Synchronous Generators
Dr. Suad Ibrahim Shahl
II. Synchronous Generators
Synchronous machines are principally used as alternating current (AC) generators. They supply the electric power used by all sectors of modern societies: industrial, commercial, agricultural, and domestic. Synchronous generators usually operate together (or in parallel), forming a large power system supplying electrical energy to the loads or consumers. Synchronous generators are built in large units, their rating ranging from tens to hundreds of megawatts. Synchronous generator converts mechanical power to ac electric power. The source of mechanical power, the prime mover, may be a diesel engine, a steam turbine, a water turbine, or any similar device. For high-speed machines, the prime movers are usually steam turbines employing fossil or nuclear energy resources. Low-speed machines are often driven by hydro-turbines that employ water power for generation. Smaller synchronous machines are sometimes used for private generation and as standby units, with diesel engines or gas turbines as prime movers.
Types of Synchronous Machine
According to the arrangement of the field and armature windings, synchronous machines may be classified as rotating-armature type or rotating-field type. Rotating-Armature Type: The armature winding is on the rotor and the field system is on the stator. Rotating-Field Type: The armature winding is on the stator and the field system is on the rotor.
Synchronous Generators
Dr. Suad Ibrahim Shahl
According to the shape of the field, synchronous machines may be classified as cylindrical-rotor (non-salient pole) machines and salient-pole machines
Synchronous Generators
Dr. Suad Ibrahim Shahl
Construction The winding consists of copper bars insulated with mica and epoxy resin. The conductors are secured by steel wedges. The iron core is supported by a steel housing.
Synchronous Generators
Dr. Suad Ibrahim Shahl
Round rotor
Synchronous Generators
Dr. Suad Ibrahim Shahl
Low speed, large hydro-generators may have more than one hundred poles. These generators are frequently mounted vertically Salient Rotor
Field Excitation and Exciters
DC field excitation is an important part of the overall design of a synchronous generator The field excitation must ensure not only a stable AC terminal voltage, but must also respond to sudden load changes Rapid field excitation response is important
Three methods of excitation
1. 2. slip rings link the rotors field winding to an external dc source dc generator exciter a dc generator is built on the same shaft as the ac generators rotor a commutator rectifies the current that is sent to the field winding 5
Synchronous Generators
Dr. Suad Ibrahim Shahl
3. brushless exciter an ac generator with fixed field winding and a rotor with a three phase circuit diode/SCR rectification supplies dc current to the field windings
Typical brushless exciter system
Ventilation or Cooling of an Alternator
The slow speed salient pole alternators are ventilated by the fan action of the salient poles which provide circulating air. Cylindrical rotor alternators are usually long, and the problem of air flow requires very special attention. The cooling medium, air or hydrogen is cooled by passing over pipes through which cooling water is circulated and ventilation of the alternator. Hydrogen is normally used as cooling medium in all the turbine-driven alternators because hydrogen provides better cooling than air and increases the efficiency and decreases the windage losses. Liquid cooling is used for the stators of cylindrical rotor generators.
Synchronous Generators
Dr. Suad Ibrahim Shahl
Synchronous Generators
Dr. Suad Ibrahim Shahl
The rms. value of the induced voltages are:
Ean = Erms e i O deg
where:
Ebn = Erms e i120 deg
2 = 4.44 f N a f k w
Ecn = Erms e i 240 deg
Erms =
kw N a f
k w = 0.85-0.95 is the winding factor.
Synchronous Generators
Dr. Suad Ibrahim Shahl
Synchronous Generators
Dr. Suad Ibrahim Shahl
H.W A four pole, three-phase synchronous generator is rated 250 MVA, its terminal voltage is 24 kV, the synchronous reactance is: 125%. Calculate the synchronous reactance in ohm. Calculate the rated current and the line to ground terminal voltage. Draw the equivalent circuit. Calculate the induced voltage, E f , at rated load and pf = 0.8 lag. (Ans: X syn =2.88, Ig =6.01-36.87oKA, E gn =27.9329.74KV)
10
Synchronous Generators
Dr. Suad Ibrahim Shahl
Armature Reaction in Synchronous Machines
Armature reaction refers to the influence on the magnetic field in the air gap when the phase windings a, b, and c on the stator are connected across a load. The flux produced by the armature winding reacts with the flux set up by the poles on the rotor, causing the total flux to change.
The generator delivers a load at a unity power factor.
