Gen Protection
Gen Protection
Manoj Barsaiyan
In this scheme no switchgear is provided between the generator and generator transformer, which are treated as a unit; a unit transformer is tapped off the interconnection for supplying of power to auxiliary plant.
GCB SCHEME
Generator circuit breaker scheme: In this scheme a generator circuit breaker is provided between the generator and generator transformer. unit transformer is tapped off before the GCB for supplying of power to auxiliary plant. B)
CLASS A TRIPS
All electrical trip Trip turbine , field, generator,GT,UT
CLASS-B TRIP
Mechanical trips Avoid over speeding of turbine due to steam entrapped in turbine. Turbine trip signal is given first and the active power, sensed by the low forward relay (32g) gives the trip signal to the unit breaker & field breaker after a time delay. In GCB scheme, only GCB and field is tripped, keeping UAT charged through GT In non GCB scheme, HV CB,Field,UT LCV CB are tripped.
Class C
Trips only Gen CB
CLASS OF TRIP
Class A
BREAKERS TO BE TRIPPED UNDER VARIOUS CLASSES OF TRIPPING GCB SCHEME NON GCB SCHEME (additional LV CB between Gen and GT) A1: GCB,HVCB,UT HVCB,UT LV CB, FIELD, TURBINE LV CB, (All the system tripped) FIELD, TURBINE (All the system tripped) A2 : GCB, FIELD, TURBINE (Generator circuit tripped & Auxiliaries charged from the grid through GT&UT) GCB,FIELD BREAKER Initiated by Turbine trip & Low Forward /reverse power, to release the trapped steam. Generator circuit breaker tripped & Auxiliaries charged from the grid through GT&UT) HVCB (Generator under House load )
Class B
Class C
Differential Relay
GEN WDG
Current flow in relay secondary circuit in case a fault occurs in side the equipment.
Differential Protection
Generator Differential UAT Differential Overhead line Differential G.T. Restricted Earth Fault Overall Differential includes Generator, GT, and both UAT
Differential Protection
The relay operates on the principle of circulating current system The current entering and leaving the protected zone is determined by CT During a fault, there is distinct difference between the current at neutral and terminal ends of winding. This difference is detected by Differential relay
GEN WDG
I1 I2
87
CT 7000 A
0.7 A
0A R
0.7 A
0.7 A Y
B 7000 A 0.7 A
CT 2000 A
0.2 A
0.5 A R
0.2 A
0.7 A Y
B 7000 A 0.7 A
50Z
GT
Ig
GENERATOR
87 GT
64
Operate zone
Blind zone
Operate zone
O
0
Y
50 100
x to y represents a blind zone. The relay operates if the magnitude of the third harmonic voltage is
a) Less than OA/or b) more than OB
The problem of blind-zone is overcome by providing two protection system operating simultaneously 1) The one system monitors the fundamental component of the neutral voltage.
50
100
With the combined protection system, each relay element covers the blind zone
of the other and the combined protection system will detect earth faults anywhere on stator winding
A three phase balanced load ( i.e, generator stator ) produces a reaction field which rotates synchronously with rotor field system. Any unbalanced condition can be resolved into positive, negative & zero phase sequence condition The positive sequence components are similar to balanced load. Zero phase sequence reaction produces no armature reaction no reaction field.
The negative sequence components are similar to positive sequence system except that the resulting reaction field (armature reaction) rotates counter clockwise to D.C field(rotor). Voltage inducing in the rotor at double frequency. Eddy currents are very large and cause severe heating in the rotor, alternate electromagnetic torque unsatisfactory vibration in stator core.
A machine can be assigned a continuous negative sequence current rating. for turbogenerators this rating is low( 10 to 15 % of the continuous mean rating.i.e. positive sequence).
For short- time heating is of interest during system fault conditions, the heat dissipation during such periods is negligible and the heat generated can be considered to be retained entirely within the thermal capacity of the rotor.
I2 2 t = K
Where I2 = Negative sequence component
The protection should have a time delay characteristics which is as near as is practicable
to the heating characteristics of the machine. The protection should contain an alarm feature which operates at a setting slightly lower than
that of the tripping element.
Shaping Circuit
Integrator
Comparator
Starter
AND Trip
C. T. INPUT
Starter
It is usual to provide overcurrent relays of the IDMT pattern to generators, as a general backup feature. These relays are in no way related to the thermal characteristics of the generator and are intended to operate only under fault conditions.
LOSS OF EXCITATION
Loss of excitation results in a generator losing synchronism and running above synchronous speed. It will operate as an induction generator. The main flux is produced by the wattless stator current drawn from the system
The machine will continue to generate power, the value being determined by the load setting of the turbine governor. Slip frequency currents flow in the rotor, the currents flow in the damper windings and also in the slot wedges and the surface of the solid rotor body.
(a) Abnormal heating of the rotor (b) Overloading of the stator winding Operation as an induction generator brings no immediate danger to a set.
