Synchronous Generators
Synchronous Generators
Synchronous Generators
According to the shape of the field, synchronous machines may be classified as cylindrical-rotor (non-salient pole) machines and salient-pole machines
Synchronous Generators
Construction The winding consists of copper bars insulated with mica and epoxy resin. The conductors are secured by steel wedges. The iron core is supported by a steel housing.
Synchronous Generators
Round rotor
Synchronous Generators
Low speed, large hydro-generators may have more than one hundred poles. These generators are frequently mounted vertically Salient Rotor
Synchronous Generators
3. brushless exciter an ac generator with fixed field winding and a rotor with a three phase circuit diode/SCR rectification supplies dc current to the field windings
Synchronous Generators
Synchronous Generators
Erms =
kw N a f
Synchronous Generators
Synchronous Generators
H.W A four pole, three-phase synchronous generator is rated 250 MVA, its terminal voltage is 24 kV, the synchronous reactance is: 125%. Calculate the synchronous reactance in ohm. Calculate the rated current and the line to ground terminal voltage. Draw the equivalent circuit. Calculate the induced voltage, E f , at rated load and pf = 0.8 lag. (Ans: X syn =2.88, Ig =6.01-36.87oKA, E gn =27.9329.74KV)
10
Synchronous Generators
Figure.1 (a) The per-phase equivalent circuit of a synchronous generator without armature reaction while depicting the revolving field produced by the rotor. The phasor diagrams for a (b) lagging pf, (c) unity pf, and (d) leading pf. 11
Synchronous Generators
(a) If p is the flux per pole in the generator under no load, then the generated voltage E a must lag p by 90o, as shown in Figure 2. ~ (b) Since the power factor is unity, the phase current I a is in phase with the terminal phase voltage Va . (c) As the phase current I a passes through the armature winding, its magnetomotive force (mmf) produces a flux ar which is in phase with ~ I a . The effective flux e per pole in the generator is the algebraic sum of the two fluxes; that is, e = p + ar , as shown in the figure.
Figure 2: Phasor diagram depicting the effect of armature reaction when the power factor is unity.
(d) The flux ar , in turn, induces an emf E ar in the armature winding. E ar is called the armature reaction emf. The armature reaction emf E ar lags the flux ar by 90o. Hence the effective generated voltage per-phase E e is the algebraic sum of the no-load voltage E a and the armature reaction emf E ar . That is, E e = E a + E ar . An equivalent circuit showing the armature reaction emf is given in Figure 3.
12
Synchronous Generators
Figure 3: A per-phase equivalent circuit showing the induced emf in the armature winding due to the armature reaction.
(e) The per-phase terminal voltage Va is obtained by subtracting the voltage drops
~ ~ ~ Ee = Va + I a ( Ra + j X a )
From the phasor diagram, it should be obvious that the armature reaction has reduced the effective flux per pole when the power factor of the load is unity. Also, the terminal voltage is smaller than the generated voltage.
Figure 4: The phasor diagram showing the effect of armature reaction when the power factor is lagging.
13
Synchronous Generators
By following the above sequence of events, we can obtain the phasor diagrams for the lagging (Figure 4) and the leading (Figure 5) power factors. From these figures it is evident that the resultant flux is (smaller/larger) with armature reaction for the ~ (lagging/leading) power factor than without it. In addition, the terminal voltage Va is (higher/lower) than the generated voltage E a when the power factor is (leading/ lagging). Since the flux per pole p is different for each of the three load conditions, the field current I f must be adjusted each time the load is changed. ~ ~ Since the armature reaction emf E ar lags the current I a by 90o, we can also express it as
~ ~ Ear = jI a X m
where X m , a constant of proportionality, is known as the magnetization reactance.
Figure 5: The phasor diagram showing the effect of armature reaction when the power factor of the load is leading.
Both the magnetization reactance and the leakage reactance are present at the same time. It is rather difficult to separate one reactance from the other. For this reason, the two reactances are combined together and the sum
Xs = Xm + Xa
is called the synchronous reactance. The synchronous reactance is usually very large compared with the resistance of the armature winding. We can now define the synchronous impedance on a per-phase basis as Z s = Ra + j X s
14
Synchronous Generators
Ra = 0.5 RL
The Open-Circuit Test The open-circuit test, or the no-load test, is performed by 1) 2) 3) 4) Generator is rotated at the rated speed. No load is connected at the terminals. Field current is increased from 0 to maximum. Record values of the terminal voltage and field current value.
With the terminals open, I A =0, so E A = V . It is thus possible to construct a plot of E A or V T vs I F graph. This plot is called open-circuit characteristic (OCC) of a generator. With this characteristic, it is possible to find the internal generated voltage of the generator for any given field current.
15
Synchronous Generators
The OCC follows a straight-line relation as long as the magnetic circuit of the synchronous generator does not saturate. Since, in the linear region, most of the applied mmf is consumed by the air-gap, the straight line is appropriately called the air-gap line. The Short-Circuit Test The short-circuit test provides information about the current capabilities of a synchronous generator. It is performed by 1) 2) 3) 4) Generator is rotated at rated speed. Adjust field current to 0. Short circuit the terminals. Measure armature current or line current as the field current is increased.
