Control of Shunt Active Power Filter Using Multi Resonant Controller
Control of Shunt Active Power Filter Using Multi Resonant Controller
Abstract— Active power filters are used to eliminate current reference control current. Here highly efficient
harmonics near nonlinear loads. In this paper the control of synchronous frame reference method is employed for
3-level shunt active power filter is proposed using frequency balanced harmonic systems. The new idea of controlling
selective proportional plus multiple resonant controllers. power system quality is presented for non-linear
The voltage source converter (VSC) is operated using ramp- unbalanced system for getting the reference current. The
comparison current control method. The method provides formulated technique is done by means of the closed-loop
fixed switching frequency operation, and unipolar control of source current. The reference current is
modulation of a control function yields three levels PWM identified by the idea of energy balancing under the
output. The resonant controllers are tuned near the
controlled system [4], [5].
harmonic frequencies to be compensated. The analysis of
THD’s also done to realize the accuracy of this active filter. The resonant controllers are tuned near harmonic
The performance of the proposed shunt active power filter is frequencies to be compensated. This compensates the
illustrated through the compensation of a distribution selected frequencies and improves total harmonic
system using PSCAD/EMTDC simulation package. distortion (THD). Furthermore, a resonant action at
fundamental frequency provides near unity power factor
Keywords- Shunt Active Power Filter, resonant controller, operation with balanced source currents. Here two
3-level modulation, synchronous reference frame, THD.
different situations are taken and solved using resonant
controllers tuned near fundamental frequency. The
I. INTRODUCTION performance of proposed shunt active power filter is
illustrated through PSCAD/EMTDC simulation package
The ac power system has always been susceptible to and results are verified.
problem regarding harmonics and reactive power from the
very beginning. It has worsened with the increased use of
power electronic converters as some of these converters II. SHUNT ACTIVE POWER FILTER
not only increase currents but also generate harmonics in Shunt active filters (Fig.1) have been recognized as a
the source current. The increased reactive power, solution of harmonic current and reactive power
harmonics and unbalances cause an increase in line losses, compensation for non-linear loads. The principle of
instability and voltage distortion. A shunt active power operation of the shunt active filter is based on the
filter is a voltage source converter based device operated in generation and injection of harmonic currents up to a
a current control mode. It improves the quality of power desired order to the system. Consequently, the
by eliminating harmonic content of load [1]-[3]. characteristics and efficiency of harmonic compensation
The resonant controller means PI controller tuned near and its effectiveness depend on the control algorithm
fundamental frequencies to be compensated. The method applied to calculate the load current harmonics problems.
of ramp comparison used here gives two level controls of
VSC’s. Here performance is decided by triangular carrier.
The use of multiresonant controller gives frequency
selective compensation. The three level control of shunt
active power filter is achieved by using frequency selective
proportional plus multiresonant controllers. Also
modulation of control function provides three- level PWM
output.
The performance of active power filter is dependent on
how the reference compensating signals are estimated.
Conventionally, either the instantaneous active and
reactive power p-q method or the instantaneous active and
reactive current component method is employed. Both
Figure. 1. The principle diagram of shunt active power filter
these methods require complexity in calculating the
V ta V o
The control function Cerr is compared with the carrier
i shrefa i la ( P lav P dc ) (1)
Vtri of frequency c and amplitude Vtri. Three-level
V Vo output voltage vo . is obtained following the unipolar
i shrefb i lb tb ( P lav P dc ) (2)
PWM of the control function as follows. The condition
V Vo for firing of Inverter Bridge is given here.
i shrefc i lc tc ( P lav P dc ) (3)
_ For 1st leg of the H-bridge,
where ilk and vtk, are load currents and PCC terminal
voltages respectively for the three phases and Condition 1 Cerr - Vtri > 0 then Sw1 is on, leading to
1 uA = +1 and vAO = + Vdc/2
Vo Vt
3 a ,b , c
(4) Condition 2 Cerr - Vtri < 0 then Sw4 is on, leading to
uA = - 1 and vAO = - Vdc/2
2
Vt Vo
2
(5) Similarly for 2nd leg of the H-bridge
a , b ,c
Note that the PCC terminal voltages vtk, k = a,b,c, Condition 3 - Cerr - Vtri > 0 then Sw3 is on, leading to
used in (4), are the fundamental frequency components of uB = +1 and vBO = + Vdc/2
the terminal voltages that are extracted from the Condition 4 - Cerr - Vtri < 0 then Sw2 is on, leading to
measurement of the actual voltages.The objective of pdc in
(6) is to hold the average dc voltage Vdcav constant and uB = -1 and vBO = - Vdc/2
equal to Vdcref , by extracting the real power from ac
system, and hence the dc control loop is given by
where Kpdc and Kidc are the proportional and integral gains
respectively. The error e between the reference dc voltage
and the average dc voltage is given as
Cerr is assumed sinusoidal, i.e., M iVtri cos(0t ) where ishrefa erra Cerra Voa _
Gc (s) GM G(s)
+
0 is the fundamental frequency and Mi is the modulation +
_
index under closed loop, then the analytical expression for isha
three-level inverter output voltage vo is given as,
kpdc
i shref + -
kidc
i sh
Table 1
Parameters Numerical Value
System Voltage and
440 V,50 HZ
frequency
Feeder impedence 1.0,10.0 mH
System MVA
100 KVA
Transformer 100 KVA,11V/440V
Rectifier bridge load
100 Ω,200µF
Figure. 11. Inverter output voltage for phase-a.