Figure.1 (a) The per-phase equivalent circuit of a synchronous generator without armature reaction while depicting the revolving field produced by the rotor. The phasor diagrams for a (b) lagging pf, (c) unity pf, and (d) leading pf. 11
Synchronous Generators
Dr. Suad Ibrahim Shahl
(a) If p is the flux per pole in the generator under no load, then the generated voltage E a must lag p by 90o, as shown in Figure 2. ~ (b) Since the power factor is unity, the phase current I a is in phase with the terminal phase voltage Va . (c) As the phase current I a passes through the armature winding, its magnetomotive force (mmf) produces a flux ar which is in phase with ~ I a . The effective flux e per pole in the generator is the algebraic sum of the two fluxes; that is, e = p + ar , as shown in the figure.
Figure 2: Phasor diagram depicting the effect of armature reaction when the power factor is unity.
(d) The flux ar , in turn, induces an emf E ar in the armature winding. E ar is called the armature reaction emf. The armature reaction emf E ar lags the flux ar by 90o. Hence the effective generated voltage per-phase E e is the algebraic sum of the no-load voltage E a and the armature reaction emf E ar . That is, E e = E a + E ar . An equivalent circuit showing the armature reaction emf is given in Figure 3.
12
Synchronous Generators
Dr. Suad Ibrahim Shahl
Figure 3: A per-phase equivalent circuit showing the induced emf in the armature winding due to the armature reaction.
(e) The per-phase terminal voltage Va is obtained by subtracting the voltage drops
~ ~ ~ I a Ra and jI a X a from Ee . In other words,
~ ~ ~ Ee = Va + I a ( Ra + j X a )
From the phasor diagram, it should be obvious that the armature reaction has reduced the effective flux per pole when the power factor of the load is unity. Also, the terminal voltage is smaller than the generated voltage.
Figure 4: The phasor diagram showing the effect of armature reaction when the power factor is lagging.
13
Synchronous Generators
Dr. Suad Ibrahim Shahl
By following the above sequence of events, we can obtain the phasor diagrams for the lagging (Figure 4) and the leading (Figure 5) power factors. From these figures it is evident that the resultant flux is (smaller/larger) with armature reaction for the ~ (lagging/leading) power factor than without it. In addition, the terminal voltage Va is (higher/lower) than the generated voltage E a when the power factor is (leading/ lagging). Since the flux per pole p is different for each of the three load conditions, the field current I f must be adjusted each time the load is changed. ~ ~ Since the armature reaction emf E ar lags the current I a by 90o, we can also express it as
~ ~ Ear = jI a X m
where X m , a constant of proportionality, is known as the magnetization reactance.
Figure 5: The phasor diagram showing the effect of armature reaction when the power factor of the load is leading.
Both the magnetization reactance and the leakage reactance are present at the same time. It is rather difficult to separate one reactance from the other. For this reason, the two reactances are combined together and the sum
Xs = Xm + Xa
is called the synchronous reactance. The synchronous reactance is usually very large compared with the resistance of the armature winding. We can now define the synchronous impedance on a per-phase basis as Z s = Ra + j X s
14
Synchronous Generators
Dr. Suad Ibrahim Shahl
Synchronous Generator Tests
To obtain the parameters of a synchronous generator, we perform three simple tests as described below. The Resistance Test This test is conducted to measure-winding resistance of a synchronous generator when it is at rest and the field winding is open. The resistance is measured between two lines at a time and the average of the three resistance readings is taken to be the measured value of the resistance, R L , from line to line. If the generator is Yconnected, the per-phase resistance is
Ra = 0.5 RL
The Open-Circuit Test The open-circuit test, or the no-load test, is performed by 1) 2) 3) 4) Generator is rotated at the rated speed. No load is connected at the terminals. Field current is increased from 0 to maximum. Record values of the terminal voltage and field current value.
Circuit diagram to perform open-circuit test.
With the terminals open, I A =0, so E A = V . It is thus possible to construct a plot of E A or V T vs I F graph. This plot is called open-circuit characteristic (OCC) of a generator. With this characteristic, it is possible to find the internal generated voltage of the generator for any given field current.
15
Synchronous Generators
Dr. Suad Ibrahim Shahl
Open-circuit characteristic (OCC) of a generator
The OCC follows a straight-line relation as long as the magnetic circuit of the synchronous generator does not saturate. Since, in the linear region, most of the applied mmf is consumed by the air-gap, the straight line is appropriately called the air-gap line. The Short-Circuit Test The short-circuit test provides information about the current capabilities of a synchronous generator. It is performed by 1) 2) 3) 4) Generator is rotated at rated speed. Adjust field current to 0. Short circuit the terminals. Measure armature current or line current as the field current is increased.
