device, such as a computer, that establishes or determines the operating sequence of major devices in an equipment during starting and stopping or during other sequential switching operations.
26.
27. 28.
29.
30.
31.
32.
33.
34.
23
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
24
48.
49.
50.
51.
52.
53.
54. 55.
56.
57.
58.
59. 60.
61.
25
63.
64.
65.
Governor is the assembly of fluid, electrical, or mechanical control equipment used for regulating flow of water, steam, or other medium to the prime mover for such purposes as starting, holding speed or load, or stopping. Notching or Jogging Device is a device that functions to allow only a specified number of operations of a given device, or equipment, or a specified number of successive operations within a given time of each other. It is also a device that functions to energize a circuit periodically or for fractions of specified time intervals, or that is used to permit intermittent acceleration or jogging of a machine at Iow speeds for mechanical positioning. A-C Directional Overcurrent Relay is a relay that functions on a desired value of a-c overcurrent flowing in a predetermined direction. Blocking Relay is a relay that initiates a pilot signal for blocking of tripping on external faults in a transmission line or in other apparatus under predetermined conditions, or cooperates with other devices to block tripping or to block reclosing on an out-of-step condition or on power swings. Permissive Control Device is generally a two-position, manually operated switch that, in one position, permits closing of a circuit breaker, or placing of an equipment into operation, and in the other position prevents the circuit breaker or equipment from being operated. Rheostat is variable resistance device used in an electric circuit, which is electrically operated or has other electrical accessories, such as auxiliary, position, or limit switches. Level Switch is a switch which operates on given values or on a given rate of change, of level.
66.
67.
68.
69.
70.
71.
26
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
27
86.
87.
88.
89.
90.
91.
92.
93.
94.
28
29
Examples: SPST NO DB designates single-pole, single-throw, normally open, double-break contacts. All contacts are single break except when noted as double-break (DB). Relays having several sets of differently functioning contacts will have the contact forms listed in alphabetical order of their letter symbols. Example: 1A2B refers to SPST NO contacts and DPST NC contacts. For a relay on which the moving contact engages more than two stationary contacts during its cycle of operation, the contact arrangement is described as MPNT, where M is the number of poles and N is tile number of throws, e.g., 8P 20T. Contact Overtravel. -Sometimes used for Contact Follow.
30
31
(FIST3-8 11/91)
(F!ST3-8 11/91)
32
33
34
35
36
37
38
Reclamation personnel have experienced considerable difficulty with Westinghouse Type KD relays due to inadequate contact restraint upon loss of restraint potential. When the relay is adjusted in accordance with the manufacturer's instructions, the restraint in the contact opening direction is so slight that vibration or jarring of the switchboard panel will close the contacts, and they sometimes remain closed. This causes a problem on schemes where the restraint potential is obtained from the line (in a ring bas scheme, for example) or when loss of main bas potential occurs (when restraint potential is obtained from the bus) since it is impossible to close the breaker under this condition. Present design practice is to provide overcurrent supervision of distance relays where potential is line connected. In older installations where overcurrent supervision is not provided the existing relay adjustment instructions should be modified to insure that the relays will rest when they are deenergized. Westinghouse relay engineers have provided the following supplementary instructions. If minimum voltage at the relay, for a fault at the balance point setting, is less than 30 volts secondary line-to-line, then the spring restraint should be adjusted as per pages 25 and 27 of I.L.41-491H for Type KD and KD-1 relays, or as per pages 24 and 25 of I.L. 41-491.4N for Type KD-4 and KD-41 relays. However, if with this adjustment the relay contacts fail to reset when relay is deenergized, the spring restraint should be increased only enough to hold the moving contact against the backstop while the relay is deenergized. Where minimum voltage at the relay, for a fault at the balance point setting, is 30 volts line-toline or more, the spring restraint for both three-phase and phase-to-phase element may be set as follows: Connect relay to Test No. 1 except reverse the voltage phase sequence by interchanging the connections to Brush 1 and Brush 2. Adjust voltages VlF2F and V2F3F for 3.5 volts each. Position the moving contact spring adjuster so that the moving contact just restrains against the backstop. This adjustment will make the three-phase unit characteristic somewhat nonlinear with respect to balance point voltage, but the effect is almost negligible at 30-volt lineto-line and above. There is one other possible problem due to loss of potential on these relays. If the relays are deenergized because of the tripping of remote source circuit breakers, the contacts may momentarily blip closed due to the transient decay of energy in the potential circuit of the relay. If is desired to prevent tripping under such conditions where the relay can be deenergized without attendant opening of the "52 a" contact, the recommended solution is to use fault detectors as stated on Page 3 of I.L. 41-491H and page 1 of I.L. 41-491.4N.
39