The document provides instructions for calculating the rating of a capacitor for a detuned filter circuit. It prompts the user to enter the rated capacitor voltage, system voltage, percentage the reactor is detuned, frequency, and detuned capacitor kvar. It then calculates the detuned inductance, detuned reactor and maximum capacitor currents, and maximum voltage across the capacitor while accounting for harmonic limits. The recommended capacitor rating is 525 volts with a rating of 81 kvar.

Uploaded by

shaikhsajid242
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
130 views2 pages

Cap Calculation For Detune Filter - Eng

The document provides instructions for calculating the rating of a capacitor for a detuned filter circuit. It prompts the user to enter the rated capacitor voltage, system voltage, percentage the reactor is detuned, frequency, and detuned capacitor kvar. It then calculates the detuned inductance, detuned reactor and maximum capacitor currents, and maximum voltage across the capacitor while accounting for harmonic limits. The recommended capacitor rating is 525 volts with a rating of 81 kvar.

Uploaded by

shaikhsajid242
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

CAPACITOR CALCULATION FOR DETUNE FILTER

** Enter 4 value ** Capacitor rated : System voltage : % detuned reactor : Frequency : Detuned Capacity of Capacitor 75 Kvar Detuned Capacitor Voltage 506 Volt Detuned Capacitor Current 85.77 Amp 50 400 6 50 Kvar Volt % Hz

Detuned Inductance of Reactor 0.650 mH.

Maximum of Hamonic Limit

U1 = 6 % , U3 = 0.5 % , U5 = 5 %

CAPACITOR RATED WITH DETUNE FILTER =

525

Volt

81

Kvar

* Norminal capacitor current is summed with maximum harmonic current through capacitor. ** Norminal system voltage is summed with maximum harmonic voltage across capacitor.

ATION FOR DETUNE FILTER

Detuned Reactor Current 88.83 Amp

Max Current of Capacitor including Harmonic Current * 84.60 Amp

Max Voltage across Capacitor ** 506 Volt

U1 = 6 % , U3 = 0.5 % , U5 = 5 % , U7 = 5 %

REMARK : FOR CAPACITOR RATED STANDARD 400V, 440V , 480V , 525V 580V , 690V , 790V , 1000V