0% found this document useful (0 votes)
10 views

ECE4762011 Lect21

The document discusses symmetrical components and analysis of unbalanced faults on power systems. It covers different types of single line to ground faults, line to line faults, and double line to ground faults. It derives the relationships between sequence networks for each fault type and provides examples of analyzing faults on a sample system.

Uploaded by

Muhammad Ali
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views

ECE4762011 Lect21

The document discusses symmetrical components and analysis of unbalanced faults on power systems. It covers different types of single line to ground faults, line to line faults, and double line to ground faults. It derives the relationships between sequence networks for each fault type and provides examples of analyzing faults on a sample system.

Uploaded by

Muhammad Ali
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 36

Lecture 21

Symmetrical Components, Unbalanced Fault Analysis





Professor Tom Overbye
Department of Electrical and
Computer Engineering



ECE 476
POWER SYSTEM ANALYSIS
1
Announcements
Be reading Chapters 9 and 10
HW 8 is due now.
HW 9 is 8.4, 8.12, 9.1,9.2 (bus 2), 9.14; due Nov 10 in class
Start working on Design Project. Tentatively due Nov 17 in
class
Second exam is on Nov 15 in class. Same format as first
exam, except you can bring two note sheets (e.g., the one
from the first exam and another)
2
Single Line-to-Ground (SLG) Faults
Unbalanced faults unbalance the network, but only
at the fault location. This causes a coupling of the
sequence networks. How the sequence networks
are coupled depends upon the fault type. Well
derive these relationships for several common
faults.
With a SLG fault only one phase has non-zero fault
current -- well assume it is phase A.

3
SLG Faults, contd
?
0
0
f
a
f
b
f
c
I
I
I
(
(
(
(
=
(
(
(
(

(

0
2 0
2
Then since
1 1 1
?
1 1
1 0
3 3
0
1
f
f
f f f f a
f
I
I I I I I
I
o o
o o
+ +

(
(
(
(
(
(
(
= = = =
(
(
(
(
(

(

4
SLG Faults, contd
0
2
2
0
1 1 1
1
1
This means
The only way these two constraints can be satisified
is by coupling the sequence networks in series
f f
a f a
f
f
a
f
f
b
f
c
f
f
a f f f
V Z I
V
V
V V
V
V
V V V V
o o
o o
+

+
=
(
(
(
(
(
(
(
=
(
(
(
(
(
(
(


= + +
5
SLG Faults, contd
With the
sequence
networks in
series we can
solve for the
fault currents
(assume Z
f
=0)

0
1.05 0
1.964
(0.1389 0.1456 0.25 3 )
5.8 (of course, 0)
f f f
f
f f f
s a c b
I j I I
j Z
I j I I
+
Z
= = = =
+ + +
= = = = I A I
6
Example 9.3
7
Line-to-Line (LL) Faults
The second most common fault is line-to-line,
which occurs when two of the conductors come in
contact with each other. With out loss of generality
we'll assume phases b and c.
0
bg
Current Relationships: 0, , 0
Voltage Relationships: V
f f f
a c f b
cg
I I I I
V
= = =
=
8
LL Faults, cont'd
( ) ( )
0
2
2
0
2 2
Using the current relationships we get
1 1 1 0
1
1
3
1
0
1 1

3 3
Hence
f
f
f b
f
b
f
f
f f
f f
b b
f f
I
I I
I
I
I
I I I I
I I
o o
o o
o o o o
+

+
+
(
( (
(
( (
(
=
( (
(
( (

(

=
= =
=
9
LL Faults, con'td
( )
( )
0
2
2
2
2
Using the voltage relationships we get
1 1 1
1
1
3
1
Hence
1
3
1
3
f
f ag
f
f
bg
f
f
cg
f f
f ag
bg
f f
f ag f f
bg
V V
V V
V
V
V V V
V V V V V
o o
o o
o o
o o
+

+
+
( (
(
( (
(
( (
=
(
( (
(
( (

(
= + +

(
= + + =

10
LL Faults, cont'd
To satisfy &
the positive and negative sequence networks must
be connected in parallel
f f f f
I I V V
+ +
= =
11
LL Faults, cont'd
2
2
Solving the network for the currents we get
1.05 0
3.691 90
0.1389 0.1456
1 1 1
0 0
1 3.691 90 6.39
3.691 90 6.39
1
f
f
a
f
b
f
c
I
j j
I
I
I
o o
o o
+
Z
= = Z
+
(
(
( (
(
(
( (
= Z =
(
(
( (
(
(
Z
( (


