Lecture 21: Introduction To Primary Systems (Central Plants)
Lecture 21: Introduction To Primary Systems (Central Plants)
Material prepared by GARD Analytics, Inc. and University of Illinois at Urbana-Champaign under contract to the National Renewable Energy Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
water for the secondary systems as well as other energy sources that are needed by the building Some knowledge of the primary systems (central plants) is required to accurately simulate buildings and to understand what the model input parameters are
2
Cooling Equipment
Thermodynamic cycle through which refrigerant goes Refrigerant is enclosed within cycle components
Components Condenser Compressor Evaporator (aka Liquid Cooler) Expansion Valve Primary and secondary fluids (refrigerant, water, etc.)
Compression Cycle
Typical compression cycle diagram:
Condenser
QC
Compressor
Expansion Valve
Work
Evaporator
QE
6
capacity
temperatures become more extreme Presence of a more moderate/constant temperature source can keep system running efficiently (e.g., ground)
difference?
Difference in system components: none Chillers are generally cooling only device and are used to produce chilled water for cooling coils (size range can be quite large) Heat pumps can provide both heating and cooling and are typically smaller in size (often residential units) Heat pumps are typically compression cycle only and almost all use electric energy as input Chillers can use various cycles and may actually use other energy sources as the system energy input
10
Condensers
Purpose: to reject heat from refrigerant to
surrounding environment, condensing the refrigerant from a (superheated) vapor to a (subcooled) liquid Condenser is really a heat exchanger which transfers energy from one fluid stream to another without mixing the two streams Water-Cooled Condensers
Heat exchanged with water which is circulated to another component (ground, lake, pondnatural or constructed, river, cooling tower, etc.) as closed or open loop Condenser temperature depends on water source temperature
11
Condensers (contd)
Air-Cooled Condensers Heat exchanged with outdoor air Fans required to improve heat transfer Condenser temperature linked to outside air dry bulb temperature Evaporative Condensers Heat exchanged sensibly and latently with outdoor air Fan and pump required: fan to circulate air through unit, pump to circulate water Added evaporation process increases performance Condenser temperature linked to outside wet bulb temperature (less than or equal to dry bulb) Condenser water and evaporative water kept separat
12
Condensers (contd)
Cooling Towers
13
Condenser Examples
14
15
Digital images on this slide courtesy of: Lisa Fricker, Graduate Student, UIUC
16
17
from the surrounding environment, evaporating the refrigerant from a liquid (or liquid/vapor mixture) to a (superheated) vapor Evaporator is also a heat exchanger Evaporator can be a cooling coil itself or a refrigerant (DX or direct expansion coil) to water heat exchanger to the chilled water loop
18
Heat Exchangers
Heat Exchanger Types (largest to smallest): Shell-and-Tube Plate/Plate-and-Frame Tube-in-Tube Shell-and-Coil Heat Exchanger Issues: Larger exposed air means largest UA (more heat transfer) Fouling can affect performance over time (maintenance issues) Interior and exterior fins on coils
19
Compressors
Purpose: to compress the refrigerant vapor to a
higher pressure (also increases the temperature) Mechanical device: power input converted to mechanical energy Types of Compressors:
Dynamic: spinincrease pressure by transferring angular momentum, momentum converted to pressure increase
Centrifugal
Compressors (contd)
Motor Types
Hermetic: motor and compression chamber same, motor shaft and compressor crankshaft integral Semi-hermetic: bolted construction allows field service
21
Expansion Valve
Condenser
Compressor
Evaporator
To Zones
22
Compression-based chillers use electrical energy (work) to produce heating or cooling (in the opposite direction of natural energy flow) Absorption-based chillers use mixture/solution chemistry and a heat source to produce heating (reverse cyclealso called heat transformer) or cooling (forward cyclemore common)\ Absorption-based systems are most effective when a free or very inexpensive source of heat is available
Solar energy Waste heat Heat source must be high enough quality (temperature) to drive system
No compressor or other large rotating mechanical equipment needed Two refrigerantsprimary and secondary (absorbent)
Primaryusually water Secondaryusually ammonia or lithium bromide (LiBr)
23
Generator (desorber)high pressure side Condenserhigh pressure side Evaporatorlow pressure side Absorberlow pressure side Heat Exchanger Pump Expansion valve/flow restrictors Refrigerants
24
25
26
Initially, this was as simple as cutting ice blocks from Lake Michigan and storing those until summer Now, energy storage is produced during off-peak hours when energy costs are lower
Overall dollar effect is a reduction in the conditioning costs for the buildingprimary (or only) benefit is economic Reduction in cost per kW-hr and reduction in demand costs
Costs based on type of power plants running Cost of start-up and shutdown of power plants
Mainly an issue for industrial customers, usually used for cooling Utilities have in the past actually paid (in part) for systems
Reduced demand reduces need for new power plants Shift of electric load uses power that might not otherwise be used (hydroelectric, nuclear, etc.)
