0% found this document useful (0 votes)
1K views18 pages

Iru Pro

The document describes an AC voltage relay that provides protection functions like under voltage, over voltage, zero-sequence overvoltage, and negative sequence overvoltage. It has three models that vary in their ability to calculate zero sequence, negative sequence, and positive sequence voltages. The relay monitors phase voltages, calculates symmetrical components, and trips three output contacts if voltage thresholds are exceeded. It stores event and fault records, has two setting groups, and displays measurements on its front-face LCD.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views18 pages

Iru Pro

The document describes an AC voltage relay that provides protection functions like under voltage, over voltage, zero-sequence overvoltage, and negative sequence overvoltage. It has three models that vary in their ability to calculate zero sequence, negative sequence, and positive sequence voltages. The relay monitors phase voltages, calculates symmetrical components, and trips three output contacts if voltage thresholds are exceeded. It stores event and fault records, has two setting groups, and displays measurements on its front-face LCD.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

IRU-Pro

AC Voltage Relay 27, 59, 59N, 47, 59D

C&S Electric Limited


(Protection & Control Division)

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Contents
1. 2. 3. 4. Introduction Features & Characteristics Model for Voltage Protection Voltage Protection 4.1 4.2 4.3 4.4 4.5 4.6 5. 6. 7. 8. 9. 10. 11. 12. Under / Overvoltage Zero-sequence overvoltage Negative sequence over voltage Positive sequence over voltage Output Trip contact Front Plate

Setting groups Measurements Event record Fault record Communication User interface Hardware & case Relay testing and commissioning 12.1 12.2 12.3 12.4 12.5. Testing the output relays Test of symmetrical components Wrong phase sequence Phase failure Earth fault

13. 14. 15. 16. 17. 18. 19. 20. 21.

Terminal Description Setting Procedure Technical data VT ratios Accuracy Setting Range Connection diagrams Cases & Dimensions Ordering Information

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

1. Introduction
PRO range of relays provide reliable and high performance protection. The IRU_PRO is a relay for AC voltage supervision with universal application; it protects the three-phase network against over-, under- voltage, unbalance or earth faults in isolated networks. Beside the pure RMS value measurement of the line voltage the IRU_PRO evaluates the symmetrical components (U1, U2 & U0 sequence system). By evaluating these components relay IRU_PRO can detect the phase sequence, voltage unbalance and earth-faults Recording of up to last 100 Events with time stamp. Assignment matrix for output relays for all protections. Suitable for 50Hz/ 60Hz. Single Phase/ Three Phase selection. USB front end interface for PC/Laptop interface. Front-end Live Link simulation support for testing of relay even without three phase injection voltage source. Off line Trip Test mode. Digital filtering of the measured values by using discrete Fourier analysis to suppress higher harmonics and D.C. components induced by faults or system operations. Two Groups of configuration parameter. Protection ANSI: 27, 59, 59N, 47, 59D Voltage supervision each with two step under-/ and over voltage detection. Inverse as well as Definite Trip timing curve selection for under/over voltage. Separate tripping elements for over- and undervoltage and positive sequence system. Over voltage detection in positive, negative- and zero sequence system. Display of measuring values of the line voltages and system voltages U0, U1 and U2 as RMS values. Suitable for Star /Delta connection. VT Ratio for Primary Voltage display configuration. Block on under voltage in case of Power failure (user selectable). Last 10 faults saving in memory for all line voltages and the voltages of the symmetrical components, with time stamp. Wide range SMPS based Auxiliary Supply (24260VAC/24-360VDC). Front IP54 transparent dust cover.

2. Features & Characteristics


Numeric DSP technology based relay.

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

PROTECTION FUNCTIONS OVERVIEW ANSI 27 59 59N 47 59D Phase-to-neutral or phase-to-phase voltage Protection (Delta/star configuration) Phase under voltage Phase over voltage Zero-sequence over voltage Negative sequence over voltage Positive sequence Over voltage Over /Under Voltage Blocking Single/ Three Phase Selection Three output relays Front Communication (USB)