(

12
LL Faults, cont'd
2
2
Solving the network for the voltages we get
1.05 0 0.1389 3.691 90 0.537 0
0.1452 3.691 90 0.537 0
1 1 1
0 1.074
1 0.537 0.537
0.537 0.537
1
f
f
f
a
f
b
f
c
V j
V j
V
V
V
o o
o o
+

= Z Z = Z
= Z = Z
(
(
(
(
(
(
= =
(
(
(
(
(

(


(

(
(
(
(

13
Double Line-to-Ground Faults
With a double line-to-ground (DLG) fault two line
conductors come in contact both with each other
and ground. We'll assume these are phases b and c.
0 ( )
f f f f f
a cg f c
bg b
I V V Z I I = = = +
14
DLG Faults, cont'd
0
2
2
0
From the current relationships we get
1 1 1
1
1
Since 0 0
Note, because of the path to ground the zero
sequence current is no longer
f
f
a
f
f
b
f
c
f
f
a f f f
I
I
I I
I
I
I I I I
o o
o o
+

+
(
(
(
(
(
(
(
=
(
(
(
(
(
(
(


= + + =
zero.
15
DLG Faults, cont'd
0
2
2
0 2
2 2
0
From the voltage relationships we get
1 1 1
1
1
3
1
Since
Then ( )
But since 1 0 1
f
f ag
f
f
bg
f
f
bg
f f
cg f f bg
f
f f
bg
f
f f
bg
V V
V V
V V
V V V V
V V V
V V V
o o
o o
o o
o o o o
+

+
+
+
( (
(
( (
(
( (
=
(
( (
(
( (

= =
= + +
+ + = + =
=
16
DLG Faults, cont'd
0
0 2
0 2
2
0 0
0 0
( )
Also, since
Adding these together (with -1)
(2 ) with
3
f
f f
bg
f f
f c
b
f
f f f
b
f
c f f f
f
f f f f f f f
bg
f f f f
V V V
Z I I
I I I I
I I I I
V Z I I I I I I
V V Z I
o o
o o
o o
+
+ +
+ +
+ +
+
=
= +
= + +
= + +
+ =
= =
=
17
DLG Faults, cont'd
The three sequence networks are joined as follows
0
1.05 0
0.1389 0.092
( 3 )
4.547 0
f
f
V
I
j j
Z Z Z Z
+
+
+
Z
= =
+
+ +
= Z 9
Assuming Z
f
=0, then
18
DLG Faults, cont'd
0
1.05 4.547 90 0.1389 0.4184
0.4184/ 0.1456 2.874
4.547 2.874 1.673
Converting to phase: 1.04 6.82
1.04 6.82
f
f
f f f
f
b
f
c
V j
I j j
I I I j j j
I j
I j
+

+
= Z =
= =
= = =
= +
= +
19
Unbalanced Fault Summary
SLG: Sequence networks are connected in series,
parallel to three times the fault impedance
LL: Positive and negative sequence networks are
connected in parallel; zero sequence network is not
included since there is no path to ground
DLG: Positive, negative and zero sequence
networks are connected in parallel, with the zero
sequence network including three times the fault
impedance
20
Generalized System Solution
Assume we know the pre-fault voltages
The general procedure is then
1. Calculate Z
bus
for each sequence
2. For a fault at bus i, the Z
ii
values are the thevenin
equivalent impedances; the pre-fault voltage is the
positive sequence thevenin voltage
3. Connect and solve the thevenin equivalent sequence
networks to determine the fault current
4. Sequence voltages throughout the system are

21
Generalized System Solution, contd
4. Sequence voltages throughout the system are given
by

0
0
0
0
prefault
f
I
Z
(
(
(
(
(

= +
(
(
(
(
(

V V
This is solved
for each
sequence
network!
5. Phase values are determined from the sequence values
22
Unbalanced System Example
For the generators assume Z
+
= Z

= j0.2; Z
0
= j0.05
For the transformers assume Z
+
= Z

=Z
0
=

j0.05
For the lines assume Z
+
= Z

= j0.1; Z
0
= j0.3
Assume unloaded pre-fault, with voltages =1.0 p.u.
23
Positive/Negative Sequence Network
24 10 10 0.1397 0.1103 0.125
10 24 10 0.1103 0.1397 0.125
10 10 20 0.1250 0.1250 0.175
bus bus
j j
+ +