Ra=200 Ω ,La=200mH,Ca=1.0µF
Unbalanced load Rb=250 Ω Lb=300mH,Cb=2.0µF
Rc=100 Ω,Lc=400mHCc=5.0µF
Figure 13. FFT analysis of source and load current after compensation
Figure. 10. Transient characteristics for tracking reference shunt current
for phase-a
-
loss V. COMPARISON WITH EXSTING METHOD
ila iaf
dqo
Isha ref Here this new method is compared against existing
abc HPF
- - ibf loss method like instantaneous power theory. By doing the
ilb abc Ishb ref
dqo same procedure and system conditions with instaneous
ilc icf lossc power theory gives a worst result than this newly adopted
HPF Ishc ref method. The spectrum analysis gives this in detail. From
this study it knows that old method is used in the situation
Fig. 14. Reference generation using dq-transformation where loads are present with lower ratings and also with
less complicated load situations. Table II give comparison
result between resonant methods with old method. The
resonant method gives better result than old method.
VI. CONCLUSIONS
In this paper, ramp comparison control method
with unipolar PWM of active power filter is presented
which gives 3-level inverter output voltage. Here two
different situations are taken and which is solved using
Figure. 15. Three-phase load current with harmonics resonant controllers. Use of proportional plus multiple
resonant controllers tuned near fundamental frequency
mitigate the poor power factor and tuned near harmonic
frequencies balances the source currents with
improvement in THD. All simulations are verified though
PSCAD/EMTDC simulation package. Working efficiency
of this method is determined by comparing it against old
method like Instaneous power theory method.
VII. REFERENCES
Figure. 16. Three-phase compensated source current, free from harmonics
B. Example [1] Rajesh Gupta, Arindam Ghosh and Avinash Joshi, “Control
of 3-level Shunt Active Power Filter using Harmonic
The parameters of the system considered in this Selective controller” Proceedings of IEEE Power India
example is same as that used in Example 1. However Conference, April 2006, pp. 10-15.
transformer kVA rating is reduced to 40 kVA with same [2] E.Twinning and D.G. Holmes, “Grid Current Regulation of a
three-phase voltage source inverter with an LCL input filter”,
voltage ratio and percent leakage impedance. The linear IEEE Trans. on Power Electronics, vol.18 ,no.3, pp.888-895
load is balanced and given by Rl = 50.0 Ω and Ll = 200.0 May/June 2003.
mH, for each phase. Nonlinear load is also same as [3] A.Ghosh and G. Ledwich, “Load compensating
considered in Example 1. Multiresonant controller is DTSTATCOM in weak AC systems”, IEEE Trans. on Power
tuned near 5th and 7th harmonics only. The three-phase Delivery, vol.18, no.4, pp.1302-1309 October 2003.
[4] J.M.M Ortega,M.P Esteeve,M.B Poyan,A.G Exposito and
load currents are having a THD of 31.0%.Fig. 15 shows
L.G Franquelo, “Reference current computation methods for
the tracking performance of shunt current. After active filter: Accuracy assessment in the frequency domain”,
compensation, source current is balanced and free from IEEE Trans. on Power Electronics, vol.20 ,no.2, pp.446-456
harmonics with THD of 1.8% with exact estimation of March 2005.
fundamental frequency. This is shown in fig. 16. [5] S.Buso,L.Malesani and P.Mattavelli, “Comparison of Current
Control Technique for Active Power Filter”, IEEE
Table II Transactions on Industrial Electronics, vol.18, no.4,
THD analysis pp.1302-1309 October 2003.
Method System [6] D. N. Zmood and D. G. Holmes, “Stationary frame current
Condition regulation of PWM Inverters with zero-steady-state error”,
used Phase a Phase b
Phase
IEEE Trans. on power Electronics, Vol.18, no.3, pp 814-822,
c
may 2003.
Before
25.1 25.4 25 [7] Green, T.C., and Marks, J.H.: ‘Control techniques for active
Instantaneous Compensation
power filters”, IEE Proc. Electr. Power Appl., Vol. 152,
power theory No. 2, March 2005, pp. 369–381.
After
method 18 18.1 18 [8] D. Zmood, D. Holmes, and G. Bode, “Frequency-domain
Compensation
analysis of three-phase linear current regulators,” IEEE
Trans. Ind. Appl., vol.37, pp. 601–610, 2001.
Before
[9] E. Lavers, P.W. Lehn, "A benchmark system for digital time
Compensation 25.1 25.4 25
Resonant domain simulation of an active power filters", IEEE Trans.
controller Power. Del., Vol. 20, No.1, January 2005, pp.234-241.
method [10] P. Verdelho, G. D. Marques, “Active Power Filter Control
After 1.2 1.19 1.19 Circuit with Phase Locked Loop Phase Angle Determination”
Compensation PEMC’98, Sep. 8-10, 1998.