Short Circuit Lecture Using EDSA-ETAP-PSSE-Matlab
Short Circuit Lecture Using EDSA-ETAP-PSSE-Matlab
Short Circuit Lecture Using EDSA-ETAP-PSSE-Matlab
Roel B. Calano
a c Z0 Z0 Z0
Z0 N0 b
a c Z0 Z0 Zn Z0 b 3Zn
Z0
N0
a c Z0 Z0
Z0
Z0 b
N0
Sequence Networks
One of the most useful concepts about the symmetrical components is the sequence network. A sequence network is an equivalent network for power system under the assumption that only one sequence component of voltages and currents is presented in the system. There will be no interaction between each sequence network and each of them is independent of each other. The positive sequence network is the only one containing voltage source since generators produce only voltages of positive sequence. Negative and zero sequence networks contain only their corresponding impedances and these impedances are obtained based on the location of the fault under investigation. These sequence networks are shown in Figure. The types of fault conditions will determine the connections between the sequence networks. The positive sequence impedance, Z1, is the impedance looking into the positive sequence network from the fault point. Similarly, the negative sequence impedance, Z2, is the impedance looking into the negative sequence network from the fault point, and the zero sequence impedance, Z0, is the impedance looking into the zero sequence networks from the fault point.
Example: Draw the Zero sequence network of the power system shown
Y grounded - Y grounded -
G
Y grounded
G
Reactance grounded
Y grounded - Y grounded
Solution:
j0.2
j0.3
j0.3
j0.06
j0.25 5
j0.5 6
j0.35
j0.06
j0.09
Example: Draw the Zero sequence network of the power system shown
Y ungrounded - Y grounded Y ungrounded - Y ungrounded
G
Y ungrounded
G
Reactance grounded
Y ungrounded - Y ungrounded
Solution:
j0.2
j0.3
j0.3
j0.06
j0.25
j0.5
j0.35
j0.06
j0.09
Y grounded- Y grounded
G
Y ungrounded
G
Reactance grounded - Y ungrounded
Y grounded - Y grounded
Y ungrounded - Y grounded
G
Y grounded j0.2 2 j0.3 3 j0.3
j0.06
j0.25 5 6 j0.09
j0.35
j0.06
j0.5
j0.09
j0.09
j0.09
Y grounded - Y grounded
- Y ungrounded
Y ungrounded
- Y grounded
Y ungrounded - Y grounded
- Y grounded
Solidly grounded
Problem: Draw the Positive, Negative and zero sequence model for the power system shown.
Y grounded - Y grounded
1 2 3
G
Y grounded
G
6 Reactance grounded
Y grounded - Y grounded
- Y grounded
- Y grounded
- Y grounded
- Y grounded
- Y grounded
- Y grounded
j0.2
j0.15
j0.3
j0.2
j0.25 5
j0.22 6
j0.35
j0.2
1.0 angle 0
1.0 angle 0
j0.2
j0.15
j0.3
j0.14
j0.25 5
j0.22 6
j0.35
j0.14
j0.2
j0.3
j0.3
j0.06
j0.25 5
j0.5 6
j0.35
j0.06
j0.09
j0.2
j0.82
j0.2
1.0 angle 0
1.0 angle 0
N1 3 3
j0.0.0714
j0.3673
1.0 angle 0
1.0 angle 0
1.0 angle 0
1.0 angle 0
N1
N1
3 3
j0.0.0714
j0.0.0714 j0.0.2618
j0.3952
j0.3952
j0.3673
j0.1904 G
N1 N1
B B
N1
B B
j0.14
j0.82
j0.14
N2 3 3
j0.0.0714
j0.14
j0.14
j0.3352
j0.3073
N2
N2
3 3
j0.0.0714
j0.0.0714 j0.0.2317
j0.3352
j0.3952
j0.3073
j0.1603
N2 N2
B B
N2
B B
N0
N0
Problem: Draw the connection diagram of Positive, Negative and Zero sequence network of the 4 bus shown.