The active power delivered as induction generator will be slightly less than the prefault load because of the speed regulation characteristic of the governor The rotor currents are proportional to this power output and heating is proportional to the square of the rotor current.
characteristics of each machine. 1. A 60 MW unit with conventional cooling will not be heated excessively
by asynchronous operation at full load for 5 minutes.
2. Higher machine ratings are obtained by more intensive cooling techniques, such as hydrogen and water cooling, rather
than by an increase in physical size. The effect is to reduce the thermal time
constants and in particular the ability to withstand abnormal conditions.
FIELD FAILURE PROTECTION Generator runs as induction generator heavy reactive loading of stator slip freq induced currents in rotor
below a preset value. The relay must have a setting below the minimum exciting current, which may be 8% of that corresponding to the MCR of
the machine.
&
&
To T GG o G G
TTR-A
TTR-B ESV/IV closed Trip relay
>
A relay reset
Delayed tripping of generator after 2 seconds of power <0.5% of rated power to evaluate the mechanical of steam entrapped in the turbine and eliminate the chance of over speeding of turbine.
VT Healthy
T1 2 sec
Reverse Power detected
&
To 286G
>
T1 = 2A/37G T2 = 2B/37B
T2 50 sec
&
This protection acts under the following conditions of operation. 1.Turbine tripped and reverse power detected for 2 seconds. 2.Turbine stop valves closed and reverse power detected 2 seconds. 3.Reverse power detected for 50 seconds. In steam turbine under normal operation there is a continuous flow of steam through the machine. Any losses due to turbulence will be converted into heat, which will be continuously carried away by the steam.
If the flow of steam ceases(control valve close due to any protection, generator fails to trip on low forward power) while set continues to run at full speed, the turbulence losses in the trapped steam may then build up a high temperature condition in low pressure stages, leading to softening and distortion of blades.
86 G 286 G
>1
386 G
To trip Generator main breaker To trip Generator middle breaker Generator back up protection trip relay
impedance stage-2
>1
286 G
386 G 486 G
ROTOR FAULTS
The field circuit of a generator , comprising the winding and the armature of the exciter with any associated field circuit breaker, is an isolated d.c. circuit which in itself need not be earthed. If an earth fault occurs, no fault current will flow and the need for action will not be required.
separate point in the winding, causing the current to be diverted, and therefore produces an unbalanced field forces on the rotor and results shaft distortion if fault is not cleared quickly .
Unbalanced magnetic forces on the rotor results in violent vibration of the rotor, which may damage rotor.
Exciter
Field winding
POTENTIOMETER METHOD
The potentiometer method comprises a center tapped resistor connected in parallel with the field
winding. The center point of the resistor is connected to earth through a voltage relay.
An earth fault on the field winding will produce a voltage across the relay, the maximum voltage occurring for faults at the ends of the winding.
undetected,
the
tapping
point
on
the
Exciter
Field winding
Auxiliary Supply
Sensitive Relay
64
It comprises an auxiliary supply transformer, the secondary of which is connected between earth and
one side of the field circuit, through an interposed capacitor and a relay coil.
An earth fault anywhere in the field winding will give rise to a current which is detected by the relay.
current and blocks the nominal field voltage, preventing discharge of a large direct current through the transformer.
ADVANTAGE
This scheme has the advantage over the potentiometer method in that there is no BLIND SPOT in the supervision of the field system.
DISADVANTAGE
The A.C. injection method has disadvantage that some current will flow continuously through the capacitance of the field winding to earth.
The current may flow through the machine bearings, causing erosion of the machine bearing surface.
bearings and to provide an earth brush for the shaft, and if this is done the capacitance current should be harmless.
The capacitance currents associated with the a.c. injection method are avoided by rectifying the injection voltage.
The d.c. output of the transformer-rectifier power unit is arranged to bias the positive side of the field circuit to a negative voltage w.r.t. the earth.
The negative side of the field system is at greater negative voltage to earth, so an earth fault at any point on the field winding will cause current to flow through the power unit.
The current is limited by including a high resistance in the circuit and a sensitive relay is used to detect the current.
maximum.
Slip ring
Field winding
Diode wheel
Main exciter
Rotor E/F relay
500MW GENERATOR
Exciter
Field winding
Auxiliary Supply
Sensitive Relay
64
The capacitance currents associated with the a.c. injection method are avoided by rectifying the injection voltage.
The d.c. output of the transformer-rectifier power unit is arranged to bias the positive side of the field circuit to a negative voltage w.r.t. the earth.
The negative side of the field system is at greater negative voltage to earth, so an earth fault at any point on the field winding will cause current to flow through the power unit. The current is limited by including a high resistance in the circuit and a sensitive relay is used to detect the current.
maximum.
MECHANICAL PROTECTIONS
Protections that initiate turbine trip:: Liquid in terminal box High cold gas temp. High exciter hot air temp. High seal oil temperature from cooler Stator Water conductivity high Stator Water Flow Low GCB and FB open on low forward power.
THANK YOU