16
Synchronous Generators
Dr. Suad Ibrahim Shahl
SCC is essentially a straight line. To understand why this characteristic is a straight line, look at the equivalent circuit below when the terminals are short circuited.
Circuit diagram to perform short-circuit test.
When the terminals are short circuited, the armature current I A is:
IA =
And its magnitude is:
EA RA + jX S
I A=
EA
2 2 RA + XS
From both tests, here we can find the internal machine impedance (E A from OCC, I A from SCC):
ZS =
2 2 RA + XS =
EA IA
E A V oc = IA IA
Since X s >> R A , the equation reduces to:
Xs
17
Synchronous Generators
Dr. Suad Ibrahim Shahl
Short Circuit Ratio Ratio of the field current required for the rated voltage at open circuit to the field current required for rated armature current at short circuit. , = , , = 1
18
Synchronous Generators
Dr. Suad Ibrahim Shahl
Example: The following data are taken from the open- and short-circuit characteristics of a 45-kVA, three-phase, Y-connected, 220-V (line-to-line), six-pole, 60-Hz synchronous machine. From the open-circuit characteristic: Line-to-line voltage = 220 V Field current = 2.84 A From the short-circuit characteristic:
From the air-gap line: Field current = 2.20 A Line-to-line voltage = 202 V 19
Synchronous Generators
Dr. Suad Ibrahim Shahl
Compute the unsaturated value of the synchronous reactance, its saturated value at rated voltage, and the short-circuit ratio. Express the synchronous reactance in ohms per phase and in per unit on the machine rating as a base.
Solution
At a field current of 2.20 A the line-to-neutral voltage on the air-gap line is
and for the same field current the armature current on short circuit is
Note that rated armature current is
Therefore, la, sc = 1.00 per unit. The corresponding air-gap-line voltage is
in per unit
The saturated synchronous reactance can be found from the open- and short-circuit characteristics
In per unit
20
Synchronous Generators
Dr. Suad Ibrahim Shahl
Finally, from the open- and short-circuit characteristics, the short-circuit ratio is given by
The inverse of the short-circuit ratio is equal to the per-unit saturated synchronous reactance
H.W
Calculate the saturated synchronous reactance (in /phase and per unit) of a 85 kVA synchronous machine which achieves its rated open-circuit voltage of 460 V at a field current 8.7 A and which achieves rated short-circuit current at a field current of 11.2 A. [Answer: Xs = 3.21 /phase = 1.29 per unit]
21
Synchronous Generators
Dr. Suad Ibrahim Shahl
Voltage regulation of Alternator
The voltage regulation of an Alternator is defined as the change in terminal voltage from no-load to load condition expressed as per-unit or percentage of terminal voltage at load condition; the speed and excitation conditions remaining same.
Per unit
Determination of Voltage Regulation
The following are the three methods which are used to determine the voltage regulation of smooth cylindrical type Alternators 1. Synchronous impedance / EMF method 2. Ampere-turn / MMF method 3. Potier / ZPF method 1. Synchronous impedance / EMF method Synchronous impedance is calculated from OCC and SCC as Z s = E 0 /I sc (for same I f ) A compromised value of Z s is normally estimated by taking the ratio of (E 0 /I sc ) at normal field current I f . A normal field current I f is one which gives rated voltage V r on open circuit. Z s = V r /I sc Advantages: Simple no load tests (for obtaining OCC and SCC) are to be conducted Calculation procedure is much simpler Disadvantages: The value of voltage regulation obtained by this method is always higher than the actual value.
22
Synchronous Generators
Dr. Suad Ibrahim Shahl
23
Synchronous Generators
Dr. Suad Ibrahim Shahl
24
Synchronous Generators
Dr. Suad Ibrahim Shahl
2. Ampere-turn / MMF method The ampere-turn /MMF method is the converse of the EMF method in the sense that instead of having the phasor addition of various voltage drops/EMFs, here the phasor addition of MMF required for the voltage drops are carried out. Further the effect of saturation is also taken care of. Data required for MMF method are: Effective resistance per phase of the 3-phase winding R Open circuit characteristic (OCC) at rated speed/frequency Short circuit characteristic (SCC) at rated speed/frequency Compared to the EMF method, MMF method, involves more number of complex calculation steps. Further the OCC is referred twice and SCC is referred once while predetermining the voltage regulation for each load condition. Reference of OCC takes care of saturation effect. As this method requires more effort, the final result is very close to the actual value. Hence this method is called optimistic method.