G
- Y grounded - Y grounded
G G
Consider a Three phase Fault occurs near the terminal of the generator
e= VS sin (t + )
) + sin (
s2 + 2
)]
Is [R + Ls] = VS
[ [
cos s2 + 2 +
s sin s2 + 2
cos + s sin s2 + 2
Is [ R + Ls] = VS
Is = VS
[ [
]
C + (s + R/L)
As + B (s2 + 2 )
Is = VS/ L
Solving for A, B and C: A = Ls/Z [sin ( )] C = L/Z [sin ( )] = arctan ( L/R) B = l/Z [cos ( )] Z = (R2 + (l)2
Is = VS/L
[ [
] ]
Is = VS/L
sin ( )
s s2 + 2
} + cos ( ) {
s s2 + 2
}+
sin ( ) (s + R/L)
It = VS/Z {sin ( )} (cos t) + [{cos ( )} (sin t) - {sin ( )}e Rt/L It = VS/Z {sin (t + - {sin ( )}e Rt/L
[ [
Symmetrical
Unsymmetrical
Example: Draw the wave form of short circuit current of different L/R and power factor angle Solution: L/R program
Simplifications When computing short circuits in a power system further simplifications can be made. The following simplifications are also used for the analysis All line capacitances are ignored. All non-motor shunt impedances are ignored; motor loads are treated the same way as generators. The voltage magnitude and phase angle of generators and in feeds are all set to the same value All tap changing transformers are in middle position.
These simplifications are indicated for studies regarding medium- and long-term network planning. In the planning stage, the calculations are based on estimated and hence inaccurate data. Therefore, the demands on the short circuit computation algorithm are lower than for real-time applications in the network operation, where accurate results are desired. Studies have shown that the shunt elements and loads have little influence on the short circuit currents (0.5%. . . 4%) and may compensate each other. However, disregarding the actual generator pole voltages and the actual positions of tap changing transformers may sometimes lead to errors of up to 30%.
a b c
Zf
Iaf
Ibf = 0
Icf = 0
F0 Va0 Ia0 Z0
Zero - sequence network
N0
F1
3Zf
Va1
Ia1 G
Z1
N1
F2 Va2 Ia2 Z2
Negative sequence network
N2
Analysis of Single Line to - Ground Fault Ia0 = Ia1 = Ia2 = Iaf Ibf Icf 1 1 1 1.0 0 Z0 + Z1 + Z2 + 3Zf 1 a2 a 1 a a2 Ia0 Ia1 I a2
Iaf = Ia0 + Ia1 + Ia2 Iaf = 3Ia0 = 3Ia1 = 3Ia2 Vaf = Zf Iaf Vaf = 3Zf Ia1 Vaf = Va0 + Va1 + Va2 Va0 + Va1 + Va2 = 3Zf Ia1 Va0 Va1 Va2 = 0 1.0 0 0 Z0 - 0 0 0 Z1 0 0 0 Z2 Ia0 Ia1 Ia2
Va0 = - Z0 Ia0 Va1 = 1.0 Z1 Ia1 Va2 = -Z2 Ia2 Vaf Vbf Vcf = 1 1 1 1 a2 a 1 a a2 Va0 Va1 Va2