28
differences of water at different temperatures Inlet diffusers must be designed to avoid mixing Some energy transfer does occur between hot and cold sides Water in tank can serve as emergency water source in case of fire Water temperatures for cooling same as for standard chiller only system Large tank needs large space, tank losses
29
Ice Storage
Storage of cooling energy in the form of ice Latent heat of solidification allows large amount
of energy storage in a much smaller area than a water system System types:
Ice-on-coil outside melt (obsolete) Ice-on-coil inside melt Encapsulated ice (ice container) Ice harvester Ice slurry
30
Chiller priority: chiller runs during on-peak only up to some set demand limit, ice meets all other needs Ice priority: storage meets demand up to some limit and chiller is turned on if the demand is higher than the limit
Some shift of energy consumption to off-peak, also savings on demand costs Smaller chiller requirements than full storage or no storage
32
Zero predictionchiller charges system at its capacity as soon as off-peak period starts Optimal strategies
Delay start of charging to take advantage of
presumably cooler outdoor air in early morning hours And/or run chiller at less than full capacity at whatever its optimal fraction of full load is
33
Heating Equipment
Boiler Furnace
Heat Pump
Heating Equipment
Electric resistance heating
Heat pump in heating mode Solar panels Boiler
Water
Steam
Furnace (air)
35
Boilers
Definition: equipment whose sole
purpose is to provide hot water or steam for various uses within a building Size (capacity) range: 15 kW 30+ MW
Fuels: coal, wood, fuel oil, (natural)
gas, electricity
36
Boiler Uses
Steam: Heating coils (reheat, preheat) Hot water heat exchangers Absorption cooling Laundry Sterilizers Water: Heating coils (reheat, preheat) Domestic hot water
37
Goal: Try to get most efficient transfer of heat from flue gas (combustion products) to water
burner
air/fuel mix
38
Digital image on this slide courtesy of: Lisa Fricker, Graduate Student, UIUC
39
Boilers: Types
Dry Base/Back
Wet Base/Back/Leg
Base (bottom), back (with respect to multipass boilers), leg (top and sides) Flue gas condensing due to low return temperature of water More efficient, but potential for rust greatly increased
Condensing
40
Boilers: Efficiency
Fuel Boiler (combustion efficiency)
Condensing 88-95+%
Furnaces
Heats air indirectly
Combustion products do not mix with circulated air dangerous Natural gas (most common) LPG (liquefied petroleum gas) Oil Electric
42
Fuels:
Furnaces (continued)
Sizes:
Various configurations:
44
Boiler/Furnace Stack
45
Furnace Efficiency
ANSI/ASHRAE Standard 103 Annual Fuel Utilization Efficiency (AFUE)
Usable Heat Output AFUE Fuel Input
AFUE includes: latent and sensible losses, cyclic effects, infiltration, pilot burner effects, and losses from a standing pilot when furnace not in use AFUE 78-80% for non-condensing, 90+% for condensing
46
supply fan
Secondary System
pump
cooling coil
pump
boiler
Primary System
chiller
pump
cooling tower
47
Summary
Primary systems convert one form of
energy (fuel, electricity, etc.) to thermal energy Chillers/heat pumps are used to provide cooling (direct expansion or chilled water) Boilers are used to provide steam or hot water for heating coils Furnaces are used to provide hot air
48