4. Voltage protection
The relay is equipped with an independent, 2-step over(U>, U>>) and under voltage supervision (U<, U<<) simultaneously with separately adjustable tripping values and delay times. Voltage measuring is 3-phase. In this process there is a continuous comparison of the line conductor voltages in case of a delta connection and of the phase voltages in case of a star connection with the preset limit values. The highest voltage is always evaluated for over voltage supervision and the lowest voltage for under voltage supervision. A distinction is made between 1-phase and 3-phase tripping. With 1-phase tripping the voltages are evaluated as follows: U</U<<: Activation cum tripping takes place if at least one phase has fallen short of the tripping value. U>/U>>: Activation cum tripping takes place if at least one phase has exceeded the tripping value. With 3-phase tripping the voltages are evaluated as follows: U</ U<<: Activation cum tripping takes place if all three phases have fallen short of the tripping value. But if pickup occurs in only one or two phase then phase LED of those phases will glow.

3. Model for Voltage Protection


IRU_PRO relays are available in the following configurations:

Model

PTs Zero sequence calculation 3 3 3 Numerical Numerical Numerical External PT

IRU-PRO-O IRU-PRO-U IRU-PRO-UO

Negative Positive sequence sequence U>/ U>>: Activation cum tripping takes place if all three calculation calculation phases have exceeded the tripping value. But if pickup occurs X X in only one or two phase then phase LED of those phases will glow. X X X X

4.1 Under / over voltage


Two thresholds are available for each function: each one can be independently activated or deactivated. If a threshold is activated, it can be configured to detect:

IRU-PRO-UOR 4

UN will be 1/3 times of 110V / 400V in star Under Voltage Protection will not get activated unless 1configuration phase or 3-Phase (depending upon the phase setting in MMI) 230V model is available only in star configuration
crosses the level of the selected scheme : SCH-A / SCH-B/ SCH-C SCH-A : Undervoltage protection is activated without crossing any therhold level.

U<

Pickup Activated at powering

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

SCH-B : Under voltage protection is activated only after voltage goes above the set value of undervoltage pickup.

4.6 Front Plate


At the front of the relay following operating and indicating elements are arranged:

U<

Activated Pickup

SCH -C: Under voltage Protection is activated only after the voltage crosses the set UV theshold level.

Five push switches for set values of normal tripping characteristics including a RESET push switch. Eight LEDs for indicating faults and readiness to operate. LCD display to display settings and running values etc. Running parameters are fundamental voltages for L1,L2,L3 phases, zero sequence voltage Uo , Positive phase sequence voltage U1,Negative phase sequence voltage U2. The RESET switch is provided for acknowledgement and reset of the fault LEDs/Relay.

UV Th U<

Activated Pickup

The eight lamps on the front plate of IRU_PRO have following functions: Lamp ON indicates that the relay is in service. Lamps L1, L2, L3 indicates pickup phase. Lamp U> flash state indicates pickup due to over voltage & steady state indicates trip due to over voltage. Lamp U< flash state indicates pickup due to under voltage & steady state indicates trip due to Under voltage. Lamp Uo> flash state indicates pickup due to zero sequence & steady state indicates trip due to neutral Displacement. Lamp U1/2> flash state indicates pickup due to Positive/Negative sequence component & steady state indicates trip.

NOTE : The IRU_PRO relays provide a block on under voltage (parameter UlossBlk) in case of power failure (voltage lesser than 10% Vn), if Power failure Protection is enabled.

4.2 Zero-sequence over voltage


IRU_PRO relays will operate from the zero sequence voltage, which is calculated internally, or from the residual voltage, which is measured directly or internally U0=1/3| (U 1 +U 2 +U 3 )|

4.3 Negative sequence over voltage


This function is based on the negative-sequence component of the voltage, which is calculated internally and displayed on the screen of the front panel: It is designed to detect any voltage unbalance condition. U2=1/3| (U 1 +a 2 U 2 +aU 3 )|

5. Setting groups
The IRU_PRO relays have two independent setting groups, which can be used to adapt the protection functions to different operating conditions. The switch from one setting group to another will only take effect if no protection is running, to prevent unwanted tripping.