( (
( (
= =
( (
( (

Y Z
Negative sequence is identical to positive sequence
24
Zero Sequence Network
0 0
16.66 3.33 3.33 0.0732 0.0148 0.0440
3.33 26.66 3.33 0.0148 0.0435 0.0.292
3.33 3.33 6.66 0.0440 0.0292 0.1866
bus bus
j j

( (
( (
= =
( (
( (

Y Z
25
For a SLG Fault at Bus 3
The sequence networks are created using the pre-fault
voltage for the positive sequence thevenin voltage,
and the Z
bus
diagonals for the thevenin impedances
Positive Seq. Negative Seq. Zero Seq.
The fault type then determines how the networks are
interconnected
26
Bus 3 SLG Fault, contd
0
1.0 0
1.863
(0.1750 0.1750 0.1866)
1.863
1.0 0 0 0.7671
1.0 0 0 0.7671
1.0 0 1.863 0.6740
0 0.2329
0 0.2329
1.863 0.3260
f
f f f
bus
bus
I j
j
I I I j
j
j
+
+
+ +

Z
= =
+ +
= = =
Z
( ( (
( ( (
= Z + =
( ( (
Z
( ( (

( (
( (
= =
(

(

V Z
V Z
(
(
27
Bus 3 SLG Fault, contd
0 0
3
1
0 0.0820
0 0.0544
1.863 0.3479
We can then calculate the phase voltages at any bus
0.3479 0
0.6740 0.522 0.866
0.3260 0.522 0.866
0.0820
0.7671
bus
j
j
j

( (
( (
= =
( (

( (

( (
( (
= =
( (
+
( (

=
V Z
V A
V A
0.4522
0.3491 0.866
0.2329 0.3491 0.866
j
j
( (
( (
=
( (
+
( (

28
Faults on Lines
The previous analysis has assumed that the fault is
at a bus. Most faults occur on transmission lines,
not at the buses
For analysis these faults are treated by including a
dummy bus at the fault location. How the
impedance of the transmission line is then split
depends upon the fault location

29
Line Fault Example
Assume a SLG fault occurs on the previous system
on the line from bus 1 to bus 3, one third of the way
from bus 1 to bus 3. To solve the system we add a
dummy bus, bus 4, at the fault location
30
Line Fault Example, contd
44 10 0 30
10 24 10 0
0 10 25 15
30 0 15 45
Adding the dummy bus only changes the new
row/column entries associated with the dummy bus
0.1397 0.1103 0.1250 0.1348
0.1103 0.1397 0.1250 0.1152
0.125
bus
bus
j
j
+
+

(
(

(
=

(
(


=
Y
Z
0 0.1250 0.1750 0.1417
0.1348 0.1152 0.1417 0.1593
(
(
(
(
(

The Y
bus

now has
4 buses
31
Power System Protection
Main idea is to remove faults as quickly as possible
while leaving as much of the system intact as
possible
Fault sequence of events
1. Fault occurs somewhere on the system, changing the
system currents and voltages
2. Current transformers (CTs) and potential transformers
(PTs) sensors detect the change in currents/voltages
3. Relays use sensor input to determine whether a fault has
occurred
4. If fault occurs relays open circuit breakers to isolate fault


32
Power System Protection
Protection systems must be designed with both
primary protection and backup protection in case
primary protection devices fail
In designing power system protection systems
there are two main types of systems that need to be
considered:
1. Radial: there is a single source of power, so power
always flows in a single direction; this is the
easiest from a protection point of view
2. Network: power can flow in either direction:
protection is much more involved

33
Radial Power System Protection
Radial systems are primarily used in the lower
voltage distribution systems. Protection actions
usually result in loss of customer load, but the
outages are usually quite local.
The figure shows
potential protection
schemes for a
radial system. The
bottom scheme is
preferred since it
results in less lost load
34
Radial Power System Protection
In radial power systems the amount of fault current is
limited by the fault distance from the power source:
faults further done the feeder have less fault current
since the current is limited by feeder impedance
Radial power system protection systems usually use
inverse-time overcurrent relays.
Coordination of relay current settings is needed to
open the correct breakers
35
Inverse Time Overcurrent Relays
Inverse time overcurrent relays respond instan-
taneously to a current above their maximum setting
They respond slower to currents below this value
but above the pickup current value

You might also like