Line-Line Fault
Model
Fault point
a b c
Ibf Zf Icf
Iaf = 0
F0 Va0 Ia0 = 0 Z0
Zero - sequence network
N0
Zf
F1 Va1 Ia1 G N1 N2 Z1
Positive sequence network
F2 Va2 Ia2 Z2
Negative sequence network
Analysis of Line to line Fault Iaf = 0 Ibf = -Icf Vbc = Vb Vc = Zf Ibf Ia0 = 0 Ia1 = -Ia2 = 1.0 0 Z1 + Z2 + Zf 1.0 0 Z1 + Z2
Ia1 = -Ia2 =
Ibf = -Icf = 3Ia1 -90 Va0 = 0 Va1 = 1.0 Z1 Ia1 Va2 = -Z2 Ia2 = Z2 Ia1 Vaf = Va1 + Va2 Vaf = 1.0 + Ia1 (Z2 Z1 ) Vbf = a2Va1 + aVa2 Vbf = a2 + Ia1(aZ2 a2Z1 ) Vcf = aVa1 + a2Va2 Vcf = a + Ia1(a2Z2 aZ1 ) Vab = Vaf Vbf Vab = 3 (Va1 30 + Va2 -30 ) Vbc = Vbf Vcf Vbc = 3 (Va1 -90 + Va2 90 ) Vca = Vcf Vaf Vca = 3 (Va1 150 + Va2 -150 )
Fault point
a b c
Zf Iaf = 0 Ibf Zg Zf Icf Ibf + Icf
Zf + 3ZG
Zf
Zf
F1 Z1 Va2 Ia2
F2 Z2
N0
N2 N1
Analysis of Double Line to ground Fault Iaf = 0 Vbf = (Zf +Zg ) Ibf + Zg Ibf Ia1 = 1.0 0 (Z1 +Zf ) + (Z2+Zf )(Z0 +Zf + 3Zg) Z0 + Z2 + 2Zf + 3Zg Z0 + Zf + 3Zg ( Z0 + Zf + 3Zg ) + (Z2 +Zf ) (Z2 + Zf ) ( Z2 + Zf ) + (Z0 + Zf +3Zg)
Iaf = 0 = Ia0 + Ia1 + Ia2 Ia0 = - (Ia1 + Ia2) Iaf = 0 Ibf = Ia0 + a2Ia1 + aIa2 Icf = Ia0 + aIa1 + a2Ia2 Ia = Ibf + Icf = 3Ia0 Va0 = - Z0 Ia0 Va1 = 1.0 Z1 Ia1 Va2 = - Z2 Ia2 Vaf = Va0 + Va1 + Va2 Vbf = Va0 + a2Va1 + aVa2 Vcf = Va0 + aVa1 + a2Va2 Vab = Vaf Vbf Vbc = Vbf Vcf Vca = Vcf Vaf Va0 = Va1 = Va2 = 1.0 Z1 Ia1 Ia2 = - Va2 Z1 Ia0 = -Va0 Z0
Vab = Vaf Vbf = Vaf Vbc = Vbf Vcf = 0 Vca = Vcf Vaf = -Vaf
a b c
Iaf Zf Ibf Zf Zf Icf
Zg
F0 Va0 Ia0 = 0 Z0
F2
Zf
Va2
Ia2 = 0
Z2
N0 Va1 Ia1 G
F1 Z1
N2
N1
Analysis of Three phase fault (symmetrical) Iao = 0 Ia2 = 0 Ia1 = Iaf Ibf Icf
1.0 0 Z1 + Zf = 1 1 1 1 a2 a 1 a a2 0 Ia1 0
Ia1 = Iaf = Ibf = a2 Ia1 = Icf = a Ia1 = Va0 = 0 Va1 = Zf Ia1 Va2 = 0 Vaf Vbf Vcf =
1 1 1
1 a2 a
1 a a2
0 Va1 0
Vaf = Va1 = Zf Ia1 Vbf = a2Va1= Zf Ia1240 Vbf = aVa1 = Zf Ia1120 Vab = Vaf Vbf = Va1 ( 1- a2 ) = 3 Zf Ia130 Vbc = Vbf Vcf = Va1 ( a2 -a ) = 3 Zf Ia1-90 Vca = Vcf Vaf = Va1 ( a -1 ) = 3 Zf Ia1150
a b c
Zf1 Zf2 Zf3
Zg
Fault point
a b c
Zf1 Zf1 Zf2
Zg
Fault point
a b c
Zf1 Zf2 Zf3
Fault point
a b c
Zf1 Zf2 Zf3
Fault point
a b c
Zf1 Zf2 Zf3
Fault point
a b c
Zf1 Zf2 Zf3
Fault point
a b c
Zf Zf
Zg
Fault point
a b c
Zf Zf
Fault point
a b c
Zf
Zg
Fault point
a b c
Zf Zf
Zg
Fault point
a b c
Zf
Fault point
a b c
Fault point
Fault point
a b c
Zg
Fault point
Fault point
a b c
Zf Zf Zf
Fault point
Fault point
a b c