4.4 Positive sequence over voltage


This function is based on the positive phase sequence component of the voltage, which is calculated internally. U1=1/3|(U 1 +aU 2 +a 2 U 3 )|

6. Measurements
Depending on the configuration of the VTs connected to IRU_PRO relays, the following values will be measured and displayed as true RMS values on the back-lit screen: In addition, the IRU_PRO relays calculate the following values internally: phase-to-neutral voltages L1, L2, L3 phase-to-phase voltages L12, L23, L31 Zero sequence voltage U0 Positive sequence voltage U1 Negative sequence voltage U2

4.5 Output Trip Contact


The IRU_PRO is provided with three tripping relay. All three relays can be configure to any fault through relay assignment menu of MMI. Relay reset operation can be configurable in automatic reset or manual reset mode from MMI (man machine interface). In automatic reset mode relay will be reset after the voltage goes below/above the pick-up level for OV & UV. In manual mode relay will be reset by pressing reset button for 1 second if fault has been over.
5

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

7. Event record
Any change of state of logic inputs, output contacts or protection functions will be recorded in the non-volatile memory of the IRU_PRO relays, with a maximum of 100 events. When the memory is full, the oldest events will be deleted, Each event can be retrieved locally to a PC using the IRU_PRO support software through front USB port or can be viewed on LCD.

Star-Connection: Phase-to-neutral voltages: LED L1, L2, L3 Delta-connection: Phase-to-phase voltages: LED L1+L2, L2+L3, L3+L1 Green ON LED flashing indication gives the status of healthiness of protection relay. Five tactile keys for editing/scrolling through the menus with password protection.

8. Fault record
The IRU_PRO relays can store the last 10 faults that have occurred in non-volatile memory. Fault1 is the latest fault. Each record provides the following information: Date and time of fault Origin of fault (under voltage, etc.) Faulted phase(s) Magnitude of phase-to-neutral or phase-to-phase voltages Magnitude of the zero-sequence voltage (if available) Magnitude of the positive sequence voltage (if available) Magnitude of the Negative sequence voltage (if available)

11. Hardware & case


All the models of the IRU_PRO range have a plastic IP54 protected case, and can be flush-mounted in switchboard or panel. External connections are made via Barrier terminal blocks. Each terminal connection is suitable for 8mm ring type lugs with M3.5 screw fixing.

12. Relay testing and commissioning 12.1 Testing the output relays
Select the <TRIP TEST> menu from MMI, It will start operating the LEDs & Contacts one by one, unless the enter key is pressed again.

9. Communication
One communication port is available on IRU_PRO relay based on ordering information. This front USB port provides a local communication with PC. The front end software provided for relay is fully Windows TM compatible. The front end software of IRU_PRO relays has following functions: To edit the parameters of relay To view the running parameters of relay. To download the last 10 faults of relay To download the last 100 Events of relay To Test the complete functionality of all protections of relay without using any three phase injection voltage source

12.2 Test of symmetrical components


For this test the relay has to be correctly connected with all of the three phases and the star point. If the measuring voltage system is symmetrical, the unit should indicate the following measuring values: Measuring Value L1,L2,L3 U1 U2 U0 Indication UN UN 0 0

10. User interface


The user interface for IRU_PRO relays comprises: LCD display of 2 x 16 characters Eight dedicated LEDs to provide information such as Trip, Alarm, Over, Under Voltage protection information.

12.3 Wrong phase sequence


For this test two phases must be reversed. The third phase and the star point N are connected as usual. The theoretical indicating values are: Measuring Value L1,L2,L3 U1 U2 U0
6

Indication UN 0 UN 0

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

12.4 Phase failure


The IRU_PRO is now to be connected with the two phases L2 and L3 and with the neutral conductor. The two phases must be assigned correctly. The measuring input of phase L1 is connected with the star point of the relay in order to prevent interference voltages at the input. (This simulation is realistic because in a real case of failure other relays in parallel or the voltage transformer itself would cause this pull down effect). The test can basically be carried out with any phase. The result of the measurement differs only in the indicating values for the phase voltages L1-L3.

13. Terminal Description


There are two terminal blocks A & B. Block A is for Voltage connection while Block B is for Auxiliary & trip contact connection as per below table.

Measuring Value L1 L2, L3 U1 U2 U0

Indication 0 UN 2/3 x UN 1/3 x UN 1/3 x UN A1 A2 A3 A4 A5 A6 A7 A8

Terminal

Description

A
L1 Voltage Transformer Phase L1 Voltage Transformer Neutral L2 Voltage Transformer Phase L2 Voltage Transformer Neutral L3 Voltage Transformer Phase L3 Voltage Transformer Neutral Residual Transformer Phase Residual Transformer Neutral

12.5 Earth fault


For this test all conductors L1-L3 have to be correctly connected. The star point N from the mains is not connected. Instead the star point of the IRU_PRO is connected with phase L1. This type of connection simulates an earth fault of phase L1.