16
Synchronous Generators
SCC is essentially a straight line. To understand why this characteristic is a straight line, look at the equivalent circuit below when the terminals are short circuited.
When the terminals are short circuited, the armature current I A is:
IA =
And its magnitude is:
EA RA + jX S
I A=
EA
2 2 RA + XS
From both tests, here we can find the internal machine impedance (E A from OCC, I A from SCC):
ZS =
2 2 RA + XS =
EA IA
E A V oc = IA IA
Xs
17
Synchronous Generators
Short Circuit Ratio Ratio of the field current required for the rated voltage at open circuit to the field current required for rated armature current at short circuit. , = , , = 1
18
Synchronous Generators
Example: The following data are taken from the open- and short-circuit characteristics of a 45-kVA, three-phase, Y-connected, 220-V (line-to-line), six-pole, 60-Hz synchronous machine. From the open-circuit characteristic: Line-to-line voltage = 220 V Field current = 2.84 A From the short-circuit characteristic:
From the air-gap line: Field current = 2.20 A Line-to-line voltage = 202 V 19
Synchronous Generators
Compute the unsaturated value of the synchronous reactance, its saturated value at rated voltage, and the short-circuit ratio. Express the synchronous reactance in ohms per phase and in per unit on the machine rating as a base.
Solution
At a field current of 2.20 A the line-to-neutral voltage on the air-gap line is
and for the same field current the armature current on short circuit is
in per unit
The saturated synchronous reactance can be found from the open- and short-circuit characteristics
In per unit
20
Synchronous Generators
Finally, from the open- and short-circuit characteristics, the short-circuit ratio is given by
The inverse of the short-circuit ratio is equal to the per-unit saturated synchronous reactance
H.W
Calculate the saturated synchronous reactance (in /phase and per unit) of a 85 kVA synchronous machine which achieves its rated open-circuit voltage of 460 V at a field current 8.7 A and which achieves rated short-circuit current at a field current of 11.2 A. [Answer: Xs = 3.21 /phase = 1.29 per unit]
21
Synchronous Generators
Per unit
Synchronous Generators
23
Synchronous Generators
24
Synchronous Generators
2. Ampere-turn / MMF method The ampere-turn /MMF method is the converse of the EMF method in the sense that instead of having the phasor addition of various voltage drops/EMFs, here the phasor addition of MMF required for the voltage drops are carried out. Further the effect of saturation is also taken care of. Data required for MMF method are: Effective resistance per phase of the 3-phase winding R Open circuit characteristic (OCC) at rated speed/frequency Short circuit characteristic (SCC) at rated speed/frequency Compared to the EMF method, MMF method, involves more number of complex calculation steps. Further the OCC is referred twice and SCC is referred once while predetermining the voltage regulation for each load condition. Reference of OCC takes care of saturation effect. As this method requires more effort, the final result is very close to the actual value. Hence this method is called optimistic method.
25
Synchronous Generators
26
Synchronous Generators
27
Synchronous Generators
diagram
28
Synchronous Generators
29
Synchronous Generators
30
Synchronous Generators
Fig.2
31
Synchronous Generators
32
Synchronous Generators
33
Synchronous Generators
34
Synchronous Generators
H.W
35
Synchronous Generators
Fig.1
36
Synchronous Generators
Let the subscripts i, o, g denote input, output, generator. By KVL in the network of Fig.1.
37
Synchronous Generators
38
Synchronous Generators
39
Synchronous Generators
40
Synchronous Generators
41
Synchronous Generators
Salient-pole generators, such as hydroelectric generators, have armature inductances that are a function of rotor position, making analysis one step more complicated. The key to analysis of such machines is to separate mmf and flux into two orthogonal components. The two components are aligned with the direct axis and the quadrature axis of the machine. The direct axis is aligned with the field winding, while the quadrature axis leads the direct by 90.
42
Synchronous Generators
43
Synchronous Generators
44
Synchronous Generators
45
Synchronous Generators
46
Synchronous Generators
47
Synchronous Generators
48
Synchronous Generators
49
Synchronous Generators
50
Synchronous Generators
51
Synchronous Generators
52
Synchronous Generators
53
Synchronous Generators
54
Synchronous Generators
55
Synchronous Generators
56
Synchronous Generators
Synchronizing may be achieved with the help of synchronizing lamps, the rotary lamp method being the most popular. Alternatively, a device known as the synchroscope may conveniently be used to facilitate synchronizing.
57
Synchronous Generators
58
Synchronous Generators
59
Synchronous Generators
60
Synchronous Generators
Example:
61
Synchronous Generators
Example: Two alternators running in parallel supply lighting load of 2500 KW and a motor load of 5000 KW at 0.707 P.F. one machine is loaded to 4000 KW at a P.F. of 0.8 lagging. What is the KW output and P.F. of the other machine? Solution: For first machine. Load power (or KW) of lighting load, p = 2500 KW Load reactive power (or KVAR) of lighting load, = cos sin
cos = 1
Load sharing
= 0 + 5000 = 5000
0.6 = 3000
= tan