Calculation of Short Circuit
Calculation of Short Circuit
is normally given on each and every transformer. Percentage impedence = short circuit impedence Asume we want to do the calculations on 20MVA,66/11kV Power transformer having % impedence of 14% , the following shall be taken in to account:If we apply 14% of high side voltage i.e. 14% of 66kV then the full rated current shall flow in the shorted secondary/ low voltage winding. Rated MVA Rated HV Rated LV % impedence Assume LT supply voltage 20 66 11 14 MVA KV KV % = = = = 20000000 66000 11000 0.14 VA V V V
Rated primary current of the transfomer :Rated secondary current of the transfomer :-
On application of 14% of 66kV in HV side then full rated current flows in shorted secondary Wdg = 1049.758556 On application of 1Volt in HV side then full rated current flows in shorted secondary Wdg = 1049.759 66000X 0.14 = 0.113610233 On application of 415 V Lt supply in HV side then full rated current flows in shorted secondary Wdg = 1049.759 X 415 66000X 0.14 = 47.14824681 = 47.15 So total current shall flow in the shorted secondary LV winding = 47.15 Amp And in the primary side, HV winding the current shall flow:= = = So total current shall flow in the shorted secondary HV winding = 7.86 Amp 174.958 X 415 66000X 0.14 7.858041135 7.86
In the same we can calculate the primary side current on short circuit. Current in relay with CT ratio of 200/1 (HV side) = = = = 7.86 200/1 0.0393 47.15 1200/0.578 0.023