Measuring Value L1 L2,L3 U1 U2 U0

Indication 0

B
B1 B2 B3 B4 B5 B6 B7 B8 B9 Relay-3 NO Relay-3 COMM Relay-2 NO Relay-2 COMM Relay-1 NO Relay-1 COMM Auxiliary Supply Line (Non polar) Auxiliary Supply Line (Non polar) Earth

3 x UN
UN 0 UN

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

14. Setting Procedure


MENU DISPLAY DISCRIPTION

Menu 1
Default Page (Running Parameters)

L1 L2 L3 U0 U1 U2

:XXX.XX V :XXX.XX V :XXX.XX V :XXX.XX V :XXX.XX V :XXX.XX V

Fundamental voltage of L1phase Fundamental voltage of L2phase Fundamental voltage of L3phase Zero sequence voltage Positive sequence voltage Negative sequence voltage

Menu 2
(Pressing Reset Key)

# EDIT / VIEW MENU# <PROTECTION> <RELAY CONFIG.> <TRIP TEST> <FAULT RECORD> <EVENT RECORD> BACK

Group -1, Group-2 Protection parameters Relay Configuration Setting Trip Testing Fault Record Event Record

Menu 3
(Pressing Reset Key on PROTECTION)

# GROUP SELECTN # <GROUP-1> <GROUP-2> <ACTIVE-GROUP> BACK

Group1 Setting Group2 Setting Change Active Group Back to previous page

# PROTECTION #

Menu 4
( Pressing Reset Key on GROUP-1 OR GROUP-2 Selection )

<Under Voltage> <Over Voltage> <Zero Seq. OV> <Pos./Neg. OV> <Set-up Config.> BACK

Undervoltage parameter setting Overvoltage parameter setting Zero sequence OV parameter setting Positive / Negative sequence parameter setting Relay set-up configuration setting

Menu 5
(Pressing Reset Key on UnderVoltage Selection )

# UnderVoltage # UVchar:DEFT/IDMT UlossBlk:Disable UV-SCH:SCH-A/SCH-B/SCH-C UV-THRE:XXX %Un U<Prot: Disable/Enable U<Pkup:XXX %UN U<Ti:X.XX U<Td:XX.XXs U<<Prot:Disable/Enable U<<Pkup:XXX%UN U<<Td:XX.XXs BACK

Undervoltage Characteristic selection Blocking on loss of voltage enable/disable Undervoltage Protection Scheme selection Undervoltage Threshold selection(for SCH-C) Undervoltage Protection Blocking/unblocking Undervoltage Pickup setting Undervoltage TMS Setting Undervoltage Definite time setting Undervoltage Protection 2nd level Block/unblock Undervoltage Pickup setting for 2nd level Undervoltage Definite time setting for 2nd level

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Setting Procedure
MENU DISPLAY DISCRIPTION

Menu 6
(Pressing Reset Key on OverVoltage Selection )

# OverVoltage# OVchar: DEFT/IDMT U>Prot: Disable/Enable U>Pkup:XXX %UN U>Ti:X.XX U>Td:XX.XXs U>>Prot:Disable/Enable U>>Pkup:XXX%UN U>>Td:XX.XXs BACK # Zero Seq. OV# U0char: DEFT U0>Prot: Disable/Enable U0>Pkup:XXX %UN U0>Td:XX.XXs BACK

Overvoltage Chracteristic selection Overvoltage Protection Blocking/unblocking Overvoltage Pickup setting Overvoltage TMS Setting Overvoltage Definite time setting Overvoltage Protection 2nd level Block/unblock Overvoltage Pickup setting for 2nd level Overvoltage Definite time setting for 2nd level

Menu 7
(Pressing Reset Key on Zero Seq. OV Selection)

Zero sequenceOV Characteristic Zero sequenceOV Protection Blocking/unblocking Zero sequenceOV Pickup setting Zero sequenceOV Definite time setting

# Pos./Neg. OV # U1>Prot: Disable/Enable

Menu 8
(Pressing Reset Key on Pos./Neg. OV Selection )

