MCC-Size
MCC-Size
STANDARD TIER
RQD. TOTAL MODULES PER ITEM MODULES REQUIRED
STANDARD TIER
RQD. TOTAL MODULES PER ITEM MODULES REQUIRED
ITEM DESCRIPTION DOL <= 15kW DOL >15kW<=55kW DOL >55kW<=110kW DOL >110kW<=250kW S/D <= 15kW S/D >15kW<=55kW S/D >55kW<=110kW S/D >110kW<=250kW VSD <= 15kW VSD >15kW <= 75 kW S-STR >15kW <= 75 kW F/SW TO 63A F/SW 100A F/SW 100A-400A F/SW 400A-800A
NO.OF ITEMS
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 2 3 5 2 4 6 10 5 10 10 1 2 3 5 TOTAL (A)=
1 2 3 5 2 4 6 10 5 10 10 1 2 3 5 69
ITEM DESCRIPTION 400/230v DISBOARD 110v DISBOARD 110 VOLT Tx PLC SPARE MODULES
NO.OF ITEMS
5 2 3
TOTAL (B)= 69 10 7
TOTAL NUMBER OF MODULES REQUIRED SO FAR (A+B)= THE NUMBER OF MODULES PER TIER = NUMBER OF COMPLETE TIERS REQUIRED FOR THESE MODULES = WIDTH OF A TYPICAL STANDARD TIER (mm) = (say 600mm for front and rear access; 800mm for front only access) FULL HEIGHT PANELS
RQD. RQD. PANEL TOTAL RQD.
PANEL DESCRIPTION VSD >75kW<=125kW VSD >125kW S-STR >75kW<=125kW S-STR >125kW ACB METERING
NO.OF PANELS
WIDTH(mm) WIDTH(mm)
NO.OF PANELS
WIDTH(mm) WIDTH(mm)
TOTAL(D)=
RESULTS:
THE ESTIMATED TOTAL OVERALL WIDTH OF THIS SWITCHGEAR / MCC = FOR AN AVERAGE HEAT LOSS PER TIER OR PANEL OF THE ESTIMATED TOTAL HEAT LOSS FOR THIS SWITCHGEAR / MCC = mm
300 2.10
watts kW
NOTES 1. THE MCC WILL BE FRONT AND REAR ACCESS / FRONT ACCESS ONLY / BACK TO BACK 2. LINEUP HEIGHT WILL BE 2200mm OR AS VENDOR 3. LINEUP DEPTH WILL BE 550mm (PLUS 250 FOR CABLE BOXES; 350 FOR S/D CABLE BOXES) 4. CABLE ENTRY WILL BE FROM ABOVE / BELOW 5. MINIMUM CLEARANCE OF 1000mm WILL BE REQUIRED IN FRONT 6. MINIMUM CLEARANCE OF 500mm WILL BE REQUIRED TO REAR 7. THE MCC WILL BE EXTENSIBLE AT BOTH ENDS