25
Synchronous Generators
Dr. Suad Ibrahim Shahl
26
Synchronous Generators
Dr. Suad Ibrahim Shahl
27
Synchronous Generators
Dr. Suad Ibrahim Shahl
diagram
28
Synchronous Generators
Dr. Suad Ibrahim Shahl
29
Synchronous Generators
Dr. Suad Ibrahim Shahl
Fig. 1Potier triangle
30
Synchronous Generators
Dr. Suad Ibrahim Shahl
Fig.2
31
Synchronous Generators
Dr. Suad Ibrahim Shahl
32
Synchronous Generators
Dr. Suad Ibrahim Shahl
33
Synchronous Generators
Dr. Suad Ibrahim Shahl
34
Synchronous Generators
Dr. Suad Ibrahim Shahl
H.W
35
Synchronous Generators
Dr. Suad Ibrahim Shahl
Power flow transfer equations for a synchronous generator
Fig.1
36
Synchronous Generators
Dr. Suad Ibrahim Shahl
Let the subscripts i, o, g denote input, output, generator. By KVL in the network of Fig.1.
37
Synchronous Generators
Dr. Suad Ibrahim Shahl
38
Synchronous Generators
Dr. Suad Ibrahim Shahl
39
Synchronous Generators
Dr. Suad Ibrahim Shahl
40
Synchronous Generators
Dr. Suad Ibrahim Shahl
Salient-Pole Synchronous Generator Two-Reaction Theory
41
Synchronous Generators
Dr. Suad Ibrahim Shahl
Salient-pole generators, such as hydroelectric generators, have armature inductances that are a function of rotor position, making analysis one step more complicated. The key to analysis of such machines is to separate mmf and flux into two orthogonal components. The two components are aligned with the direct axis and the quadrature axis of the machine. The direct axis is aligned with the field winding, while the quadrature axis leads the direct by 90.
42
Synchronous Generators
Dr. Suad Ibrahim Shahl
43
Synchronous Generators
Dr. Suad Ibrahim Shahl
44
Synchronous Generators
Dr. Suad Ibrahim Shahl
45
Synchronous Generators
Dr. Suad Ibrahim Shahl
46
Synchronous Generators
Dr. Suad Ibrahim Shahl
47
Synchronous Generators
Dr. Suad Ibrahim Shahl
Power-angle Characteristics of Synchronous Generators
48
Synchronous Generators
Dr. Suad Ibrahim Shahl
49
Synchronous Generators
Dr. Suad Ibrahim Shahl
50
Synchronous Generators
Dr. Suad Ibrahim Shahl
Salient-Pole Synchronous Generator
51
Synchronous Generators
Dr. Suad Ibrahim Shahl
52
Synchronous Generators
Dr. Suad Ibrahim Shahl
53
Synchronous Generators
Dr. Suad Ibrahim Shahl
54
Synchronous Generators
Dr. Suad Ibrahim Shahl
55
Synchronous Generators
Dr. Suad Ibrahim Shahl
56
Synchronous Generators
Dr. Suad Ibrahim Shahl
Synchronizing may be achieved with the help of synchronizing lamps, the rotary lamp method being the most popular. Alternatively, a device known as the synchroscope may conveniently be used to facilitate synchronizing.
57
Synchronous Generators
Dr. Suad Ibrahim Shahl
58
Synchronous Generators
Dr. Suad Ibrahim Shahl
59
Synchronous Generators
Dr. Suad Ibrahim Shahl
60
Synchronous Generators
Dr. Suad Ibrahim Shahl
Example:
61
Synchronous Generators
Dr. Suad Ibrahim Shahl
Example: Two alternators running in parallel supply lighting load of 2500 KW and a motor load of 5000 KW at 0.707 P.F. one machine is loaded to 4000 KW at a P.F. of 0.8 lagging. What is the KW output and P.F. of the other machine? Solution: For first machine. Load power (or KW) of lighting load, p = 2500 KW Load reactive power (or KVAR) of lighting load, = cos sin
For second machine P of motor load=5000 KW . . cos = 0.707
= 0 sin = sin 0 = 0 2500 0= 0 = 1 sin = 0.707
cos = 1
Load sharing
= 0 + 5000 = 5000
= 2500 + 5000 = 7500
5000 sin = 0.707 = 5000 cos 0.707
Load taking by 1st machine= 4000 KW 1 =
4000 0.8
2nd machine will supply = 7500 4000 = 3500 =
sin cos
0.6 = 3000
= 5000 3000 = 2000
2000
. . , cos = cos 29.7448 = 0.8682
62
= tan1 0.57142 = 29.7448
tan = = 3500 = 0.57142
= tan