U1>Pkup:XXX%UN U1>Td:XX.XXs U2>Prot: Disable/Enable U2>Pkup:XXX%UN U2>Td:XX.XXs BACK #Set-up Config. # Nom. Freq. Fn: XX Hz Protectn : 1- PHASE / 3-PHASE VT RATIO : XXXX Wire Config. : STAR / DELTA # GROUP # Active Group G1/ G2 BACK #RELAY CONFIG.# <PASSWORD CHNG> <RELAY ASSIGN> <RELAY RESET> <COMM-ADDRESS> <SET TIME/DATE> <LOAD DEFAULT> <FACTORY SETNG> BACK
9

Positive sequence unbalance Protection Blocking/unblocking Positive sequence OV Pickup setting Positive sequence OV Definite time setting Negative sequence unbalance Protection Blocking/unblocking Negative sequence OV Pickup setting Negative sequence OV Definite time setting

Menu 9
(Pressing Reset Key on Set-up Config. Selection )

50Hz/60Hz Frequency selection Single / Three phase selection VT Ratio Selection for primary voltage display Star / Delta wiring selection

Menu 10
( Pressing Reset Key on ACTIVE-GROUP Selection )

Change the active group

Menu 11
(Pressing Reset Key on RELAY CONFIG. Selection )

Change password Relay Assignment Relay Reset Slave Address Clock Setting Set default setting of relay Factory setting

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Setting Procedure
MENU DISPLAY DISCRIPTION

Menu 12
(Pressing Reset Key on PASSWORD CHNGE selection )

#PASSWORD CHNG# Enter Password XXXX New Password XXXX Re-Password XXXX ! SUCCESS ! Password Changed # RLYAssignment # U< - - U<< - - U> - - U>> - - U1> - - U2> - - U0> - - BACK # RELAY-RESET# AUTO / MANUAL BACK # SLAVE ADDRESS # SlaveAddress: xx BACK

Menu 13
( Pressing Reset Key on RELAY ASSIGN Selection )

Relay assignment for Undervoltage Relay assignment for Undervoltage Level2 Relay assignment for Overvoltage Relay assignment for Overvoltage Level2 Relay assignment for Positive Sequence OV Relay assignment for Negative Sequence OV Relay assignment for Zero Sequence OV

Menu 14
(Pressing Reset Key on RELAY RESET selection )

Relay reset Auto / Manual mode selection

Menu 15
(Pressing Reset Key on SLAVE- ADDRESS selection )

Slave address selection for front communication

Menu 16
(Pressing Reset Key on SET TIME & DATE selection )

# CLOCK # Hour:XXX Min:XXX Sec:XXX Day:XXX Mnt:XXX Year:XXX BACK

To To To To To To

set Hour of clock set Minute of clock set Second of clock set Date of clock set Month of clock set Year of clock

Enter Password (Pressing Reset Key on LOAD XXXX

Menu 17

Set default setting of relay

DEFAULT selection )

Menu 18
(Pressing Reset Key on FACTORY SETNG selection)

Enter Password (Not for user configuration) XXXXXX Enter Password XXXX Offline TRIP Test Press Reset KEY
10

Menu 19
(Pressing Reset Key on TRIP TEST selection )

To test Relay and LED Functioning

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Setting Procedure
MENU DISPLAY DISCRIPTION

Menu 20
(Pressing Reset Key on FAULT RECORD Selection )

#FAULT-MENU# <FAULT-SELECTN> <FAULT-VIEW> <FAULT ERASE> BACK # FAULT-NUMBER # FaultNo: XX BACK # FAULT-VIEW # <F-TYPE>: [F]L1 XXX.XX V [F]L2 XXX.XX V [F]L3 XXX.XX V [F]U0 XXX.XX V [F]U1 XXX.XX V [F]U2 XXX.XX V Hour Min XX:XX Sec Msec XX:XXX <DATE>XX:XX:XX BACK # FAULT-ERASE # ? EraseWARNING ? YES NO CANCEL BACK # EVENT-MENU # <EVENT-SELECTN> <EVENT-VIEW> <EVENT ERASE> BACK # EVENT-NUMBER # EventNo: XX BACK # EVENT VIEW # <E>: Hour Min XXX:X Sec Msec XXX:XX Date XXX:XXX:XX BACK #EVENT-ERASE# ?EraseWARNING ? YES NO CANCEL BACK

Fault number selection To view Fault data To Erase all 10 Faults

Menu 21
( Pressing Reset Key on FAULT-SELECTN)

Fault number selection to view fault details. 1st fault no is latest fault no.

