Specifications: Type
Part Number
Supply Voltage: ……………….230/240Vac, ……50/60Hz , .… +/- 15% Temperature Range / Scale Divisions Thermocouple
115Vac, ……….. 50/60Hz ,…..+/- 15% 230/240Vac
24VAC, ………...50/60Hz,……+/- 15%
0 to + 250 °C 5 °C Type J 89 420 047
Max Power Consumption …… 2 VA 0 to + 450 °C 10 °C Type J 89 420 067
0 to + 650 °C 10 °C Type J 89 420 097
Inputs: 0 to + 800 °C 20 °C Type K 89 420 077
Thermocouple …………………IAW IEC 584………….………….J or K types 0 to + 1000 °C 20 °C Type K 89 420 087
Max line resistance:………………………………………..………..150Ω 115Vac
0 to + 250 °C 5 °C Type J 89 420 045
Derating with regard………….Per 10°C Variation in …………… ≤ 1 °C 0 to + 450 °C 10 °C Type J 89 420 065
to setpoint in Ambient Temp.
0 to + 650 °C 10 °C Type J 89 420 095
Per 10Ω of line ……………………≤ 1 °C
0 to + 1000 °C 20 °C Type K 89 420 085
Resistance Variation
Per 10% variation ……………… ≤ 0.1 % 24Vac
In supply voltage 0 to + 250 °C 5 °C Type J 89 420 041
0 to + 450 °C 10 °C Type J 89 420 061
PT100………………………….IAW IEC 751……………………… 2 Wire 0 to + 650 °C 10 °C Type J 89 420 091
Derating following line resistance …………………………………..1 °C / 0.4Ω 0 to + 800 °C 20 °C Type K 89 420 071
0 to + 1000 °C 20 °C Type K 89 420 081
Derating with regard………….Per 10°C Variation in …………… ≤ 1 °C
to setpoint in Ambient Temp.
Per 10% variation …… ≤ 0.1 % Outputs:
In supply voltage Contact relay……………………SPDT…………………….5 A / 250Vac max
5
Operation Mechanical life……………………………………………….3 x 10 operations
ON/OFF output………………..Fixed Hysteresis…………………..0.4% Scale resolution……………………………………………..80mm
PD output…………………… Fixed proportional…………………3% Display accuracy……………....J – K (full scale)……….. ± 2%
Band (% of full scale) PT 100 (full scale)……….± 1.5%
Period proportional………………..22 s Temperature limits……………. Operational………………0 °C + 55 °C
band Storage………….………-20 °C + 70 °C
Front Panel Rating …………….IP 41
Case……………………………..IP 20
Weight…………………………...350 g