Menu 22
(Pressing Reset Key on FAULT-VIEW Selection)

Type of Fault occured L1 phase voltage at the time of Fault L2 phase voltage at the time of Fault L3 phase voltage at the time of Fault U0 voltage at the time of Fault U1 voltage at the time of Fault U2 voltage at the time of Fault Hour & Minute of Fault Second & millisecond of Fault Date of Fault

Menu 23
( Pressing Reset Key on FAULT ERASE Selection

To Erase all 10 Faults

Menu 24
(Pressing Reset Key on EVENT RECORD Selection)

Event number selection To view Event with its Time stamp To Erase all 100 Events

Menu 25
( Pressing Reset Key on EVENT-SELECTION Selection )

Event number selection to view

Menu 26
( Pressing Reset Key on EVENT VIEW Selection )

Type of Event Hour & Minute of Event Second & millisecond of Event Date of Event

Menu 27
(Pressing Reset Key on EVENT ERASE Selection )

To Erase all 100 Events

11

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

15. Technical data


Mechanical specifications Design Mounting Enclosure Protection Dimensions PC Interface : : : : : Weight approx. 1Kg Rack or flush mounting. Front Panel: IP 54 See dimensions diagram USB type B connector

Ratings Auxiliary voltage SMPS Based 24V 260 VAC / 24V360VDC (Tolarance 5%) Output Relay Contacts The output contacts of the IRU_PRO relays are AgCdO dry contacts. Make and carry Carry Break 40ms) AC : 1250VA AC : 1250 VA inductive (cos O = 0.5) 5A and 300V 10 000 operation minimum 100 000 operation minimum < 10 ms Burdens Voltage circuits IEC 60255-21-1, class 2. IEC 60255-21-2, class 1. IEC 60255-21-3, Class 2. NOMINAL VOLTAGE (UN) Un = 110V Un = 230V Un = 400V : : : <0.25 VA <0.36 VA <0.42 VA 30A for 3s 8A continuous DC : 50W resistive DC : 25W inductive (L/R =

Environmental conditions (Recommended Ambient temperature range) Operating Temperature Range: Continuous Withstand -25 to +55C Limit(Note 1) -25 to +70C. Storage Temperature Range: -25 to +70C Note: The upper limit is permissible not for for continuous period. Solar Radiation: Avoid exposure of the front panel to direct solar adiation. Mechanical environment Vibration Test Shock and Bump Test Seismic Test Product safety

Type tests
S.N.Description of test 1 2 3 4 Standard

Duration Thermal withstand continuous (2x Un)

16. VT ratios
The primary can be independently set for each set of VT inputs, for example the residual VT ratio can be different to that used for the phase voltages. Range is as per below Primary VT Ratio 1- 1000 Step 1

Insulation testI EC 60255-5 Dielectric test IEC 60255-5 5 KV impulse voltage test IEC 60255-5 High freq interference test IEC 60255-22-1 severity class 3 5 Radio interference suppression EN55011 cl 5.1.2 test 6 Radio interference suppression EN55011 cl 5.22.2 test 7 Radiated radio freq IEC 60255-22-3 electromagnetic field immunity test 8 Conductive RF immunity test ENV50141 9 Surge immunity EN61000-4-5 10 ESD test severity class 3 EN61000-4-2 11 Fast transient disturbance test IEC 60255-22-4 12 Power frequency magnetic IEC61000-4-8 Field immunity test

17. Accuracy
MEASUREMENTS ACCURACY at nominal frequency Quantity Phase Voltage Range 0.3xUn to 1.5xUn &<0.3x Un 0.3xUn to 1.5xUn &<0.3xUn Accuracy < 2%< 0.4% Un < 5%< 1% Un

Phase Secquence component

TRIP TIME ACCURACY FOR UNDER/OVER VOLTAGE Operate time accuracy at definite time characteristic: 3% of the set start value or 40 ms. Operate time accuracy at IDMT characteristic: 40 ms or the accuracy appearing when the measured voltage varies 2%.
12

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

18. Setting Range : (IRU -PRO-UOR-XX)


S.No. 1 2 4 5 6 Features Phase selection VT Ratio Wiring Connection Protection Setting Name SINGLE/THREE VT Ratio STAR/ DELTA Characteristic Blocking on loss of volt Undervoltage Protection Scheme Undervoltage threshold U< Protection Blocking U< Pickup setting U< TMS Setting U<Definite time setting U<< Protection Blocking U<< Pickup setting U<<Definite time setting Characteristic U> Protection Blocking U> Pickup setting U> TMS Setting U>Definite time setting U>> Protection Blocking U>>Pickup setting U>>Definite time setting Characteristic U0> Protection Blocking U0> Pickup setting Setting Range 1-1000 Steps 1

Undervoltage U< & U<<

Overvoltage U> & U>>

Zero sequence Over Voltage U0>

IDMT/DEFT Enable/Disable SCH-A/SCH-B/SCH-C 50-100% of Un Enable/Disable 5 - 120% of Un 0.05 .. 2.00 30ms - 20s Enable/Disable 5 - 120% of Un 0.03 - 20 sec IDMT/DEFT Enable/Disable 20 - 150% of Un 0.05 .. 2.00 30ms - 20s Enable/Disable 20 - 150% of Un 0.03 - 20 sec DEFT Enable/Disable 2 - 50% of Un*

5% x Un 1% x Un 0.01 0.01s 1% x Un 0.01s 1% x Un 0.01 0.01s 1% x Un 0.01s 1% x Un

( * IRU-PRO-UOR )
2 - 100% of Un**

(** IRU-PRO-U/O/UO )
9 Positive/Negative sequence Voltage U1 > U2 > 10 11 12 Relay assignment Relay Reset Auto/Manual Slave address U0> Definite time setting U1 > Protection Blocking U1> Pickup setting U1> Definite time setting U2 > Protection Blocking U2> Pickup setting U2> Definite time setting RELAY 1 ,2,3 Auto/Manual 1 - 32 0.03 - 20s Enable/Disable 10 - 100% of Un 0.03 - 10s Enable/Disable 10 - 100% of Un 0.03 - 10s 0.01s 1% x Un 0.01s 1% x Un 0.01s

13

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Inverse Time Delay Characteristic The inverse characteristic is defined by the following formula

TMS V t= VS 1

Where: t = operating time in seconds TMS = time Multiplier Setting V = applied input voltage Vs = relay setting voltage V NOTE: this equation is only valid for ratio< than 0.95 (Under Voltage) VS or ratio > than 1.1 (over voltage)

19. Connection Diagrams

L1

L2

L3

B7

B8

B9

t
U</U> A a A1 A2 B b A3 A4 c A5 A6 VB VY tU</tU> VR

Auxilary Supply

Relay-3

B1 B2

U t

Relay-2

B3 B4

A7 A8 VE

U1> U2> U0> U>>/U<< tU>>/tU<< tU1> tU2> tU0>

Relay-1

B5 B6

*External PT VE (on A7 & A8) will be only in IRU-PRO-UOR Star Connection in IRU-PRO

14

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Delta connection in IRU-PRO

20. Cases & Dimensions

146 136.5

72

68

15

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

Cases & Dimensions

Side View

148

134

36.5

TOP View
136.5 146

Cut out Dimensions Installation Depth : 175mm All dimensions in : mm

16

72

IRU-Pro- : AC Voltage Relay 27,59,59N,47,59D

21. Ordering Information


IRU-PRO Protection: a) 3VT Under voltage b) 3VT Over voltage c) 3 VT Under Over Voltage d) 3 VT + 1 Residual VT Rated Voltage (UN) a) 110V b) 230V c) 400V Relay-2 Contact type a) NO - COMM b) NC - COMM Protection Rated Voltage Relay-2 Contact

U O UO UOR

1 2 4

O C

Model Example: IRU-PRO-UOR-1-C: 3VT+1Residual VT for Un: 110V and Relay-2 contact type is NC -COMM with USB front interface & front end livelink software support

17

C&S Electric Limited


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA) Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413 E-mail: [email protected] Web : www.cselectric.co.in

Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839 BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153 CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003 FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631 NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34